D700 QUICK START MANUAL 

4

CAUTION  

WIRING

• Do not install a power factor correction capacitor or surge

suppressor/capacitor type filter on the inverter output side. These
devices on the inverter output side may be overheated or burn out.

• The connection orientation of the output cables U, V, W to the motor

will affect the direction of rotation of the motor.

CAUTION  

TRIAL RUN

• Before starting operation, confirm and adjust the parameters. A

failure to do so may cause some machines to make unexpected
motions.

DANGER 

 USAGE

• When you have chosen the retry function, stay away from the

equipment as it will restart suddenly after trip.

• Since pressing STOP/RESET key may not stop output depending on

the function setting status, provide a circuit and switch separately to
make an emergency stop (power off, mechanical brake operation for
emergency stop, etc).

• Make sure that the start signal is off before resetting the inverter

alarm. A failure to do so may restart the motor suddenly.

• The load used should be a three-phase induction motor only. 

Connection of any other electrical equipment to the inverter output
may damage the equipment.

• Do not modify the equipment.
• Do not perform parts removal which is not instructed in this manual. 

Doing so may lead to fault or damage of the product.

CAUTION  

USAGE

• The electronic thermal relay function does not guarantee protection

of the motor from overheating. It is recommended to install both an 
external thermal and PTC thermistor for overheat protection.

• Do not use a magnetic contactor on the inverter input for frequent

starting/stopping of the inverter. Otherwise, the life of the inverter
decreases.

• Use a noise filter to reduce the effect of electromagnetic interference. 

Otherwise nearby electronic equipment may be affected.

• Take measures to suppress harmonics. Otherwise power supply

harmonics from the inverter may heat/damage the power factor
correction capacitor and generator.

• When a 400V class motor is inverter-driven, please use an

insulation-enhanced motor or measures taken to suppress surge
voltages. Surge voltages attributable to the wiring constants may
occur at the motor terminals, deteriorating the insulation of the
motor.

• When parameter clear or all parameter clear is performed, reset

the required parameters before starting operations. Each parameter
returns to the initial value.

• The inverter can be easily set for high-speed operation. Before

changing its setting, fully examine the performances of the motor
and machine.

• In addition to the inverter’s holding function, install a holding device

to ensure safety.

• Before running an inverter which had been stored for a long period,

always perform inspection and test operation.

• For prevention of damage due to static electricity, touch nearby

metal before touching this product to eliminate static electricity from
your body.

CAUTION  

EMERGENCY STOP

• Provide a safety backup such as an emergency brake which will

prevent the machine and equipment from hazardous conditions if the
inverter fails.

• When the breaker on the inverter input side trips, check for the

wiring fault (short circuit), damage to internal parts of the inverter,
etc. Identify the cause of the trip, then remove the cause and power
on the breaker.

• When any protective function is activated, take the appropriate

corrective action, then reset the inverter, and resume operation.

CAUTION  

MAINTENANCE, INSPECTION AND PARTS 

REPLACEMENT
• Do not carry out a megger (insulation resistance) test on the control

circuit of the inverter. It will cause a failure.

CAUTION  

DISPOSAL

• Treat as industrial waste.

1.2  AVAILABLE MODELS

The main unit incorporates a CPU, memory, input and output terminals 
and power supply.

FR-

hh

-NA

1.3  CAPACITY AND RATING PLATE

Unpack the inverter and check the capacity plate on the front cover 
and the rating plate on the inverter side face to ensure that the product 
agrees with your order and the inverter is intact.

2. INSTALLATION OF THE INVERTER

Enclosure surface mounting. Remove the front cover and wiring cover 
to fix the inverter to the surface.

FR-D710W-008 to 025 
FR-D720-008 to 042
FR-D720S-008 to 042

Rating plate

Inverter type

Input rating

Output rating

Serial number

FR-D740-036-NA

Inverter type

Serial number

Capacity plate

FR-D740-036-NA

Symbol

Voltage Class

D710W

Single-phase 110V class

D720

Three-phase 200V class

D740

Three-phase 400V class

D720S

Single-phase 200V class

Displays the rated current

Front cover

Wiring cover

MitsubishiElectric Automation, Inc.

Summary of Contents for D700

Page 1: ...VARIABLE FREQUENCY DRIVE MODEL D700 QUICK START MANUAL MitsubishiElectric Automation Inc ...

Page 2: ...TING PLATE 4 2 INSTALLATION OF THE INVERTER 4 2 1 PRODUCT CHECKING AND PARTS IDENTIFICATION 5 3 OUTLINE DIMENSION DRAWINGS 5 4 WIRING 6 5 PRECAUTIONS FOR USE OF THE INVERTER 6 6 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 7 7 PARAMETER LIST 7 8 OPERATION PANEL 10 MitsubishiElectric Automation Inc ...

Page 3: ... Do not change the cooling fan while power is on It is dangerous to change the cooling fan while power is on Do not touch the printed circuit board with wet hands Otherwise you may get an electric shock When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering off Never touch the motor terminal etc right after powering off to prevent an electric s...

Page 4: ...rminals deteriorating the insulation of the motor When parameter clear or all parameter clear is performed reset the required parameters before starting operations Each parameter returns to the initial value The inverter can be easily set for high speed operation Before changing its setting fully examine the performances of the motor and machine In addition to the inverter s holding function insta...

Page 5: ...OTE Install the inverter on a strong surface securely and vertically with bolts Leave enough clearances and take cooling measures Avoid places where the inverter is subjected to direct sunlight high temperature and high humidity Install the inverter on a non combustible wall surface 3 OUTLINE DIMENSION DRAWINGS Single phase 110V class Inverter Type W W1 H H1 D FR D710W 008 68 2 68 56 2 20 128 5 04...

Page 6: ...nd insulation and phase to phase insulation of the inverter output side before power on Especially for an old motor or use in hostile atmosphere securely check the motor insulation resistance etc 10 Do not use the inverter input side magnetic contactor to start stop the inverter Always use the start signal turn ON OFF STF STR signal to start stop the inverter 11 Across P and PR terminals connect o...

Page 7: ...nning signal Start signal STF signal STR signal Running signal RUN signal 4 Inverter running status Logic check of the start signal and output current Start signal STF signal STR signal Output current detection signal Y12 signal Backup method outside the inverter Even if the interlock is provided by the inverter status signal enough failsafe is not ensured depending on the failure status of the in...

Page 8: ...eference 0 to 500A Rated inverter current 57 Restart coasting time 0 0 1 to 5s 9999 9999 58 Restart cushion time 0 to 60s 1s 59 Remote function selection 0 1 2 3 0 Parameter Name Setting Range Initial Value 60 Energy saving control selection 0 9 0 0 9 0 65 Retry selection 0 to 5 0 66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz 67 Number of retries at fault occurrence 0 ...

Page 9: ... speed 11 0 to 400Hz 9999 9999 236 Multi speed setting speed 12 0 to 400Hz 9999 9999 237 Multi speed setting speed 13 0 to 400Hz 9999 9999 238 Multi speed setting speed 14 0 to 400Hz 9999 9999 239 Multi speed setting speed 15 0 to 400Hz 9999 9999 240 Soft PWM operation selection 0 1 0 241 Analog input display unit switchover 0 1 1 244 Cooling fan operation selection 0 1 1 245 Rated slip 0 to 50 99...

Page 10: ...18 FR D740 012 to 160 FR D720S 025 to 100 4 The parameter number in parentheses is the one for use with the operation panel FR PA02 02 for the FR E500 series or parameter unit FR PU04 FR PU07 5 The initial value differs according to the voltage class 200V class 400V class 6 Available only for the three phase power input specification model 8 OPERATION PANEL The operation panel cannot be removed fr...

Page 11: ...operate with Setting Dial y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press and for 0 5s 3 Turn until appears refer to the table below for other settings 4 Press to set Flicker Parameter setting complete The monitor display appears after 3s Flickering Flickering Flickering Operation Panel Indication Operation Method Start command Frequency command External...

Page 12: ...layed nor set n SETTING DIAL PUSH Push the setting dial to display the set frequency currently set Appears when PU operation mode or external PU combined operation mode 1 is selected Pr 79 3 y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press to choose the PU operation mode PU indication is lit 3 Press to choose the parameter setting mode PRM indication is l...

Page 13: ...ernon Hills IL 60061 Ph 847 478 2100 Fx 847 478 2253 us MitsubishiElectric com fa en support January 2016 2016 Mitsubishi Electric Automation Inc Specifications subject to change without notice All rights reserved AZ IB 0600367ENG A MitsubishiElectric Automation Inc ...

Reviews: