8. Specifications
PLFY-M·VEM Series
Model
M20
M25
M32
M40
M50
M63
M80
M100
M125
Power source
(Voltage <V>/Frequency<Hz>)
~N/ 220-230-240/50, 220/60
Capacity(Cooling/Heating)
<kW>
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
9.0/10.0
11.2/12.5 14.0/16.0
Dimension(Height)
<mm>
258(40)
298(40)
Dimension(Width)
<mm>
840(950)
Dimension(Depth)
<mm>
840(950)
Net weight
<kg>
19(5)
21(5)
24(5)
Fan airflow rate
(Low-Middle2-Middle1-High)
<m
3
/min>
12-13-14-15
13-14-15-16 13-14-15-17 13-14-16-18 14-15-16-18 14-17-20-23 20-23-26-29 22-26-30-35
Noise level (SPL)
(Low -Middle2-Middle1-High)
<dB>
24-26-27-29
26-27-29-31
28-29-30-32 28-31-34-37 34-37-39-41 35-39-42-45
Note:
* Operation temperature of indoor unit.
Cooling mode: 15 °C WB - 24 °C WB
Heating mode: 15 °C DB - 27 °C DB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
*2 This figure ( ) indicates standard panel’s.
17
en
RG79F455H01_en.indd 17
2019/07/15 9:13:16
019