11. M-NET CONTROL
WR2-Series-575V
PQRY
PQRY
PQRY
11-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, Lossnay, Booster for long M-NET wiring
2. M-NET power is supplied by the Heat source unit at TB3, while Indoor unit and ME R/C consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to
11-3. "System configuration restrictions".
NOTE:
1. Heat source units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
3. Indoor units should be set with a branch number.
4. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are connected
to each sub BC controller and 50.
When the address assigned to sub BC controller overlaps those of any other units including heat source units (OC/OS) or main BC controller,
sub BC controller will be given priority to have the address.
Indoor unit
ME R/C
*1 System controller should connect to TB7 at the Heat source unit and use power supply unit together in Multi-Refrigerant-System.
For AG-150A-A, 24VDC should be used with the PAC-SC51KUA. For AE-200A, AE-50A, and EW-50A the power supply unit PAC-SC51KUA is unused.
.
01
02
03
30
TB5
BC controller
(Main)
53
TB02
BC controller
(Sub)
80
TB02
BC controller
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA-G
TB5
TB3
ME R/C ME R/C
Indoor unit
ME R/C
144
145
195
130
41
93
44
45
TB5
TB5
TB5
ME R/C
141
ME R/C
101
ME R/C
102
Group 2
Group 1
Group 21
Group 31
Group 33
Group 34
TB3
TB7
TB7
TB7
TB7
TB7
TB3
52
51
OC
OS
TB3
TB3
92
91
OC
OS
TB3
96
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
11-4-3-7. Example: BC, BC sub
NOTE
• Indoor units should be set with a branch number.
• BC (main) address = O/U a 1
• BC (sub) address = Lowest address within the indoor units connected to the BC controller (sub) + 50
• If applicable, set the sub BC controllers in an PQRY system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
OC
BC controllers
Group 1
51
TB3
TB3
TB02
TB5
TB5
TB5
TB5
TB5
TB5
TB5
TB5
TB02
TB02
01
02
03
101
Group 3
Group 2
04
05
06
104
106
53
54
CMB-P-NU-KB1(No.1 sub)
BC controllers
: M-NET wiring
CMB-P-NU-JA1(main)
DipSW5-1
OFF
OS
52
CN41
CN40
CN41
CN40
DipSW5-1
OFF
: Piping
Group 4
07
08
107
57
CMB-P-NU-KB1(No.2 sub)
BC controllers
PQRY
*1
000 or 201
PSU
Power supply
unit (PSU)
(PAC-SC51KUA)
SC
ME R/C
142
42
43
TB5
TB5
Group 32
Lossnay
Interlocked with
M-NET address 42