3-46
Emergency stop input and output etc.
3 Controller
3.6.2 Special stop input (SKIP)
The SKIP is the input signal to stop the robot. Please connect the pin 4, 13 of the CNUSR12 connector
shown in
Table 3-4: Special stop input electric specification
Fig.3-8: Connection of the special-stop-input
Item
Specifications
Internal circuit
Type
DC input
No. of input point
1
Insulation method
Photo-coupler insulation
Rated input voltage
DC24V
Rated input current
Approx. 11mA
Working voltage range
DC 21.6 to 26.4V (Ripple rate within 5%)
ON voltage/ON current
DC 8V or more / 2mA or more
OFF voltage/OFF current
DC 4V or less / 1mA or less
Input resistance
Approx. 2.2k
Ω
Response
time
OFF
→
ON
1ms or less
ON
→
OFF
1ms or less
Common method
1 point per common
External wire connection
method
Connector
330
2.2k
入力
+24V(COM)
1A
1B
Input
4
13
CNUSR12 connector
Note) In the customer's system, do not ground the + side of 24V power supply prepared by customer for
connect to the controller. (related with emergency stop and parallel input/output) If it connects with
the controller under the condition that the + side is grounded, it will lead to failure of controller.
* Refer to
Page 45 "Fig. 3-7: Wiring method to the user
for more details about how to wire a
connector.