4
GB
2. Items to be used
2.1. Package
contents
The table below lists all the items and their quantities included in the package.
Model name
CMB-
P104NU-J1
P106NU-J1
P108NU-J1
P1012NU-J1
P1016NU-J1
CMB-
P108NU-JA1
P1012NU-JA1
P1016NU-JA1
CMB-
P1016NU-KA1
CMB-
P104NU-KB1
P108NU-KB1
Item
Qty
1
Washer for
construction
2 kinds
(4 each)
2 kinds
(4 each)
2 kinds
(4 each)
2 kinds
(4 each)
2.2. Commercially available items
The table below lists the items not included in the package but required for in-
stallation, and their required quantity.
Hanging bolt ø10 or Anchor bolt M10
4
Nut
4
Double nuts
4
Insulating material
1
3. Selecting an installation site
3.1. About the product
Warning:
Do not use refrigerant other than the type indicated in the manuals
provided with the unit and on the nameplate.
'RLQJVRPD\FDXVHWKHXQLWRUSLSHVWREXUVWRUUHVXOWLQH[SORVLRQRU¿UH
during use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible
for malfunctions or accidents resulting from the use of the wrong type of
refrigerant.
This unit uses R410A-type refrigerant.
Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using
R410A is higher. Refer to the Data Book for more information.
Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A.
Refer to the Data Book for more information.
Do not use the existing piping, as it contains chlorine, which is found in
conventional refrigerating machine oil and refrigerant. This chlorine will
deteriorate the refrigerant machine oil in the new equipment. The existing
piping must not be used as the design pressure in systems using R410A
is higher than that in the systems using other types of refrigerant and the
existing pipes may burst.
3.2. Installation
site
Install the unit in a place not exposed to rain. The BC controller is designed
to be installed indoors.
Install the unit with adequate space around it for servicing.
Do not install the unit in a place that would result in the piping length
restrictions being exceeded.
Install the unit in a place not exposed to direct radiant heat from other heat
sources.
Do not install the unit in any oily steamy place or near any machine that
JHQHUDWHV KLJK IUHTXHQFLHV 'RLQJ VR PD\ FDXVH D ULVN RI ¿UH HUURQHRXV
operation or dew drop.
Install the unit in a location where the noise from the unit will not be a
problem. (Install indoor unit and BC controller at least 5 m [16-3/8 ft] away
from each other when installed in a space with low background noise, e.g.,
hotel rooms).
Allow enough space and access to ensure water piping, refrigerant piping
and electrical wiring can be easily connected.
$YRLGSODFHVH[SRVHGWRWKHJHQHUDWLRQLQÀRZDFFXPXODWLRQRUOHDNDJHRI
ÀDPPDEOHDQGVXOIXULFJDVHV
Ensure a downward gradient of at least 1/100 for drain piping.
Properly install the unit on a stable, load-bearing surface.
Some combination of BC controller and outdoor unit cannot be used.
Refer to the table below for details.
Do not install the unit in a place subject to a large amount of steam. Using
the unit in a humid environment may cause condensation during a cooling
operation.
Combination of BC controller and outdoor unit
Outdoor unit
BC controller
J type
JA type
KA type
KB type
P72 to P126
A
A
A
A
P127 to P336
N/A
A
A
A
P337 to P432
N/A
N/A
A
A
A:available N/A:Not available
1. For hanging from the ceiling
[Fig. 3.2.1]
Provide an inspection hole 450 mm [17-23/32 in] square in the ceiling surface
as shown in [Fig.3.2.1].
Install the unit in a suitable location (such as in the ceiling of a corridor or in
the bathroom etc) away from places regularly occupied. Avoid installing in
the center of a room.
Ensure a pull out strength of at least 60 kg [133 LBS] per bolt for hanging
bolts.
Be sure to install BC controllers level.
Install the unit in a location where the noise from the BC controller will not
directly be heard.
Warning:
Be sure to install the unit in a place that can sustain the entire weight.
If there is a lack of strength, it may cause the unit to fall down, resulting in
an injury.
Caution:
Be sure to install the unit level.