6-100
Safety
6 Safety
6.1.7 Examples of safety measures
Two emergency-stop input circuits are prepared on the user wiring terminal block of the controller.
The safety measure examples are shown in
. Create a circuit as shown below for safety
measures. In addition, the figure shows the normal state which is not in the emergency stop state.
[Note] • In the emergency-stop related wiring by the customer, if the coil (is not the contact points) of the
relay prepared by the customer is connected to the controller, please be sure to implement the
measure against the noise by the customer in the coil section. And, please also take the lifetime of
noise suppression parts into consideration.
• Electric specification of the emergency-stop-related output terminal: 24V DC or less, related current
100mA or less.
• In the customer's system, do not ground the + side of 24V power supply prepared by customer for
connect to the controller. (related with emergency stop and parallel input/output) If it connects with
the controller under the condition that the + side is grounded, it will lead to failure of controller.
Fig.6-1: Example of safety measures (wiring example 1)
T/B emergency stop button
Emergency stop switch
(2-contact type)
Peripheral
equippment
Internal emergency stop circuit
Internal power supply 24V
Error output
Mode output
Emergency stop output
Mode selector
switch input
Safety fence
door
Door switch input
CNUSR11
*1
*2
14/7
30/23
13/6
29/22
12/5
28/21
10/3
26/19
11/4
27/20
8/1
24/17
+24V
+24V
+24V
+24V
+3.3V
+3.3V
+3.3V
+3.3V
+3.3V
+3.3V
*1) The CNUSR11 connector is a two-level terminal block, indicating that there are two circuits (channels).
Two terminals (cable insertion holes) need to be used for one circuit.
*2) The T/B emergency stop button connected with the controller.
<Wiring example 1>: Connect the emergency stop switch of peripheral equipment to the controller.
The power supply for emergency stop input uses the power supply in the controller.
<Operation of the emergency stop>
If the emergency stop switch of peripheral equipment is pushed, the robot will also be in the emer-
gency stop state.