NECS-ME
HFC R410A
2.6 Control unit with LCD display (standard)
The new “W3000 Base” control unit is installed on all NECS-ME
0152..0612 units.
The new “W3000SE Compact” control unit is installed on all
NECS-ME 0604..1604 units.
Main functions
: QuickMind, local and remote FWS supervi-
sion, dual set point management, etc, confi rm Climaveneta’s
commitment to continually developing its electronics technol-
ogy.
The heat pumps, moreover, are fi tted with the original Cli-
maveneta defrosting control system called “Autotuning Defrost”
which considerably reduces defrosting times, thus improving
the energy performance of the unit. Interfaces with BMS sys-
tems: METASYS®, MODBUS®, LONWORKS®, SIEMENS®,
TREND®.
Black Box
logs data relative to 200 alarm events which can be
printed with a personal computer.
QuickMind
is a special control unit which monitors the main
operating parameters, predicts system behaviour and antici-
pates unit settings in order to constantly optimise performance;
it allows both return and delivery water temperatures to be
chosen as adjustment parameters. It can reduce outlet tem-
perature fl uctuations even with a small amount of water in
the system. When, for dual-compressor chillers featuring a
maximum of 12 start-ups per hour and using a traditional ad-
justment system, the minimum recommended water content
is 5.5 l/kW. QuickMind ensures the same chiller operates cor-
rectly even with a water content of just 2.5 l/kW and considera-
bly reduces outlet temperature fl uctuations. The above graph
shows that outlet temperature fl uctuations with QuickMind are
limited to 4.3 °C as opposed to 7.54°C if the traditional adjust-
ment system were used, without even ensuring an acceptable
minimum compressor start time.
2
3
5
4
6
5.9
4.56
7.54
11.34
3
3
3.9
3.3
3.2
3.1
7
8
10
9
T
emperatura in uscita (°C)
Variazione temperatura in uscita
11
12
0.5
1.5
2.5
3.5
4.5
5.5
6.5
7.5
8.5
9.5
4.3
3.5
3
11
10.5
3.52
3.52
3.52
3.52
3.52
3,68
3.52
Tempo minimo di accensione compressore non accettabile
Regolazione a gradini
Quickmind
Variation output temperature
Output temperature (°C)
Minimum water content in the plant lt/kW
Not acceptable minimum starting time compressors
Step-wise regulation