1. SPECIFICATIONS
WR2-Series-575V
Heat Source Model
PQRY-P120ZLMU-A1
Indoor Model
Non-Ducted
Ducted
Power source
3-phase 3-wire 575 V ±10% 60 Hz
Cooling capacity
*1 BTU/h
120,000
(Nominal)
kW
35.2
Power input
kW
7.51
(575) Current input
A
8.3
(Rated)
BTU/h
114,000
kW
33.4
Power input
kW
6.95
7.35
(575) Current input
A
7.7
8.2
Temp. range of
Indoor
W.B.
59~75°F (15~24°C)
cooling
Inlet water
ºF
50~113°F (10~45°C)
Heating capacity
*2 BTU/h
135,000
(Nominal)
kW
39.6
Power input
kW
7.09
(575) Current input
A
7.9
(Rated)
BTU/h
129,000
kW
37.8
Power input
kW
6.55
5.92
(575) Current input
A
7.3
6.6
Temp. range of
Indoor
D.B.
59~81°F (15~27°C)
heating
Inlet water
ºF
50~113°F (10~45°C)
Indoor unit
Total capacity
50~150% of heat source unit capacity
connectable
Model/Quantity
P04~P96/1~30
Sound pressure level (measured in anechoic room) dB <A>
54.0
Refrigerant
High pressure
in. (mm)
3/4 (19.05) Brazed
piping diameter
Low pressure
in. (mm)
7/8 (22.2) Brazed
Minimum Circuit Ampacity
A
11
Maximum Overcurrent Protection
A
15
Circulating water
Water flow rate
G/h
1,522
G/min (gpm)
25.4
m
3
/h
5.76
L/min
96
cfm
3.4
Pressure drop
psi
3.48
kPa
24
Operating volume
G/h
793 ~ 1,902
range
G/min (gpm)
13.2 ~ 31.7
m
3
/h
3.0 ~ 7.2
Compressor
Type x Quantity
Inverter scroll hermetic compressor x 1
Starting method
Inverter
Motor output
kW
7.7
Case heater
kW
-
Lubricant
MEL32
External finish
Galvanized steel sheets
External dimension H x W x D
in.
43-5/16 x 34-11/16 x 21-11/16
mm
1,100 x 880 x 550
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Refrigerant
Type x original charge
R410A x 11 lbs + 1 oz (5.0 kg)
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
411 (186)
Heat exchanger
plate type
Water volume in plate
G
1.32
l
5.0
Water pressure Max.
psi
290
MPa
2.0
HIC circuit (HIC: Heat Inter-Changer)
-
Drawing
External
KL94C243
Wiring
KE94G421
Standard
Document
Installation Manual
attachment
Accessory
Details refer to External Drw
Optional parts
joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-R160-J1
BC controller: CMB-P104,106,108,1012,1016NU-J1
Main BC controller: CMB-P108,1012,1016NU-JA1, CMB-P1016NU-KA1
Sub BC controller: CMB-P104,108NU-KB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re
-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
Notes:
Unit converter
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B. (20°CD.B.), Inlet water temperature: 68°F (20°C)
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.