6.
ELECTRICAL DATA
Maximum values
Size
n
Compressor
Total unit (1) (2)
F.L.I.
[kW]
F.L.A.
[A]
L.R.A.
[A]
F.L.I.
[kW]
F.L.A.
[A]
S.A.
[A]
0152
2
2x9
2x15.3
2x95
18
30.6
110
0182
2
2x10.1
2x16.4
2x111
20.2
32.8
127
0202
2
2x11.8
2x20.4
2x118
23.6
40.8
138
0252
2
2x13.2
2x22.6
2x118
26.4
45.2
141
0262
2
2x14.4
2x25.5
2x140
28.8
51
166
0302
2
2x17
2x30.5
2x173
34
61
204
0352
2
1x17+1x22.3
1x30.5+1x36.1
1x173+1x225
39.3
66.6
256
0412
2
2x22.3
2x36.1
2x225
44.6
72.2
261
0452
2
1x22.3+1x27.4
1x36.1+1x45.8
1x225+1x272
49.7
81.9
308
0512
2
2x27.4
2x45.8
2x272
54.8
91.6
318
0552
2
1x27.4+1x35.8
1x45.8+1x58.9
1x272+1x310
63.2
104.7
356
0604
4
4x17
4x30.5
4x173
68
122
265
0612
2
2x35.8
2x58.9
2x310
71.6
117.8
369
0704
4
2x17+2x22.3
2x30.5+2x36.1
2x173+2x225
78.6
133.2
322
0804
4
4x22.3
4x36.1
4x225
89
144.4
333
0904
4
2x22.3+2x27.4
2x36.1+2x45.8
2x225+2x272
99
163.8
390
1004
4
4x27.4
4x45.8
4x272
110
183.2
409
1104
4
2x27.4+2x35.8
2x45.8+2x58.9
2x272+2x310
126
209.4
461
1204
4
4x35.8
4x58.9
4x310
143
235.6
487
1404
4
2x35.8+2x46.5
2x58.9+2x73.6
2x310+2x394
164.6
265.0
585
1604
4
4x46.5
4x73.6
4x394
186
294.4
615
F.L.I. Full load power input at max admissible condition
F.L.A. Full load current at max admissible condition
L.R.A. Locked rotor amperes for single compressor
S.A. Starting current
(1) Values calculated referring to the version with the maxi-
mum number of fans working at the max absorbed current
(2) Safety values to be considered when cabling the unit for
power supply and line-protections
Power supply:
400/3/50
Voltage tolerance:
10%
Maximum voltage unbalance: 3%
19
NECS_ME_0152_1604_201004_GB
NECS-ME
HFC R410A
Summary of Contents for CLIMAVENETA NECS-ME 0152