Mitsubishi Electric City Multi PUHY-P120TKMU-A Installation Manual Download Page 2

2

GB

1.1.  Before installation and electric work

X

  Before installing the unit, make sure you read all the 

“Safety precautions”.

X

  The “Safety precautions” provide very important points 

regarding safety. Make sure you follow them.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury 
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the 
unit.

Symbols used in the illustrations

  :  Indicates an action that must be avoided.

  :  Indicates that important instructions must be followed.

  :  Indicates a part which must be grounded.

  :  Beware of electric shock. (This symbol is displayed on the main unit 

label.) <Color: yellow>

 Warning:

Carefully read the labels attached to the outdoor unit.

 HIGH VOLTAGE WARNING:

Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it 
come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, 
keep the unit off for at least 10 minutes, and con

fi

rm that the capacitor 

voltage (inverter main circuit) has dropped to 20 VDC or less. 
(It takes about 10 minutes to discharge electricity after the power 
supply is turned off.)
Control box houses high temperature parts. Be well careful even after 
turning off the power source.
Perform the service after disconnecting the fan board connector 
(CNINV) and the inverter board connector (CN1 or CNFAN). 
(To plug or unplug connectors, check that the outdoor unit fan is not 
rotating and that the voltage of capacitor in the main circuit is 20 VDC 
or below. The capacitor may collect a charge and cause an electric 
shock when the outdoor unit fan rotates in windy conditions. Refer to 
the wiring nameplate for details.)
To connect wiring to TB7, check that the voltage is 20 VDC or below.
Reconnect the connector (CNINV) back to the fan board and reconnect 
the connector (CN1 or CNFAN) back to the inverter board after 
servicing.

 Warning:

Do not use refrigerant other than the type indicated in the manuals 
provided with the unit and on the nameplate.

-  Doing so may cause the unit or pipes to burst, or result in explosion or 

fi

re 

during use, during repair, or at the time of disposal of the unit.

-  It may also be in violation of applicable laws.
-  MITSUBISHI ELECTRIC CORPORATION cannot be held responsible 

for malfunctions or accidents resulting from the use of the wrong type of 
refrigerant.



Ask the dealer or an authorized technician to install the air conditioner.

-  Improper installation by the user may result in water leakage, electric 

shock, or 

fi

re.

Install the unit at a place that can withstand its weight.

-  Failure to do so may cause the unit to fall down, resulting in injuries and 

damage to the unit.

Use the speci

fi

ed cables for wiring. Make the connections securely so 

that the outside force of the cable is not applied to the terminals.

-  Inadequate connection and fastening may generate heat and cause a 

fi

re.

Prepare for strong winds and earthquakes and install the unit at the 
speci

fi

ed place.

-  Improper installation may cause the unit to topple and result in injury and 

damage to the unit.

Always use 

fi

lters and other accessories speci

fi

ed by Mitsubishi 

Electric.

-  Ask an authorized technician to install the accessories. Improper 

installation by the user may result in water leakage, electric shock, or 

fi

re.

Never attempt to repair the unit without the proper quali

fi

cations. If 

the air conditioner must be repaired consult the dealer, contractor or 
quali

fi

ed Refrigeration Engineer.

-  If the unit is repaired improperly, water leakage, electric shock, or 

fi

re may 

result.

Do not touch the heat exchanger 

fi

ns.

-  Improper handling may result in injury.

If refrigerant gas leaks during installation work, ventilate the room.

-  If the refrigerant gas comes into contact with a 

fl

ame, poisonous gases will 

be released.

Install the air conditioner according to this Installation Manual.

-  If the unit is installed improperly, water leakage, electric shock, or 

fi

re may 

result.

Have all electric work done by a licensed electrician according to the 
“Electric Facility Engineering Standard”, the “Wire Regulations in 
each area” and the instructions given in this manual and always use a 
dedicated power supply.

-  If the power source capacity is inadequate or electric work is performed 

improperly, electric shock and 

fi

re may result.

Securely install the outdoor unit terminal cover (panel).

-  If the terminal cover (panel) is not installed properly, dust or water may 

enter the outdoor unit and 

fi

re or electric shock may result.

When installing and moving the air conditioner to another site, do not 
charge it with a refrigerant different from the refrigerant speci

fi

ed on 

the unit.

-  If a different refrigerant or air is mixed with the original refrigerant, the 

refrigerant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be 
taken to prevent the refrigerant concentration from exceeding the 
safety limit if the refrigerant should leak.

-  Consult the dealer regarding the appropriate measures to prevent the 

safety limit from being exceeded. Should the refrigerant leak and cause 
the safety limit to be exceeded, hazards due to lack of oxygen in the room 
could result.

When moving and reinstalling the air conditioner, consult the dealer or 
an authorized technician.

-  If the air conditioner is installed improperly, water leakage, electric shock, 

or 

fi

re may result.

After completing installation work, make sure that refrigerant gas is not 
leaking.

-  If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or 

other heat source, it may generate noxious gases.

1. Safety precautions

Contents

1. Safety 

precautions 

....................................................................................... 2

1.1.  Before installation and electric work ............................................ 2
1.2.  Precautions for devices that use R410A refrigerant .................... 3
1.3. Before installation 

........................................................................ 3

1.4.  Before installation (relocation) - electrical work ........................... 3
1.5.  Before starting the test run .......................................................... 3

2.  About the product ......................................................................................... 4
3.  Combination of outdoor units ....................................................................... 4
4. Speci

fi

cations ............................................................................................... 5

5.  Parts included list ......................................................................................... 5
6.  Space required for unit installation and operation ........................................ 6
7.  Transporting the unit .................................................................................... 8
8. Installation 

of 

unit 

......................................................................................... 8

8.1. Installation 

................................................................................... 8

9.  Refrigerant piping installation ....................................................................... 9

9.1. Caution 

........................................................................................ 9

9.2. Refrigerant piping system  ........................................................ 10

10. Additional refrigerant charge ...................................................................... 13

10.1. Calculation of additional refrigerant charge ............................... 13
10.2. Precautions concerning piping connection and valve  

operation ................................................................................... 14

10.3. Airtight test, evacuation, and refrigerant charging ..................... 16
10.4. Thermal insulation of refrigerant piping ..................................... 17

11.  Wiring (For details, refer to the installation manual of each indoor/outdoor 

unit and controller.) .................................................................................... 18

11.1. Caution ...................................................................................... 18
11.2. Control box and connecting position of wiring ........................... 18
11.3. Wiring transmission cables ....................................................... 20
11.4. Wiring of main power supply and equipment capacity .............. 23

12. Test run ...................................................................................................... 25

12.1. Typical unit operation ................................................................ 25
12.2. Outdoor unit function setting ..................................................... 25

13. Rating plate information ............................................................................. 26

Summary of Contents for City Multi PUHY-P120TKMU-A

Page 1: ... air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte Air Conditioners For Building Application Inverter Y Series OUTDOOR UNIT PUHY P TKMU A BS PUHY P YKMU A BS For use with R410A ...

Page 2: ...tric shock or fire Never attempt to repair the unit without the proper qualifications If the air conditioner must be repaired consult the dealer contractor or qualified Refrigeration Engineer If the unit is repaired improperly water leakage electric shock or fire may result Do not touch the heat exchanger fins Improper handling may result in injury If refrigerant gas leaks during installation work...

Page 3: ... conditioner with the panels and guards removed Rotating hot or high voltage parts can cause injuries Do not reconstruct or change the settings of the protection devices If the pressure switch thermal switch or other protection device is shorted or operated forcibly or parts other than those specified by Mitsubishi Electric are used fire or explosion may result To dispose of this product consult y...

Page 4: ... A BS PUHY P96YKMU A BS PUHY P72YKMU A BS PUHY P312YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P72YKMU A BS PUHY P336YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P96YKMU A BS PUHY P360YSKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P120YKMU A BS PUHY P144 to P360YSKMU A BS require Twinning Kit to connect component unit modules in the field 2 About the product This unit use...

Page 5: ...40TSKMU A BS PUHY P264TSKMU A BS PUHY P288TSKMU A BS PUHY P312TSKMU A BS PUHY P336TSKMU A BS PUHY P360TSKMU A BS PUHY P240YSKMU A BS PUHY P264YSKMU A BS PUHY P288YSKMU A BS PUHY P312YSKMU A BS PUHY P336YSKMU A BS PUHY P360YSKMU A BS Sound level 60Hz 63dB A 63 5dB A 64dB A 64 5dB A 64 5dB A 65dB A External static pressure 0 Pa 2 Indoor units Total capacity 50 130 1 Model 06 96 Quantity 2 50 2 50 2 ...

Page 6: ...of the unit 300 11 13 16 15 19 32 2 If the wall height H of the front rear or side exceeds the wall height restriction h 500 19 11 16 500 19 11 16 500 19 11 16 450 17 23 32 h 450 17 23 32 h 450 17 23 32 h L W W h L W W h h h L W W h Should be shorter than the unit height Should be shorter than the unit height Should be shorter than the unit height Should be shorter than the unit height Should be s...

Page 7: ...20 144 Fig 6 0 2 1 Side by side installation The space on both sides of a given group of units is minimum The space on both sides of a given group of units is minimum h 500 19 11 16 300 11 13 16 h 450 17 23 32 h h 30 1 3 16 h 500 19 11 16 h 450 17 23 32 h 100 3 15 16 h 100 3 15 16 Unit height Unit height 2 Face to face installation There are walls in the front and the back of a given group of unit...

Page 8: ... that the corner of the installation leg is securely supported as shown in the figure Fig 8 1 1 When using a rubber isolating cushion please ensure it is large enough to cover the entire width of each of the unit s legs If the corners are not firmly seated the installation feet may be bent When using cushion pads be sure that the full width of the unit is covered The projecting length of the ancho...

Page 9: ...f the outdoor unit is completely closed the factory setting Do not operate it until the refrigerant piping for the outdoor and indoor units has been connected a refrigerant leakage test has been performed and the evacuation process has been completed c Never use refrigerant to perform an air purge Always evacuate using a vacuum pump d Be sure to charge the system using liquid refrigerant e Either ...

Page 10: ...refrigerant and refrigerant oil may cause the refrigerant oil to deteriorate Mixing of water will cause the refrigerant oil to deteriorate R410A refrigerant does not contain any chlorine Therefore gas leak detectors for conventional refrigerants will not react to it Manage the tools used for R410A more carefully than normal If dust dirt or water gets in the refrigerant cycle the refrigerant oil wi...

Page 11: ...8 1 1 8 ø12 7 1 2 ø28 58 1 1 8 ø12 7 1 2 ø28 58 1 1 8 ø19 05 3 4 ø34 93 1 3 8 1 ø12 7 for over 90m 295 ft 2 ø12 7 for over 40m 131 ft 3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for unit 1 2 and 3 change make sure to use the appropriate pipe size 4 B If the piping length after the...

Page 12: ...nce between unit and unit in height h2 should be 0 1 m 3 15 16 in or below 4 h2 unit 1 unit 2 unit 3 h2 0 1 m 3 15 16 in max h2 unit 1 unit 2 unit 3 h2 0 1 m 3 15 16 in The NG example shows that oil accumulates into unit 3 while unit 1 is in operation and unit 3 is stopped Difference between unit and unit in height h2 should be 0 1 m 3 15 16 in or below B When the piping on the outdoor unit side f...

Page 13: ...A ø12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8 in 15 m 49 ft c ø6 35 mm 1 4 in 10 m 32 ft 4 12 D ø9 52 mm 3 8 in 10 m 32 ft d ø6 35 mm 1 4 in 10 m 32 ft 5 24 e ø9 52 mm 3 8 in 10 m 32 ft The total length of each liquid line is as follows ø12 7 mm 1 2 in A 40 m 131 ft 40 m 131 ft ø9 52 mm 3 8 in B C D a b ...

Page 14: ... In the case the unit is used in combination with other outdoor units 4 Furthest piping length OU from IU 90 m 295 ft 5 Furthest piping length OU from IU 40 m 131 ft 10 2 Precautions concerning piping connection and valve operation Conduct piping connection and valve operation accurately and carefully Removing the pinched connecting pipe When shipped a pinched connecting pipe is attached to the on...

Page 15: ...enerate any gas leakage Refer to the table on the below for appropriate tightening torque Appropriate tightening torque Outer diameter of copper pipe mm in Cap N m kg cm Shaft N m kg cm Size of hexagonal wrench mm Service port N m kg cm ø9 52 3 8 15 150 6 60 4 12 120 ø12 7 1 2 20 200 9 90 4 ø15 88 5 8 25 250 15 150 6 ø19 05 3 4 25 250 30 300 6 ø25 4 1 25 250 30 300 10 ø28 58 1 1 8 25 250 16 160 Ca...

Page 16: ...down to 0 1 kg 3 oz Use a vacuum pump with a reverse flow check valve Recommended vacuum gauge ROBINAIR 14830A Thermistor Vacuum Gauge or Micron Gauge Do not use a manifold gauge to measure vacuum pressure Also use a vacuum gauge that reaches 65 Pa abs 0 00943 psi 0 5 Torr or below after operating for five minutes Triple Evacuation Evacuate the system to 4 000 microns from both service valves Syst...

Page 17: ...E Band F Waterproofing layer G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material 10 4 Thermal insulation of refrigerant piping Be sure to add insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat resistant polyethylene so that no gap is observed in the joint between indoor...

Page 18: ...ted to TB7 side and TKMU outdoor unit model is used connect a PAC SC51KUA to TB7 side If a PAC SC51KUA cannot be used connect the System controller to TB3 side When YKMU outdoor unit model is used the male power supply connector can be connected to CN40 and the System controller can be connected to TB7 side When the male power supply connector is connected from TKMU outdoor unit to CN40 the power ...

Page 19: ...rubber bushing make sure the rubber bushing will not come off the sheet metal on the control box guard Fig 4 and Fig 5 Rubber bushing Sheet metal on the guard Sheet metal on the guard Rubber bushing Fig 4 Fig 5 Note 3 When tying the supplied band around the rubber bushing make sure to leave no gap between the ends Fig 6 and Fig 7 Important When putting the band on the rubber bushing make sure the ...

Page 20: ...OC 1 1 A transmission booster RP may be required depending on the number of connected indoor unit controllers 2 OC OS1 and OS2 of the outdoor units in the same refrigerant system are automatically identified They are identified as OC OS1 and OS2 in descending order of capacity If the capacity is the same they will be in ascending order of their address number 3 When a PAR 30MAAU is connected to a ...

Page 21: ... ON Fig 11 3 2 MA Remote Controller A D E B C A Change the jumper connector from CN41 to CN40 1 B SW5 1 ON 2 C Keep the jumper connector on CN41 B SW5 1 ON 2 System controller 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 except TKMU model When...

Page 22: ...OS1 and OS2 are automatically identified 1 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting 2 1 OC OS1 and OS2 of the outdoor units in the same refrigerant system are automatically identified They are identified as OC OS1 ...

Page 23: ... 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P96TKMU A BS 8 4 40 8 4 40 40 40 40 A 30 mA or 100 mA 0 1sec or less 34 57 PUHY P240TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P264TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1sec or less 45 73 PUHY P72TKMU A BS...

Page 24: ...Y P336YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P96YKMU A BS 3 3 12 3 3 12 20 20 20 A 30 mA or 100 mA 0 1sec or less 15 26 PUHY P360YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA or 100 mA 0 1sec or less 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 2...

Page 25: ...continues to operate even after the unit has been turned off No display After turning off the cooling operation unit continues to operate the drain pump for 3 minutes then shuts it off Unit also continues to operate drain pump if condensate has been generated Indoor unit emits noise when switching from heating to cooling and vice versa Normal display This is a normal sound of the refrigerant circu...

Page 26: ...del PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P120YKMU A BS PUHY P144YKMU A BS PUHY P144YSKMU A BS PUHY P168YSKMU A BS Unit combination PUHY P72YKMU A BS PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P72YKMU A BS Refrigerant R410A 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz Allowable press...

Page 27: ...Demandez à un technicien autorisé d installer les accessoires Une installation incorrecte par l utilisateur peut avoir comme conséquence une fuite d eau un choc électrique ou un incendie N essayez pas de réparer l unité si vous ne disposez pas des compétences appropriées Si le climatiseur doit être réparé contactez votre revendeur votre sous traitant ou un ingénieur frigoriste Une réparation incor...

Page 28: ...ecte du climatiseur peut avoir comme conséquence une fuite d eau un choc électrique ou un incendie Après avoir terminé les travaux d installation vérifiez que le gaz frigorigène ne fuit pas Si le gaz frigorigène fuit et est exposé à un radiateur ventilateur cuisinière four ou toute autre source de chaleur des gaz nocifs peuvent se produire Ne reconstruisez pas ou ne changez pas les configurations ...

Page 29: ... peuvent causer des blessures Ne coupez pas le courant immédiatement après avoir arrêté le fonctionnement Attendez toujours au moins 5 minutes avant de couper le courant Autrement une fuite de l eau de drainage ou une défaillance mécanique des pièces sensibles pourrait se produire Ne touchez pas la surface du compresseur pendant l entretien Si l appareil est connecté à une alimentation et n est pa...

Page 30: ...MU A BS PUHY P288TSKMU A BS PUHY P312TSKMU A BS PUHY P336TSKMU A BS PUHY P360TSKMU A BS PUHY P240YSKMU A BS PUHY P264YSKMU A BS PUHY P288YSKMU A BS PUHY P312YSKMU A BS PUHY P336YSKMU A BS PUHY P360YSKMU A BS Niveau de bruit 60 Hz 63dB A 63 5dB A 64dB A 64 5dB A 64 5dB A 65dB A Pression statique externe 0 Pa 2 Unités d intérieur Capacité totale 50 130 1 Modèle 06 96 Quantité 2 50 2 50 2 50 2 50 2 5...

Page 31: ...11 13 16 15 19 32 2 Si la hauteur du mur H à l avant l arrière ou de côté excède la restriction en hauteur du mur h 500 19 11 16 500 19 11 16 500 19 11 16 450 17 23 32 h 450 17 23 32 h 450 17 23 32 h L W W h L W W h h h L W W h Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l unité Doit être inférieur à la hauteur de l un...

Page 32: ...six unités trois unités P120 144 Fig 6 0 2 1 Installation côte à côte L espace de chaque côté d un groupe d unités est minimal L espace de chaque côté d un groupe d unités est minimal h 500 19 11 16 300 11 13 16 h 450 17 23 32 h h 30 1 3 16 h 500 19 11 16 h 450 17 23 32 h 100 3 15 16 h 100 3 15 16 Hauteur de l unité Hauteur de l unité 2 Installation face à face Il y a un mur devant et derrière cha...

Page 33: ...ments P120 144 8 1 Installation Fig 8 1 1 A B C 30 mm 1 3 16 in D Fig 7 0 1 1 P72 3 P120 P144 40 Sangles Min 8 m 26 ft x 2 Garnitures protectrices d au moins 50 mm 1 31 32 in d épaisseur deux devant et deux derrière Garnitures protectrices deux devant et deux derrière Orifices de sangle deux devant et deux derrière Grille du ventilateur 40 Sangles Min 8 m 26 ft x 2 Garnitures protectrices d au moi...

Page 34: ...ment de la tuyauterie frigorigène assurez vous que la valve de l unité extérieure est complètement fermée réglage usine Ne l actionnez pas jusqu à ce que la tuyauterie frigorigène des unités extérieure et intérieure ait été connectée qu un essai d étanchéité du frigorigène ait été exécuté et que le processus d évacuation ait été complété c N utilisez jamais de frigorigène pour exécuter une purge d...

Page 35: ...ne conventionnel et d huile réfrigérant peut détériorer l huile réfrigérante Le mélange d eau détériore l huile réfrigérante Le frigorigène R410A ne contient aucun chlore Par conséquent les détecteurs de fuite de gaz pour les frigorigènes conventionnels ne réagissent pas Gérez les outils utilisés pour le R410A plus soigneusement que d habitude Si de la poussière des saletés ou de l eau pénètre dan...

Page 36: ... 05 3 4 ø34 93 1 3 8 1 ø12 7 pour plus de 90 m 295 ft 2 ø12 7 pour plus de 40 m 131 ft 3 Les tailles de tuyaux indiquées dans les colonnes A1 à A3 de ce tableau correspondent aux tailles des modèles présentés dans les colonnes 1 2 et 3 Lorsque l ordre des modèles change veillez à utiliser la taille de tuyau appropriée 4 B Si la longueur du tube après le premier raccord dépasse 40 m 90 m utilisez l...

Page 37: ... unité et l unité en hauteur h2 doit être de 0 1 m 3 15 16 in maximum 4 h2 unité 1 unité 2 unité 3 h2 0 1 m 3 15 16 in max h2 unité 1 unité 2 unité 3 h2 0 1 m 3 15 16 in L exemple NG illustre une accumulation d huile dans l unité 3 que l unité 1 est en cours d utilisation et que l unité 3 est arrêtée La différence entre l unité et l unité en hauteur h2 doit être de 0 1 m 3 15 16 in maximum B Quand...

Page 38: ...12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8 in 15 m 49 ft c ø6 35 mm 1 4 in 10 m 32 ft 4 12 D ø9 52 mm 3 8 in 10 m 32 ft d ø6 35 mm 1 4 in 10 m 32 ft 5 24 e ø9 52 mm 3 8 in 10 m 32 ft La longueur totale de chaque ligne de fluide est la suivante ø12 7 mm 1 2 in A 40 m 131 ft 40 m 131 ft ø9 52 mm 3 8 in B C...

Page 39: ...avec d autres unités extérieures 4 Plus grande longueur de tube de unité int vers unité ext 90 m 295 ft 5 Plus grande longueur de tube de unité int vers unité ext 40 m 131 ft 10 2 Précautions concernant les connexions de la tuyauterie et le fonctionnement de la valve Les connexions de la tuyauterie et le fonctionnement de la valve doivent être exécutés soigneusement et avec précision Retirer le tu...

Page 40: ...us au tableau ci dessous pour le couple de serrage approprié Couple de serrage approprié Diamètre extérieur du tube en cuivre mm in Capuchon N m kg cm Axe N m kg cm Taille de la clé hexagonale mm Port de service N m kg cm ø9 52 3 8 15 150 6 60 4 12 120 ø12 7 1 2 20 200 9 90 4 ø15 88 5 8 25 250 15 150 6 ø19 05 3 4 25 250 30 300 6 ø25 4 1 25 250 30 300 10 ø28 58 1 1 8 25 250 16 160 Attention Mainten...

Page 41: ...rer jusqu à 0 1 kg 3 oz Utilisez une pompe à vide avec clapet anti retour de flux inverse Manomètre à vide recommandé manomètre à vide Thermistor ROBINAIR 14830A ou manomètre Micron N utilisez pas un manomètre de collecteur pour mesurer la pression à vide Utilisez en outre un manomètre à vide qui atteint 65 Pa abs 0 00943 psi 0 5 Torr ou en dessous après avoir fonctionné pendant cinq minutes Tripl...

Page 42: ...de F Couche étanche G Manchon avec bord H Matériau calorifuge I Mortier ou autre matériau de calfeutrage non combustible J Matériau d isolation thermique incombustible 10 4 Isolation thermique de la tuyauterie du frigorigène Soyez sûr d ajouter l isolation à la tuyauterie du frigorigène en couvrant le tube de fluide et le tube de gaz séparément avec une épaisseur suffisante de polyéthylène résista...

Page 43: ...tension Le frigorigène liquide du compresseur s évapore lorsque le compresseur est alimenté Lorsque le contrôleur système est connecté à TB7 et que le modèle d unité extérieure TKMU est utilisé connectez un PAC SC51KUA à TB7 Si vous ne pouvez pas utiliser de PAC SC51KUA reliez le contrôleur système à TB3 Si le modèle d unité extérieure YKMU est utilisé le connecteur d alimentation mâle peut être r...

Page 44: ...âble de transmission en place avec les sangles de câble Consultez la Fig 1 4 Connectez les câbles au bornier d alimentation et au bornier de la ligne de transmission Consultez la Fig 1 5 Fixez chaque bague en caoutchouc avec la bande fournie Consultez la Fig 1 et la remarque 3 Sangle pour câble Bague en caoutchouc Bande installation sur site Bloc de jonction d alimentation Carte M NET Bornier de l...

Page 45: ...nsmission RP 0 à 1 appareil pour 1 OC 1 1 En fonction du nombre de contrôleurs d appareils intérieurs raccordés un module élévateur du niveau des signaux de transmission RP peut s avérer nécessaire 2 OC OS1 et OS2 des appareils extérieurs dans le même système frigorifique sont automatiquement identifiés Ils sont identifiés comme OC OS1 et OS2 dans l ordre décroissant de capacité Si la capacité est...

Page 46: ...2 Contrôleur de système 1 Lorsque l unité d alimentation n est pas connectée à la ligne de transmission pour permettre un contrôle centralisé débranchez le connecteur d alimentation mâle CN41 d UNE unité extérieure du système et reliez le à CN40 hormis modèle TKMU Lorsque le contrôleur système est connecté à TB7 et que le modèle d unité extérieure TKMU est utilisé connectez un PAC SC51KUA à TB7 Si...

Page 47: ...sont automatiquement identifiés 1 M NET R C principal 101 à 150 Réglez sur une adresse IC principale au sein du même groupe plus 100 M NET R C secondaire 151 à 200 Réglez sur une adresse IC principale au sein du même groupe plus 150 MA R C Définition inutile d adresse définition principale secondaire nécessaire 2 1 OC OS1 et OS2 des appareils extérieurs dans le même système frigorifique sont autom...

Page 48: ...Y P216TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P96TKMU A BS 8 4 40 8 4 40 40 40 40 A 30 mA ou 100 mA 0 1 sec ou moins 34 57 PUHY P240TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 50 A 100 mA 0 1 sec ou moins 45 73 PUHY P264TSKMU A BS PUHY P120TKMU A BS 13 3 6 13 3 6 50 50 ...

Page 49: ...Y P96YKMU A BS 3 3 12 3 3 12 20 20 20 A 30 mA ou 100 mA 0 1 sec ou moins 15 26 PUHY P360YSKMU A BS PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 PUHY P120YKMU A BS 5 3 10 5 3 10 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 20 33 1 Utilisez une alimentation séparée pour l appareil ...

Page 50: ...nt pendant le chauffage Affichage normal Le ventilateur fonctionne très lentement lorsque le thermostat est désactivé il bascule automatiquement sur la valeur préréglée via le minuteur ou la température du frigorigène lorsque le thermostat est désactivé Le ventilateur s arrête pendant le chauffage Affichage de dégivrage Le ventilateur doit être éteint lorsque l unité est en mode de dégivrage Le ve...

Page 51: ...es n de réglage lorsque le 10e bit du commutateur SW6 est activé 3 Clignote au démarrage du système 4 Une fois le n de réglage paramétré appuyez sur SWP01 pendant au moins deux secondes Liste des paramètres de réglage de SW6 Élément Commutateur Contenu du réglage Réglage SW6 Synchronisation du réglage des commutateurs OFF ON Réglage SW6 1 SW6 2 SW6 3 SW6 4 Réglage de la pression statique élevée ch...

Page 52: ...7 LBS Modèle PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P120YKMU A BS PUHY P144YKMU A BS PUHY P144YSKMU A BS PUHY P168YSKMU A BS Unité combinée PUHY P72YKMU A BS PUHY P72YKMU A BS PUHY P96YKMU A BS PUHY P72YKMU A BS Frigorigène R410A 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz Pression...

Page 53: ...ne number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WT06580X02 This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: