EN
VISUAL INSPECTION
When the items are consigned
by the carrier:
- make sure that the goods delivered correspond to the
description on the delivery note, comparing this against
the data on the packaging label.
- make sure the packaging and the unit are intact.
If damage or missing components are noted, indicate this on
the delivery note. A formal complaint should be sent via fax
or registered post to the After Sales Department within eight
days from the date of receipt of the items.
HANDLING PACKAGED UNITS
The unit should always be handled by qualified personnel
using equipment adequate for the weight of the unit, in com-
pliance with the safety standards in force (and subsequent
amendments).
•
Lifting by forklift (1)
Insert the forks under the long side of base, opening the
forks as fare as possible.
•
Lifting by crane (2)
To lift the unit, insert tubes long enough to allow position-
ing of the lifting slings and safety pins in the special feet
on the unit.
For the sizes of these tubes, see the figures shown in the
corresponding section. To avoid the slings damaging the
unit, place protection between the slings and the unit.
STORING THE UNITS
The units must be stored sheltered from direct sunlight, rain,
wind or sand.
Avoid exposing the units to direct sunlight, as the pressure
inside the refrigerant circuit may reach dangerous values
and cause the activation of the safety valves, where fitted.
The units cannot be stacked.
RECEIVING AND HANDLING THE PRODUCT
I A
H
P
L
Bar code
(compressor side)
1
2
i-BX-(Y) dimensions and packaged weight
Size
04
06
08
10
13
15
20
25
30
35
Dimension L
mm
990
990
990
990
990
990
1530
1530
1530
1780
Dimension P
mm
490
490
540
540
540
540
700
700
700
800
Dimension H
mm
1090
1090
1390
1390
1390
1540
1400
1900
1900
1900
Weight
kg
90
95
110
125
140
155
210
270
290
325
Max no. of stackable units No.
1
1
1
1
1
1
1
1
1
1
i-BX-(Y) dimensions and weight with wooden crate
Size
04
06
08
10
13
15
20
25
30
35
Dimension L
mm
1040
1040
1040
1040
1040
1040
1630
1630
1630
1880
Dimension P
mm
545
545
595
595
595
595
750
750
750
850
Dimension H
mm
1170
1170
1470
1470
1470
1620
1450
1950
1950
1950
Weight
kg
115
120
140
155
170
190
250
320
340
380
Max no. of stackable units No.
1
1
1
1
1
1
1
1
1
1
i-BX-N-(Y) dimensions and packaged weight
Size
04
06
08
10
13
15
20
25
30
35
Dimension L
mm
990
990
990
990
990
1530
1530
1530
1530
1780
Dimension P
mm
490
490
540
540
540
700
700
700
700
800
Dimension H
mm
1090
1090
1390
1390
1540
1400
1400
1900
1900
1900
Weight
kg
95
100
115
130
150
200
225
285
310
345
Max no. of stackable units No.
1
1
1
1
1
1
1
1
1
1
i-BX-N-(Y) dimensions and weight with wooden crate
Size
04
06
08
10
13
15
20
25
30
35
Dimension L
mm
1040
1040
1040
1040
1040
1630
1630
1630
1630
1880
Dimension P
mm
545
545
595
595
595
750
750
750
750
850
Dimension H
mm
1170
1170
1470
1470
1620
1450
1450
1950
1950
1950
Weight
kg
120
125
145
160
185
240
265
335
360
400
Max no. of stackable units No.
1
1
1
1
1
1
1
1
1
1
Summary of Contents for Climaveneta i-BX 010-035T
Page 80: ...COD C010029430_04 ...