Room temperature thermistor (TH21)
Liquid pipe temperature thermistor (TH22)
Gas pipe temperature thermistor (TH23)
Thermistor R
0
=15kΩ ± 3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480 ( ) }
0°C
15kΩ
10°C
9.6kΩ
20°C
6.3kΩ
25°C
5.4kΩ
30°C
4.3kΩ
40°C
3.0kΩ
Thermistor for
lower temperature
Linear expansion valve
Operation summary of the linear expansion valve
• Linear expansion valves open/close through the use of a stepping motor after receiving the pulse signal from the indoor
controller board.
• Valve position can be changed in proportion to the number of pulse signals.
<Connection between the indoor controller board and the linear expansion valve>
1
273+t
1
273
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
8-1-1. Thermistor