i-BX-(Y)_i-BX-N-(Y)
79
INSTALLER OPERATIONS CHECKLIST
U I A
Checks (as described in the paragraph on "Checking and starting up the unit")
• Water connections have been carried out as indicated in the installation manual
• All water connections are tight
• All electrical connections are tight
• Make sure the water circuit has been washed and drained
• There is no air in the system (vent if necessary)
• The valves on the water circuit are open
• Electrical connections have been carried out correctly
• Voltage is within a tolerance of 10% of the rated voltage for the unit
• Unbalance between phases is less than 2%, for three-phase units
• Maintenance clearances comply with the specifications in the Installation manual under the section on
POSITIONING
• Power supply electrical complies with the data on the rating plate and specified in the Installation manual under
the section on MAINS POWER SUPPLY CONNECTION
• The system water content complies with the specifications in the Installation manual under the section on
WATER CONNECTIONS
• Suitable water flow-rate for operation of the entire unit is guaranteed as specified in the Installation manual
under the section on WATER CONNECTIONS
• (Air-to-water units only) The system has been protected with antifreeze, respecting the quantities shown in the
Installation manual under the section on WATER CONNECTIONS
• The DHW storage tank has been fitted with an electric heater for Legionella prevention
CHECKED
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
It is hereby declared that the site and access to the site where the unit to be operated or serviced is installed has been made
safely accessible in compliance with all safety standards specified by Italian law 81/08 in force. A supervisor must be present on
site to inform workers of residual risks in the workplace.
WARNING:
Failure to complete commissioning due to causes not attributable to the unit will require a second visit, to be charged to the cus-
tomer directly by the local service centre.
Installer's signature ___________________________________________________ Date ________________________