MEES21K047
PQ
R
Y-
P-
Z(
S)
LM
U
-A
1
118
12. PIPING DESIGN
WR2-Series-575V
12-2-2. IF more than 16 ports are in use, or if there is more than one BC controller in use for one
Heat source unit
Piping length limitation *10
(m [ft.])
Bent equivalent length
Item
Piping in the figure
Max. length
Max. equivalent length
Total piping length (Total length of high pressure and liquid pipes)
A+B+C+D+E+F+G+J+K+a+b+c+d+e+f+g+i+j+k+m+n
*1
-
Farthest IU from HU
A+F+G+J+K+n
165 [541']
190 [623']
Distance between HU and BC
A
110 [360'] *1
110 [360'] *1
Farthest IU from BC controller
D+E+i
60 [197'] *2*3
60 [197'] *2*3
Height between HU and IU (HU above IU)
H
50 [164'] *7
-
Height between HU and IU (HU under IU)
H'
40 [131'] *8
-
Height between IU and BC
h1
15 [49'] (10 [32']) *4
-
Height between IU and IU
h2
30 [98'] (20 [65']) *5
-
Height between BC(Main or Sub) and BC(Sub)
h3
15 [49'] (10 [32']) *6
-
Farthest IU from BC controller via Sub BC controller
F+G+J+K+n
90 [295'] *9
90 [295'] *9
S
T
M
N
CMY-R160-J1
(Gas side)
IU
CMY-R160-J1
(Liquid side)
BC controller
Fig. 12-2-2AA
HU: Heat source unit, IU: Indoor unit
Fig. 12-2-2A Piping scheme
(T)ø19.05ID
(N)ø9.52ID
(M)ø3/8"(Brazing)
(M)ø3/8"(Brazing)
(S)ø5/8"(Brazing)
(S)ø5/8"(Brazing)
226
226
Joint CMY-R160-J1 Gas side
Joint CMY-R160-J1 Liquid side
Note1. No Header usable on PQRY system.
Note2. Indoor unit sized P72-P96 should be connected to BC controller via Y shape joint CMY-R160-J1.
Note3. Indoor unit sized P72-P96 does NOT share BC controller ports with other Indoor units ;
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping "M" x Number of bent.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P72-P96 with 2 ports.
Note6. Do not connect multiple indoor units to the same port when operating each of them in different mode (cooling,
heating, stop, and thermo-off). In case of connecting multiple indoor units to the same port, connecting all indoor
units to one remote controller and switching SW1-1 ON in the all connected indoor units (switch to thermostat
built in the remote controller) are recommended.
Note7. The maximum total capacity of indoor units that can be connected to each sub BC controller CMB-P•NU-KB1
is 126.
Note8. Indoor capactiy is described as its model size. For example, PEFY-P24NMAU-E3, its capacity is P24.
Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream. For example,
PEFY-P24NMAU-E3 + PEFY-P06NMAU-E3 : Total Indoor capacity = P24 + P06 = P30.
Note10. To connect the BC controller to the main pipe, use the reducer (CMY-R301S-G, CMY-R302S-G1, or CMY-R304S-G1).
Note11. To connect the sub BC controller to the main BC controller, use the reducer (CMY-R303S-G1, CMY-R305S-G1, or CMY-R306S-G).
Note12. Install the pipes correctly referring to the section titled "Procedures for installing the branched pipes."
Note13. Up to 11 sub BC controllers can be connected.
HU: Heat source Unit; IU: Indoor Unit; BC: BC controller
*1. Refer to the section 12-2-4.
*2. Details refer to Fig. 2.
*3. When the P72 or P96 model of indoor units are connected to the system, the maximum
distance from the BC controller to the farthest indoor unit
indicated as "D + E + i" in the figure is 40 meters.
*4. Distance of Indoor sized P72, P96 from BC must be less than 10 m, if any.
*5. Distance of Indoor sized P72, P96 from IU must be less than 20 m, if any.
*6. When using 2 or more Sub BC controllers, max. height "h3" should be considered.
*7. 90 m is available depending on the model and installation conditions. For more detailed
information, contact your local distributor.
*8. 60 m is available depending on the model and installation conditions. For more detailed
information, contact your local distributor.
*9. When the piping length or the vertical separation exceeds the limit specified in Fig. 2,
connect a sub BC to the system. The restriction for a system with a sub BC connection is
shown in Fig. 3. When a given system configuration falls within the shaded area in Fig. 3, increase the
size of the high-pressure pipe and the liquid pipe between the main BC and sub BC by one size. When using P12, P15, P18, P36, or P48 model of
indoor units, increase the size of the liquid branch pipe between the sub BC and indoor unit by one size.
When using indoor models P54 or larger, the restrictions shown in Fig. 2 cannot be exceeded.
*10. Total length of high-pressure pipes and liquid pipes
Heat source Model
M (m/bent [ft./bent])
P144ZLMU
0.50 [1.64']
P168ZLMU
0.50 [1.64']
P192ZLMU
0.50 [1.64']
P72ZLMU
0.35 [1.15']
P96ZLMU
0.42 [1.38']
P120ZLMU
0.47 [1.54']
CMY-R160-J1 (joint)
CMY-R160-J1 (joint)
(P04-P54)
(P04-P54)
(P04-P54) (P04-P54)
(P04-P54)
(P72-P96)
Max. 3 sets for 1 port.
Total capacity < = P54
Max. 3 sets for 2 port.
P54 < Total capacity < = P96
IU (each) max < = P54
IU
A
a
a b
b
IU
IU
IU
B
B
c
c
IU
IU
IU
e
e
f
f
g
g
i i
C
C
H
D
D
E
E
h1
H'
IU
IU
BC controller (Sub BC)
BC controller (Sub BC)
BC controller (Sub BC)
j j
IU
IU
k
k
m
m
n
n
BC controller (Main BC)
F
F
F
G
G
G
K
K
K
J
J
J
BC controller (Sub BC)
h2
IU
h1
h1
h3
d
d
Pipe (LP Gas)
Pipe (HP Gas)
Pipe (Liquid)
Pipe (Gas)
Pipe
(Liquid)
(joint_B)
CMY-R201S-G
CMY-R202S-G
CMY-R203S-G
CMY-R204S-G
(joint_A)
CMY-Y102SS-G2
CMY-Y102LS-G2
Pipe (Low pressure)
Pipe (High pressure)
A
HU
0000006382.BOOK 118 ページ 2021年7月19日 月曜日 午後4時14分