1. Size of BC controller’s end connection piping
[Fig. 5.2.2]
Available connection (
ݲ
mark: available)
Model name
(MAIN)BC
CONTROLLER
CMB-P104NU-J1
CMB-P106NU-J1
CMB-P108NU-J1
CMB-P1012NU-J1
CMB-P1016NU-J1
CMB-P108NU-JA1
CMB-P1012NU-JA1
CMB-P1016NU-JA1
CMB-P1016NU-KA1
CMB-P108NU-JA1
CMB-P1012NU-JA1
CMB-P1016NU-JA1
CMB-P1016NU-KA1
SUB BC
CONTROLLER
No available
No available
No available
CMB-P104NU-KB1
CMB-P108NU-KB1
(Qty. 1 to 11)
CMB-P104NU-KB1
CMB-P108NU-KB1
(Qty. 1 to 11)
Outdoor unit Capacity
(E)P72 - 120
ݲ
ݲ
ݲ
ݲ
ݲ
(E)P121 - 336
ݲ
ݲ
ݲ
ݲ
(E)P337 - 432
ݲ
ݲ
BC CONTROLLER / MAIN BC CONTROLLER
SUB BC CONTROLLER
Unit model
High pressure
side*1
Low pressure side*1
Total capacity
of indoor units
High pressure (gas)
side *2
Low pressure (gas)
side *2
Liquid side *2
Outdoor unit side
PURY-(E)P72
ø15.88 (Brazing)
ø19.05 (Brazing)
- P72
ø15.88 (Brazing)
ø19.05 (Brazing)
ø9.52 (Brazing)
PURY-(E)P96
ø19.05 (Brazing)
ø22.2 (Brazing)
P73 - P108
ø19.05 (Brazing)
ø22.2 (Brazing)
PURY-(E)P120
ø28.58 (Brazing)
P109 - P126
ø28.58 (Brazing)
ø12.7 (Brazing)
PURY-(E)P144
ø22.2 (Brazing)
P127 - P144
ø22.2 (Brazing)
PURY-(E)P168
P145 - P216
ø15.88 (Brazing)
PURY-(E)P192
P217 - P234
ø28.58 (Brazing)
PURY-(E)P216
ø22.2(ø28.58)*2
(Brazing)
P235 - P288
ø34.93 (Brazing)
ø19.05 (Brazing)
PURY-(E)P240
ø34.93 (Brazing)
P289 - P360
ø41.28 (Brazing)
PURY-(E)P264
ø28.58 (Brazing)
P361 -
ø34.93 (Brazing)
PURY-(E)P288
*1. The maximum total capacity of indoor units that can be connected to each Sub BC
controller is P126.
*2. Use separately sold parts if the pipe diameter is not appropriate.
PURY-(E)P312
ø41.28 (Brazing)
PURY-(E)P336
*1. Use separately sold parts if the pipe diameter is not appropriate.
*2. If the length of high-pressure pipe A exceeds 65 m (213 ft), use the
ø28.58 (ø1-1/8) pipes for all pipes after 65 m (213 ft).
D
D
D
D
D
H
D
A B
F
*2
G
*1
E
05-54
72-96
*3
C
A
To outdoor unit (MAIN BC CONTROLLER)
B
End connection (brazing)
C
BC controller (MAIN BC CONTROLLER / SUB BC CONTROLLER)
D
Indoor
unit
E
Less than 18
F
Combined piping kit (Model name: CMY-R160-J1)
G
Twinning pipe (Model name: CMY-Y102S-G2)
H
Up to three units for 1 branch hole; total capacity: below 54 (but same in cooling/heat-
ing mode)
The size of BC controller’s branch piping is for 24 to 54 type indoor units.
Therefore, if you want to connect indoor units other than the above, connect pip-
ing following the procedures below.
*1. For connecting 06 to 18 type indoor units
Refer to Fig. 5.2.1.
Note:
8VHRQO\WKHÀDUHQXWVVXSSOLHGZLWKWKH%&FRQWUROOHU
*2. To connect a unit with a capacity of higher than 54.
After combining two branches using an optionally available piping kit
(CMY-R160-J1), connect indoor units.
*3. Connection of plural indoor units with one connection (or joint pipe)
Total capacity of connectable indoor units: Less than 54 (Less than 96 with
joint pipe)
Number of connectable indoor units: Maximum 3 Sets
Twinning pipe: Use the twinning pipe for CITY MULTI Y Series (CMY-
Y102S-G2)
Selection of refrigerant piping
Select the size according to the total capacity of indoor units to be installed
downstream.
(Unit: mm [in])
Total capacity of indoor units
Liquid line
Gas line
Below 54
ø9.52 [3/8]
ø15.88 [5/8]
55 to 72
ø19.05 [3/4]
73 to 96
ø22.2 [7/8]
2. Connecting to out side pipes
For PURY-P72, 96, 120, 144, 168, 192, 216, 240, 264, 288, 312, 336
[Fig. 5.2.3]
(Unit: mm [in])
High pressure/low pressure piping diagram
D
A
B
C
E
A
Connection pipe of outdoor unit
(Low pressure)
B
Connection pipe of outdoor unit
(High pressure)
C
Drain piping (NPT 3/4 in)
D
Connection pipe of indoor unit (Liquid)
E
Connection pipe of indoor unit (Gas)
Note:
Be sure to use non-oxidative brazing.