10. Additional refrigerant charge
At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and
additional charging of each refrigerant line will be required on site. In order that
future servicing may be properly provided, always keep a record of the size and
length of each refrigerant line and the amount of additional charge by writing it in
the space provided on the outdoor unit.
10.1. Calculation of additional refrigerant
charge
Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
Use the table below as a guide for calculating the amount of additional
charging and then charge the system accordingly.
If the calculation results in a fraction of less than 0.1 kg [4 oz], round up
to the next 0.1 kg [4 oz]. For example, if the result of the calculation was
12.38 kg [437 oz], round the result up to 12.4 kg [438 oz].
<Calculating the amount of refrigerant to be charged>
Additional
refrigerant charge
=
Total length of
liquid pipe sized
ø19.05 mm [3/4 in]
+
Total length of
liquid pipe sized
ø15.88 mm [5/8 in]
+
Total length of
liquid pipe sized
ø12.7 mm [1/2 in]
(kg) [oz]
(m) × 0.29 (kg/m)
(m) × 0.2 (kg/m)
(m) × 0.12 (kg/m)
(ft) × 3.12 (oz/ft)
(ft) × 2.16 (oz/ft)
(ft) × 1.30 (oz/ft)
+
Total length of
liquid pipe sized
ø9.52 mm [3/8 in]
+
Total length of
liquid pipe sized
ø6.35 mm [1/4 in]
(m) × 0.06 (kg/m)
(ft) × 0.65 (oz/ft)
(m) × 0.024 (kg/m)
(ft) × 0.26 (oz/ft)
+
Additional charge
+
α
Outdoor unit model
Charged amount
P96
2 kg
P120
8 kg
P144
<Example>
Indoor
1: 48 A : ø12.7 mm [1/2 in] 40 m [131 ft] a : ø9.52 mm [3/8 in] 10 m [32 ft]
2: 36 B : ø9.52 mm [3/8 in] 10 m [32 ft] b : ø9.52 mm [3/8 in] 5 m [16 ft]
3: 15 C : ø9.52 mm [3/8 in] 15 m [49 ft] c : ø6.35 mm [1/4 in] 10 m [32 ft]
4: 12 D : ø9.52 mm [3/8 in] 10 m [32 ft] d : ø6.35 mm [1/4 in] 10 m [32 ft]
5: 24
e : ø9.52 mm [3/8 in] 10 m [32 ft]
•
•
•
The total length of each liquid line is as follows:
ø12.7 mm [1/2 in]: A = 40 m [131 ft] = 40 m [131 ft]
ø9.52 mm [3/8 in]: B + C + D + a + b + e
= 10 m [32 ft] + 15 m [49 ft] + 10 m [32 ft] + 10 m [32 ft] +
5 m [16 ft] + 10 m [32 ft] = 60 m [193 ft]
ø6.35 mm [1/4 in]: c + d = 10 m [32 ft] + 10 m [32 ft] = 20 m [64 ft]
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 m [131 ft]
×
0.12 kg/m [1.30 oz/ft] + 60 m [193 ft]
×
0.06 kg/m [0.65 oz/ft]
+ 20 m [64 ft]
×
0.024 kg/m [0.26 oz/ft] + 3.5 kg [124 oz] = 12.4 kg [438 oz]
Value of
α
Total capacity of connecting indoor units
α
Models
~
27
2.0
kg
[71
oz]
Models
28
~
54
2.5
kg
[89
oz]
Models 55 ~ 126
3.0 kg
[106 oz]
Models 127 ~ 144
3.5 kg
[124 oz]
Models 145 ~ 180
4.5 kg
[159 oz]
Models 181 ~ 234
5.0 kg
[177 oz]
Models 235 ~ 273
6.0 kg
[212 oz]
Models 274 ~ 307
8.0 kg
[283 oz]
Models 308 ~ 342
9.0 kg
[318 oz]
Models
343
~
411
10.0
kg
[353
oz]
Models
412
~
480
12.0
kg
[424
oz]
Models
481
~
14.0
kg
[494
oz]
<Amount of factory charged refrigerant>
Outdoor unit model
Charged amount
P72
9.0 kg
P96
11.5 kg
P120
11.8 kg
P144
11.8 kg
At the
conditions
below:
A
Downward slope
B
Upward slope
C
Indoor unit
D
Trap (gas pipe only)
E
Within 2 m [6 ft]
F
Twinning pipe
G
Slope of the twinning pipes are at an angle within ±15
˚
to the ground
H
Pipes on site
I
Twinning Kit
J
Straight run of pipe that is 500 mm [19-11/16 in] or more
<C> Slope of twinning pipes
Make sure the slope of the twinning pipes are at an angle within ±15
˚
to the ground.
If the slope exceeds the speci
fi
ed angle, the unit may be damaged.
±15
°
G
F
<D> Pipe connection example
H
H
I
J