22
i-BX-(Y)_i-BX-N-(Y)
EN
INSTALLER CONNECTIONS
I A
Solution 2
System with heat pump and outlet electric heater WITHOUT
storage tank.
Position probe BT9 on the system outlet pipe.
25 34
12 22
230V / 400V
BT9
2
Outlet electric heater control
(i-BR-N only) (only if boiler is not enabled)
A) REPLACEMENT:
The electric heater is enabled when
the outside temperature is less than the value of parameter
0304 and the compressor is off, figure 3.
To enable heater activation in REPLACEMENT mode set
parameter 0303 = 1 and 010G = 1.
Electric heater operation reflects the trend in water outlet
temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm, the electric
heater is activated automatically regardless of the outside
air temperature.
In REPLACEMENT mode the electric heater activation
delay time is ignored, and the device is activated immediate-
ly if necessary.
B) SUPPLEMENTARY:
the electric heater operates in sup-
plementary heating mode, together with the compressor, to
satisfy the heating load.
Supplementary heating for low outside air temperature
The electric heater is enabled only when the outside tem-
perature is less than the value of parameter 0304, figure 3.
To enable supplementary heating for low outside air temper-
ature set parameter 0303 = 1 and 010G = 0
Electric heater operation reflects the trend in water outlet
temperature, as shown on the graph in figure 4.
Description
Activation electrical heater
0 = Electrical Heater not enabled
1 = Electrical Heater enabled
Type of outlet electric heater
operation
0 = Supplementary
1 = Replacement
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
electric heater
Minimum outside air temperature
for heat pump operation
Electric heater delay time
(allows the heat pump to reach
steady operation and thus avoid
activating the heater when not
needed)
Integration time to activate outlet
electric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0303
0304
0311
0616
0617
Value to be
set
1
0
1
Example
-5°C
-20 (default)
to be set*
60
600
UOM
°C
°C
min.
°C*sec
Outlet electric heater operating parameters in REPLACE-
MENT mode
Outlet electric heater operating parameters in SUPPLE-
MENTARY mode for OUTSIDE AIR TEMP.
Set the parameters following the sequence described in
the table
Set the parameters following the sequence described in
the table
Description
Activation electrical heater
0 = Electrical Heater not enabled
1 = Electrical Heater enabled
Type of outlet electric heater oper-
ation
0 = Supplementary
1 = Replacement
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
electric heater
Minimum outside air temperature
for heat pump operation
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Parameter
no
0300
010G
0303
0304
0311
Value to be
set
1
1
1
Example
-5°C
= value 0304
UOM
°C
°C
* set the value to the desired switch-off point