SYSTEM CONFIGURATION
U I A
Description
Menu
Parameter
no.
Default
Write set value
UOM
Select system configuration
Enable zone management
NOT = Disabled
YES = Enabled
Mn01
016A
NOT
YES
-
System type (table 1)
Mn01
0101
0
3*
-
Mixing valve ZONE 1
Type of mixing valve 1= 0-10V
Mn01
012T
0-10
HEATING compensation curve ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0167
NOT
Heating compensation curve number
Mn01
0174
0,7
Enable room temperature influence
NOT = Disabled YES = Enabled
Mn01
0178
NOT
Room Authority
Mn01
0179
30
%
MINIMUM set point limit for curve
Mn01
0180
23
°C
MAXIMUM set point limit for curve
Mn01
0181
45
°C
COOLING compensation curve of ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0169
NOT
Maximum temperature set point limit in cooling mode (Tm1)
Mn01
0132
20
°C
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Mn01
0133
23
°C
Minimum temperature set point limit in cooling mode (Tm2)
Mn01
0134
18
°C
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
Mn01
0135
36
°C
HUMIDITY CONTROL ZONE 1
Enable compensation for room humidity, ZONE LT1
NOT = Disabled YES = Enabled
Mn01
0171
NOT
Room relative humidity value to start increasing water temperature
set point
Mn01
0172
70
%
Maximum outlet temperature hysteresis corresponding to 100%
relative humidity
Mn01
0173
15
°C
Enable contact kA11 as DEHUMIDIFIER (The contact closes and the
dehumidifier is activated when the humidity measured by the probe on
the A5 room controller exceeds the value set for parameter 0172)
Mn01
011B
DEHUMIDIFIER
HEATING compensation curve ZONE 2
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0152
NOT
-
Compensation curve number
Mn01
0159
1
-
Enable room temperature influence
NOT = Disabled
YES = Enabled
Mn01
0163
NOT
-
Room Authority
Mn01
0164
30
%
MINIMUM set point limit curve
Mn01
0165
30
°C
MAXIMUM set point limit curve
Mn01
0166
48
°C
COOLING compensation curve ZONE 2
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0154
NOT
-
Maximum temperature set point limit in cooling mode (Tm1)
Mn01
0128
20
°C
Minimum outside temperature corresponding to max.
temperature (Te1)
Mn01
0129
23
°C
Minimum temperature set point limit in cooling mode (Tm2)
Mn01
0130
18
°C
Maximum outside temperature corresponding to min.
temperature (Te2)
Mn01
0131
36
°C
ZONE 2 room controller address setting
addr
1
11*
Device address setting
Low temperature ZONE LT1 room control unit address setting
addr
1
14
High temperature ZONE HT1 room control unit address setting
addr
1
11
System number 3
Parameter configuration
The SYSTEM compensation curve in HEATING mode, parameter 0159, must be set so as to reach an outlet temperature suitable for the high
temperature zone with radiators. The mixed zone is managed according to the compensation curve set for parameter 0174.
The room unit (A5), supplied as standard with the heat pump, controls the room temperature in zone 1, with radiant panels, the additional room
unit (accessory) controls the room temperature in zone 2, with radiators or fan coils.
Enable contact HL1 as secondary circuit pump:
- RELAY ALARM
- DEHUMIDIFIER
- AT1 PUMP
- SUMMER/WINTER
Mn01
015A
RELAY
ALARM
AT1 PUMP
EN
i-BX-(Y)_i-BX-N-(Y)
71
* obligatory values for the present configuration