32
i-BX-(Y)_i-BX-N-(Y)
EN
INSTALLER CONNECTIONS
I A
BT8 Domestic hot water storage temperature probe
The DHW storage tank probe, supplied as an accessory,
must be enabled by setting parameter 0232.
The domestic hot water temperature inside the storage tank
is measured using probe BT8.
33 25
BT8
32 25
SA7
Contact SA7 configured as “boiler backup”
The boiler backup function must be configured for only
one of the configurable contacts listed.
Description
Enable contact as:
- DHW FLOW-SWITCH
- BOILER BACkUP
- DEHUMIDIFIER
Menu
Mn01
Parameter
no.
011C
Value to be
set
BOILER
BACkUP
UOM
-
Description
Enable DHW storage tank
probe BT8 (it is enabled auto-
matically when DHW produc-
tion is enabled).
Menu
02
Parameter
no.
0232
Value to be
set
YES
UOM
-
BT9 Storage tank water temperature probe
The DHW storage tank probe, supplied as an accessory,
must be enabled by setting parameter 0314.
The heat pump works so as to reach the water temperature
set point based on the value measured by the “Buffer T.
probe”.
The storage tank probe is only compulsory if an external
auxiliary source for the system needs to be managed (for
example, an electric heater or boiler).
34 25
BT9
Description
Enable storage tank probe
BT9
Menu
03
Parameter
no.
0314
Value to be
set
YES
U.M.
-