background image

8

GB

[Fig. 7.0.1]

1

 P72  

 

 

 

 

 

 

3

 P120, P144

40°

Slings
(Min. 8 m [26 ft.] x 2)

50 mm [1-31/32 in.] or 

thicker protective pads
(two each in the front  

and back)

Protective pads
(two each in the 

front  and back)

Sling holes

(two each in the front  and back)

Fan guard

Slings
(Min. 8m [26 ft.] x 2)

50 mm [1-31/32 in.] or 

thicker protective pads
(two each in the front  

and back)

Protective pads
(two each in the 

front  and back)

Sling holes
(two each in the front  and back)

Fan guard

40°

2

 P96

Slings
(Min. 8m [26 ft.] x 2)

50 mm [1-31/32 in.] or 

thicker protective pads
(two each in the front  

and back)

Protective pads
(two each in the 

front  and back)

Sling holes
(two each in the front  and back)

Fan guard

40°

7.  Transporting the unit

8.  Installation of unit

A

Field-supplied M10 anchor bolt

B

Corner is not seated.

C

Fixing bracket for the hole-in anchor bolt (3 locations to 

fi

x with screws)

D

Anti-vibration rubber 
Install it so that the rubber covers the entire width of the unit leg.

Fix unit tightly with bolts so that unit will not fall down due to earthquakes or 
strong winds.

Use concrete base or an angle bracket as the foundation of unit.

Vibration may be transmitted to the installation section and noise and 
vibration may be generated from the 

fl

oor and walls, depending on the 

installation conditions. Therefore, provide ample vibrationproo

fi

ng (cushion 

pads, cushion frame, etc.).

Build the foundation in such way that the corner of the installation leg is 
securely supported as shown in the 

fi

gure. (Fig. 8.1.1) 

When using a rubber isolating cushion, please ensure it is large enough to 
cover the entire width of each of the unit's legs. If the corners are not 

fi

rmly 

seated, the installation feet may be bent.

When using cushion pads, be sure that the full width of the unit is covered.

The projecting length of the anchor bolt should be less than 30 mm [1-3/16 in].

Post-installed anchor bolts (i.e., bolts not 

fi

rmly cemented into the base) are 

not compatible with this product unless 

fi

xing brackets are 

fi

rst mounted on 

the four locations (six locations: P120, 144).

8.1. Installation

[Fig. 8.1.1]

A

B

C

30 mm

[1-3/16 in.]

D

 

Use suspension ropes that will withstand the weight of the unit.

When moving the unit, use a 

4-point suspension

, and avoid giving impacts 

to the unit (Do not use 

2-point suspension

).

Place protective pads on the unit where it comes in contact with the ropes to 
protect the unit from being scratched.

Use a 50 mm [1-31/32 in.] or thicker cardboard or cloth as a protective pad 
on the top of the unit to prevent contact between the fan guard and slings.

Set the angle of roping at 40

˚

 or less.

Use 2 ropes that are each longer than 8 m [26 ft].

 Caution:

Be very careful when carrying/moving the product.

-  When installing the outdoor unit, suspend the unit at the speci

fi

ed location of 

the unit base. Stabilize as necessary so that it does not move to the side and 
support it at 4 points. If the unit is installed or suspended with 3-point support, 
the unit may become unstable and fall.

Summary of Contents for City Multi PUHY-P120TKMU-A

Page 1: ... air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte Air Conditioners For Building Application Inverter Y Series OUTDOOR UNIT PUHY P TKMU A BS PUHY P YKMU A BS For use with R410A ...

Page 2: ...tric shock or fire Never attempt to repair the unit without the proper qualifications If the air conditioner must be repaired consult the dealer contractor or qualified Refrigeration Engineer If the unit is repaired improperly water leakage electric shock or fire may result Do not touch the heat exchanger fins Improper handling may result in injury If refrigerant gas leaks during installation work...

Page 3: ... conditioner with the panels and guards removed Rotating hot or high voltage parts can cause injuries Do not reconstruct or change the settings of the protection devices If the pressure switch thermal switch or other protection device is shorted or operated forcibly or parts other than those specified by Mitsubishi Electric are used fire or explosion may result To dispose of this product consult y...

Page 4: ... A BS PUHY P96YKMU A BS PUHY P72YKMU A BS PUHY P312YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P72YKMU A BS PUHY P336YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P96YKMU A BS PUHY P360YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P144 to P360YSKMU A BS require Twinning Kit to connect component unit modules in the field 2 About the product This unit use...

Page 5: ...40TSKMU A BS PUHY P264TSKMU A BS PUHY P288TSKMU A BS PUHY P312TSKMU A BS PUHY P336TSKMU A BS PUHY P360TSKMU A BS PUHY P240YSKMU A BS PUHY P264YSKMU A BS PUHY P288YSKMU A BS PUHY P312YSKMU A BS PUHY P336YSKMU A BS PUHY P360YSKMU A BS Sound level 60Hz 63dB A 63 5dB A 64dB A 64 5dB A 64 5dB A 65dB A External static pressure 0 Pa 2 Indoor units Total capacity 50 130 1 Model 06 96 Quantity 2 50 2 50 2 ...

Page 6: ...of the unit 300 11 13 16 15 19 32 2 If the wall height H of the front rear or side exceeds the wall height restriction h 500 19 11 16 500 19 11 16 500 19 11 16 450 17 23 32 h 450 17 23 32 h 450 17 23 32 h L W W h L W W h h h L W W h Should be shorter than the unit height Should be shorter than the unit height Should be shorter than the unit height Should be shorter than the unit height Should be s...

Page 7: ...20 144 Fig 6 0 2 1 Side by side installation The space on both sides of a given group of units is minimum The space on both sides of a given group of units is minimum h 500 19 11 16 300 11 13 16 h 450 17 23 32 h h 30 1 3 16 h 500 19 11 16 h 450 17 23 32 h 100 3 15 16 h 100 3 15 16 Unit height Unit height 2 Face to face installation There are walls in the front and the back of a given group of unit...

Page 8: ... that the corner of the installation leg is securely supported as shown in the figure Fig 8 1 1 When using a rubber isolating cushion please ensure it is large enough to cover the entire width of each of the unit s legs If the corners are not firmly seated the installation feet may be bent When using cushion pads be sure that the full width of the unit is covered The projecting length of the ancho...

Page 9: ...f the outdoor unit is completely closed the factory setting Do not operate it until the refrigerant piping for the outdoor and indoor units has been connected a refrigerant leakage test has been performed and the evacuation process has been completed c Never use refrigerant to perform an air purge Always evacuate using a vacuum pump d Be sure to charge the system using liquid refrigerant e Either ...

Page 10: ...refrigerant and refrigerant oil may cause the refrigerant oil to deteriorate Mixing of water will cause the refrigerant oil to deteriorate R410A refrigerant does not contain any chlorine Therefore gas leak detectors for conventional refrigerants will not react to it Manage the tools used for R410A more carefully than normal If dust dirt or water gets in the refrigerant cycle the refrigerant oil wi...

Page 11: ...8 1 1 8 ø12 7 1 2 ø28 58 1 1 8 ø12 7 1 2 ø28 58 1 1 8 ø19 05 3 4 ø34 93 1 3 8 1 ø12 7 for over 90m 295 ft 2 ø12 7 for over 40m 131 ft 3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for unit 1 2 and 3 change make sure to use the appropriate pipe size 4 B If the piping length after the...

Page 12: ...nce between unit and unit in height h2 should be 0 1 m 3 15 16 in or below 4 h2 unit 1 unit 2 unit 3 h2 0 1 m 3 15 16 in max h2 unit 1 unit 2 unit 3 h2 0 1 m 3 15 16 in The NG example shows that oil accumulates into unit 3 while unit 1 is in operation and unit 3 is stopped Difference between unit and unit in height h2 should be 0 1 m 3 15 16 in or below B When the piping on the outdoor unit side f...

Page 13: ...A ø12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8 in 15 m 49 ft c ø6 35 mm 1 4 in 10 m 32 ft 4 12 D ø9 52 mm 3 8 in 10 m 32 ft d ø6 35 mm 1 4 in 10 m 32 ft 5 24 e ø9 52 mm 3 8 in 10 m 32 ft The total length of each liquid line is as follows ø12 7 mm 1 2 in A 40 m 131 ft 40 m 131 ft ø9 52 mm 3 8 in B C D a b ...

Page 14: ... In the case the unit is used in combination with other outdoor units 4 Furthest piping length OU from IU 90 m 295 ft 5 Furthest piping length OU from IU 40 m 131 ft 10 2 Precautions concerning piping connection and valve operation Conduct piping connection and valve operation accurately and carefully Removing the pinched connecting pipe When shipped a pinched connecting pipe is attached to the on...

Page 15: ...enerate any gas leakage Refer to the table on the below for appropriate tightening torque Appropriate tightening torque Outer diameter of copper pipe mm in Cap N m kg cm Shaft N m kg cm Size of hexagonal wrench mm Service port N m kg cm ø9 52 3 8 15 150 6 60 4 12 120 ø12 7 1 2 20 200 9 90 4 ø15 88 5 8 25 250 15 150 6 ø19 05 3 4 25 250 30 300 6 ø25 4 1 25 250 30 300 10 ø28 58 1 1 8 25 250 16 160 Ca...

Page 16: ...down to 0 1 kg 3 oz Use a vacuum pump with a reverse flow check valve Recommended vacuum gauge ROBINAIR 14830A Thermistor Vacuum Gauge or Micron Gauge Do not use a manifold gauge to measure vacuum pressure Also use a vacuum gauge that reaches 65 Pa abs 0 00943 psi 0 5 Torr or below after operating for five minutes Triple Evacuation Evacuate the system to 4 000 microns from both service valves Syst...

Page 17: ...E Band F Waterproofing layer G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material 10 4 Thermal insulation of refrigerant piping Be sure to add insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat resistant polyethylene so that no gap is observed in the joint between indoor...

Page 18: ...ted to TB7 side and TKMU outdoor unit model is used connect a PAC SC51KUA to TB7 side If a PAC SC51KUA cannot be used connect the System controller to TB3 side When YKMU outdoor unit model is used the male power supply connector can be connected to CN40 and the System controller can be connected to TB7 side When the male power supply connector is connected from TKMU outdoor unit to CN40 the power ...

Page 19: ...rubber bushing make sure the rubber bushing will not come off the sheet metal on the control box guard Fig 4 and Fig 5 Rubber bushing Sheet metal on the guard Sheet metal on the guard Rubber bushing Fig 4 Fig 5 Note 3 When tying the supplied band around the rubber bushing make sure to leave no gap between the ends Fig 6 and Fig 7 Important When putting the band on the rubber bushing make sure the ...

Page 20: ...OC 1 1 A transmission booster RP may be required depending on the number of connected indoor unit controllers 2 OC OS1 and OS2 of the outdoor units in the same refrigerant system are automatically identified They are identified as OC OS1 and OS2 in descending order of capacity If the capacity is the same they will be in ascending order of their address number 3 When a PAR 30MAAU is connected to a ...

Page 21: ... ON Fig 11 3 2 MA Remote Controller A D E B C A Change the jumper connector from CN41 to CN40 1 B SW5 1 ON 2 C Keep the jumper connector on CN41 B SW5 1 ON 2 System controller 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 except TKMU model When...

Page 22: ...OS1 and OS2 are automatically identified 1 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting 2 1 OC OS1 and OS2 of the outdoor units in the same refrigerant system are automatically identified They are identified as OC OS1 ...

Page 23: ... 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P96TKMU A BS 8 4 40 8 4 40 40 40 40 A 30 mA or 100 mA 0 1sec or less 34 57 PUHY P240TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P264TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P72TKMU A BS...

Page 24: ...Y P336YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P96YKMU A BS 3 3 12 3 3 12 20 20 20 A 30 mA or 100 mA 0 1sec or less 15 26 PUHY P360YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 2...

Page 25: ...continues to operate even after the unit has been turned off No display After turning off the cooling operation unit continues to operate the drain pump for 3 minutes then shuts it off Unit also continues to operate drain pump if condensate has been generated Indoor unit emits noise when switching from heating to cooling and vice versa Normal display This is a normal sound of the refrigerant circu...

Page 26: ...del PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P120YKMU A BS PUHY P144YKMU A BS PUHY P144YSKMU A BS PUHY P168YSKMU A BS Unit combination PUHY P72YKMU A BS PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P72YKMU A BS Refrigerant R410A 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz Allowable press...

Page 27: ...Demandez à un technicien autorisé d installer les accessoires Une installation incorrecte par l utilisateur peut avoir comme conséquence une fuite d eau un choc électrique ou un incendie N essayez pas de réparer l unité si vous ne disposez pas des compétences appropriées Si le climatiseur doit être réparé contactez votre revendeur votre sous traitant ou un ingénieur frigoriste Une réparation incor...

Page 28: ...ecte du climatiseur peut avoir comme conséquence une fuite d eau un choc électrique ou un incendie Après avoir terminé les travaux d installation vérifiez que le gaz frigorigène ne fuit pas Si le gaz frigorigène fuit et est exposé à un radiateur ventilateur cuisinière four ou toute autre source de chaleur des gaz nocifs peuvent se produire Ne reconstruisez pas ou ne changez pas les configurations ...

Page 29: ... peuvent causer des blessures Ne coupez pas le courant immédiatement après avoir arrêté le fonctionnement Attendez toujours au moins 5 minutes avant de couper le courant Autrement une fuite de l eau de drainage ou une défaillance mécanique des pièces sensibles pourrait se produire Ne touchez pas la surface du compresseur pendant l entretien Si l appareil est connecté à une alimentation et n est pa...

Page 30: ...MU A BS PUHY P288TSKMU A BS PUHY P312TSKMU A BS PUHY P336TSKMU A BS PUHY P360TSKMU A BS PUHY P240YSKMU A BS PUHY P264YSKMU A BS PUHY P288YSKMU A BS PUHY P312YSKMU A BS PUHY P336YSKMU A BS PUHY P360YSKMU A BS Niveau de bruit 60 Hz 63dB A 63 5dB A 64dB A 64 5dB A 64 5dB A 65dB A Pression statique externe 0 Pa 2 Unités d intérieur Capacité totale 50 130 1 Modèle 06 96 Quantité 2 50 2 50 2 50 2 50 2 5...

Page 31: ...11 13 16 15 19 32 2 Si la hauteur du mur H à l avant l arrière ou de côté excède la restriction en hauteur du mur h 500 19 11 16 500 19 11 16 500 19 11 16 450 17 23 32 h 450 17 23 32 h 450 17 23 32 h L W W h L W W h h h L W W h Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l un...

Page 32: ...six unités trois unités P120 144 Fig 6 0 2 1 Installation côte à côte L espace de chaque côté d un groupe d unités est minimal L espace de chaque côté d un groupe d unités est minimal h 500 19 11 16 300 11 13 16 h 450 17 23 32 h h 30 1 3 16 h 500 19 11 16 h 450 17 23 32 h 100 3 15 16 h 100 3 15 16 Hauteur de l unité Hauteur de l unité 2 Installation face à face Il y a un mur devant et derrière cha...

Page 33: ...ments P120 144 8 1 Installation Fig 8 1 1 A B C 30 mm 1 3 16 in D Fig 7 0 1 1 P72 3 P120 P144 40 Sangles Min 8 m 26 ft x 2 Garnitures protectrices d au moins 50 mm 1 31 32 in d épaisseur deux devant et deux derrière Garnitures protectrices deux devant et deux derrière Orifices de sangle deux devant et deux derrière Grille du ventilateur 40 Sangles Min 8 m 26 ft x 2 Garnitures protectrices d au moi...

Page 34: ...ment de la tuyauterie frigorigène assurez vous que la valve de l unité extérieure est complètement fermée réglage usine Ne l actionnez pas jusqu à ce que la tuyauterie frigorigène des unités extérieure et intérieure ait été connectée qu un essai d étanchéité du frigorigène ait été exécuté et que le processus d évacuation ait été complété c N utilisez jamais de frigorigène pour exécuter une purge d...

Page 35: ...ne conventionnel et d huile réfrigérant peut détériorer l huile réfrigérante Le mélange d eau détériore l huile réfrigérante Le frigorigène R410A ne contient aucun chlore Par conséquent les détecteurs de fuite de gaz pour les frigorigènes conventionnels ne réagissent pas Gérez les outils utilisés pour le R410A plus soigneusement que d habitude Si de la poussière des saletés ou de l eau pénètre dan...

Page 36: ... 05 3 4 ø34 93 1 3 8 1 ø12 7 pour plus de 90 m 295 ft 2 ø12 7 pour plus de 40 m 131 ft 3 Les tailles de tuyaux indiquées dans les colonnes A1 à A3 de ce tableau correspondent aux tailles des modèles présentés dans les colonnes 1 2 et 3 Lorsque l ordre des modèles change veillez à utiliser la taille de tuyau appropriée 4 B Si la longueur du tube après le premier raccord dépasse 40 m 90 m utilisez l...

Page 37: ... unité et l unité en hauteur h2 doit être de 0 1 m 3 15 16 in maximum 4 h2 unité 1 unité 2 unité 3 h2 0 1 m 3 15 16 in max h2 unité 1 unité 2 unité 3 h2 0 1 m 3 15 16 in L exemple NG illustre une accumulation d huile dans l unité 3 que l unité 1 est en cours d utilisation et que l unité 3 est arrêtée La différence entre l unité et l unité en hauteur h2 doit être de 0 1 m 3 15 16 in maximum B Quand...

Page 38: ...12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8 in 15 m 49 ft c ø6 35 mm 1 4 in 10 m 32 ft 4 12 D ø9 52 mm 3 8 in 10 m 32 ft d ø6 35 mm 1 4 in 10 m 32 ft 5 24 e ø9 52 mm 3 8 in 10 m 32 ft La longueur totale de chaque ligne de fluide est la suivante ø12 7 mm 1 2 in A 40 m 131 ft 40 m 131 ft ø9 52 mm 3 8 in B C...

Page 39: ...avec d autres unités extérieures 4 Plus grande longueur de tube de unité int vers unité ext 90 m 295 ft 5 Plus grande longueur de tube de unité int vers unité ext 40 m 131 ft 10 2 Précautions concernant les connexions de la tuyauterie et le fonctionnement de la valve Les connexions de la tuyauterie et le fonctionnement de la valve doivent être exécutés soigneusement et avec précision Retirer le tu...

Page 40: ...us au tableau ci dessous pour le couple de serrage approprié Couple de serrage approprié Diamètre extérieur du tube en cuivre mm in Capuchon N m kg cm Axe N m kg cm Taille de la clé hexagonale mm Port de service N m kg cm ø9 52 3 8 15 150 6 60 4 12 120 ø12 7 1 2 20 200 9 90 4 ø15 88 5 8 25 250 15 150 6 ø19 05 3 4 25 250 30 300 6 ø25 4 1 25 250 30 300 10 ø28 58 1 1 8 25 250 16 160 Attention Mainten...

Page 41: ...rer jusqu à 0 1 kg 3 oz Utilisez une pompe à vide avec clapet anti retour de flux inverse Manomètre à vide recommandé manomètre à vide Thermistor ROBINAIR 14830A ou manomètre Micron N utilisez pas un manomètre de collecteur pour mesurer la pression à vide Utilisez en outre un manomètre à vide qui atteint 65 Pa abs 0 00943 psi 0 5 Torr ou en dessous après avoir fonctionné pendant cinq minutes Tripl...

Page 42: ...de F Couche étanche G Manchon avec bord H Matériau calorifuge I Mortier ou autre matériau de calfeutrage non combustible J Matériau d isolation thermique incombustible 10 4 Isolation thermique de la tuyauterie du frigorigène Soyez sûr d ajouter l isolation à la tuyauterie du frigorigène en couvrant le tube de fluide et le tube de gaz séparément avec une épaisseur suffisante de polyéthylène résista...

Page 43: ...tension Le frigorigène liquide du compresseur s évapore lorsque le compresseur est alimenté Lorsque le contrôleur système est connecté à TB7 et que le modèle d unité extérieure TKMU est utilisé connectez un PAC SC51KUA à TB7 Si vous ne pouvez pas utiliser de PAC SC51KUA reliez le contrôleur système à TB3 Si le modèle d unité extérieure YKMU est utilisé le connecteur d alimentation mâle peut être r...

Page 44: ...âble de transmission en place avec les sangles de câble Consultez la Fig 1 4 Connectez les câbles au bornier d alimentation et au bornier de la ligne de transmission Consultez la Fig 1 5 Fixez chaque bague en caoutchouc avec la bande fournie Consultez la Fig 1 et la remarque 3 Sangle pour câble Bague en caoutchouc Bande installation sur site Bloc de jonction d alimentation Carte M NET Bornier de l...

Page 45: ...nsmission RP 0 à 1 appareil pour 1 OC 1 1 En fonction du nombre de contrôleurs d appareils intérieurs raccordés un module élévateur du niveau des signaux de transmission RP peut s avérer nécessaire 2 OC OS1 et OS2 des appareils extérieurs dans le même système frigorifique sont automatiquement identifiés Ils sont identifiés comme OC OS1 et OS2 dans l ordre décroissant de capacité Si la capacité est...

Page 46: ...2 Contrôleur de système 1 Lorsque l unité d alimentation n est pas connectée à la ligne de transmission pour permettre un contrôle centralisé débranchez le connecteur d alimentation mâle CN41 d UNE unité extérieure du système et reliez le à CN40 hormis modèle TKMU Lorsque le contrôleur système est connecté à TB7 et que le modèle d unité extérieure TKMU est utilisé connectez un PAC SC51KUA à TB7 Si...

Page 47: ...sont automatiquement identifiés 1 M NET R C principal 101 à 150 Réglez sur une adresse IC principale au sein du même groupe plus 100 M NET R C secondaire 151 à 200 Réglez sur une adresse IC principale au sein du même groupe plus 150 MA R C Définition inutile d adresse définition principale secondaire nécessaire 2 1 OC OS1 et OS2 des appareils extérieurs dans le même système frigorifique sont autom...

Page 48: ...Y P216TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P96TKMU A BS 8 4 40 8 4 40 40 40 40 A 30 mA ou 100 mA 0 1 sec ou moins 34 57 PUHY P240TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P264TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 ...

Page 49: ...Y P96YKMU A BS 3 3 12 3 3 12 20 20 20 A 30 mA ou 100 mA 0 1 sec ou moins 15 26 PUHY P360YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 1 Utilisez une alimentation séparée pour l appareil ...

Page 50: ...nt pendant le chauffage Affichage normal Le ventilateur fonctionne très lentement lorsque le thermostat est désactivé il bascule automatiquement sur la valeur préréglée via le minuteur ou la température du frigorigène lorsque le thermostat est désactivé Le ventilateur s arrête pendant le chauffage Affichage de dégivrage Le ventilateur doit être éteint lorsque l unité est en mode de dégivrage Le ve...

Page 51: ...es n de réglage lorsque le 10e bit du commutateur SW6 est activé 3 Clignote au démarrage du système 4 Une fois le n de réglage paramétré appuyez sur SWP01 pendant au moins deux secondes Liste des paramètres de réglage de SW6 Élément Commutateur Contenu du réglage Réglage SW6 Synchronisation du réglage des commutateurs OFF ON Réglage SW6 1 SW6 2 SW6 3 SW6 4 Réglage de la pression statique élevée ch...

Page 52: ...7 LBS Modèle PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P120YKMU A BS PUHY P144YKMU A BS PUHY P144YSKMU A BS PUHY P168YSKMU A BS Unité combinée PUHY P72YKMU A BS PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P72YKMU A BS Frigorigène R410A 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz Pression...

Page 53: ...ne number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WT06580X02 This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: