10. REMOTE CONDENSERS
The new Climaveneta’s remote condensers NCE type are
available within three different acoustical versions:
standard version /B
•
low-noise version /LN
•
super-silenced version /SL
•
All versions are available for both horizontal (H) and vertical (V)
air fl ow installation.
The NCE remote condensers are provided with a single ventila-
tion management. The choice of the number of circuits affects
the refrigerant connections and / or the quantity of electrical
signals provided to the fans speed management, according to
the selected version.
Standard version (/B)
Unit equipped with 6 poles motor fan and D connections (Del-
ta).
Fan speed management based on phase cutoff control is avai-
lable as option. In this confi guration the units comes standard
with a built-in electrical board.
Low-noise version (/LN)
Unit equipped with 6 poles motor fan and Y connections
(Star).
Fan speed management based on phase cutoff control is avai-
lable as option. In this confi guration the units comes standard
with a built-in electrical board.
Super-silenced Version SUPER-SILENZIATA (/SL)
Unit equipped with 8 poles motor fan and Y connections
(Star).
Fan speed management based on frequency control is avai-
lable as option (inverter). In this confi guration the units comes
standard with a built-in the electrical board.
10.1 Electrical board
The NCE remote condensers come standard without any elec-
trical board. The NCE are provided with a junction box which
includes the electrical connections of the fans.
The electrical board is provided as standard with all the fans
speed management options (phase cutoff signal and inverter
control), provided with all here below listed components:
main switch
•
fuses on mains
•
system on/off light signalling
•
power contactor for fans on/off
•
control circuit transformer
•
protection fuses on both primary and secondary circuits
•
auxiliary relay for thermal protection remote signalling.
•
10.2 Product code
NCE
3
2
8
C
/B
-
H
1C
E
R
A
NCE
3
2
8
C
/B
H
1C
E
Remote condensers type:
NCE
= for NECS-ME units working with R410A refrige-
rant
Number of fans per row
Number of fan rows
Diameter of fans:
6
= 630 mm
8
= 800 mm
Number of coil rows:
2 rows =
A
3 rows =
B
4 rows =
C
Noise level:
/B
= standard version
/LN
= quiet version
/SL
= super-silenced version
Air fl ow:
H
= horizontal
V
= vertical
Number of refrigerant circuits:
1C
2C
Electrical connections:
E
= junction box
Q
= with built-in electrical board (standard with fan each
speed management)
R
A
Fan speed management:
R
= phase cutoff control (/B and /LN version)
Z
= inverter control (/SL version only)
Anti-vibration mountings
Note
:
Values indicated into outlined cells may not be included
B1
NECS_ME_0152_1604_201004_GB
NECS-ME
HFC R410A
Summary of Contents for CLIMAVENETA NECS-ME 0152
Page 35: ......