26
Switch
SWA
Ceiling
height
selector
SWC
Option
selector
Rotary switch
Rotary switch
SW14
Branch
No.
setting
SW11
1s digit
address
setting
SW12
10ths digit
address
setting
Pole
(High ceiling)
(Standard)
(Silent)
3
2
1
(Option)
(Standard)
1~3
2
Operation by switch
* Ceiling height can be changed depending
on SWA setting.
Remarks
<Initial setting>
Address board
Address can be set while the
unit is stopped.
Address board
<Initial setting>
Address board
3
2
1
SW12
10
SW11
1
SW12
SW11
SW14
SW14
<Initial setting>
Effective
timing
Before
power
supply
ON
Under
operation
or
suspension
Silent
2.5m
2.6m
Standard
2.7m
3.0m
High ceiling
3.5m
4.2m
P40, P63
P100, P125
SWA
* In this model it is not necessary to
change SWC to .
How to set address
Example : If address is "3", remain SW12
(for over 10) at "0", and match SW11 (for 1 to 9)
with "3".
How to set branch number SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC
contoller’s end connection number
Remain other than series R2 at "0".
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
• To operate each indoor unit by each remote controller when installed 2 indoor
units or more are near, Pair No. setting is necessary.
Pair No. setting is available with the 4 patterns (Setting patters A to D).
Make setting for J41, J42 of indoor controller board and the Pair No. of
wireless remote controller.
• You may not set it when operating it by 1 remote controller.
Setting for indoor unit
Jumper wire J41, J42 on the indoor controller board are cut according to
the table below.
Wireless remote controller pair number:
Setting operation
1. Press the SET button (using a pointed implement). Check that the
remote controller's display has stopped before continuing.
MODEL SELECT flashes, and the model No. (3 digits) appears (steadily-lit).
2. Press the MINUTE button twice. The pair number appears flashing.
3. Press the temperature buttons to select the pair number to set.
4. Press the SET button (using a pointed implement). The set pair number is
displayed (steadily-lit) for 3 seconds, then disappears.
J41, J42
Wireless
remote
controller
Pair No.
SWE
Test run
for
Drain
pump
(Option)
Connector
Jumper
Drain pump and fan are activated simultaneously after the connector
SWE is set to ON and turn on the power.
The connector SWE is set to OFF after test run.
<Initial setting>
Pattern A
<Initial setting>
SWE
SWE
OFF
ON
SWE
OFF
ON
OFF
ON
Under
operation
or
suspension
Under
operation
Setting pattern
J41
J42
Indoor controller
Jumper wire
Pair No. of wireless
remote controller *
Factory setting
A
B
D
C
—
Cut
Cut
—
—
—
Cut
Cut
0
1
3
2
—
—
—
* Pair No.4-9 of wireless remote controller is setting pattern D.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
Model No.
Temperature
button
SET button
Pair No.
Minute
button
<Initial setting>
Address board
The black square ( ) indicates a switch position.
OCH449A