11
11
*1 Nominal cooling conditions
Note :
Indoor :
Outdoor :
Pipe length :
Level difference :
27°CDB/19°CWB (81°FDB/66°FWB)
35°CDB (95°FDB)
7.5 m (24-9/16 ft)
0 m (0 ft)
*2 Nominal cooling conditions
27°CDB/19.5°CWB (81°FDB/67°FWB)
35°CDB (95°FDB)
5 m (16-3/8 ft)
0 m (0 ft)
*3 Nominal heating conditions
Unit converter
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
* Nominal conditions *1, *3 are subject to JIS B8615-1.
* Due to continuing improvement, above specification may be subject to change without notice.
kcal/h = kW
×
860
Btu/h = kW × 3,412
cfm = m
3
/min × 35.31
lb
= kg/0.4536
*Above specification data is
subject to rounding variation.
Details on foundation work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
Model
PCFY-P40VKM-E
PCFY-P63VKM-E
PCFY-P100VKM-E
PCFY-P125VKM-E
Power source
1-phase 220-240V 50Hz, 1-phase 220V 60Hz
Cooling capacity
*1 kW
4.5
7.1
11.2
14.0
(Nominal)
*1 kcal/h
3,900
6,100
9,600
12,000
*1
Btu/h
15,400
24,200
38,200
47,800
*2
kcal/h
4,000
6,300
10,000
12,500
Power input
kW
0.040
0.050
0.090
0.110
Current input
A
0.28
0.33
0.65
0.76
Heating capacity
*3 kW
5.0
8.0
12.5
16.0
(Nominal )
*3 kcal/h
4,300
6,900
10,800
13,800
*3 Btu/h
17,100
27,300
42,700
54,600
Power input
kW
0.040
0.050
0.090
0.110
Current input
A
0.28
0.33
0.65
0.76
External finish
MUNSELL (6.4Y 8.9/0.4)
External dimensions H x W x D
mm
230×960×680
230×1280×680
230×1600×680
in.
9-1/16×37-13/16×26-3/4
9-1/16×50-3/8×26-3/4
9-1/16×63×26-3/4
Net weight
kg (lb)
24 (53)
32 (71)
36 (79)
38 (84)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
FAN
Type x quantity
Sirocco fan × 2
Sirocco fan × 3
Sirocco fan × 4
External
Pa
0
static press.
mmH
2
O
0
Motor type
DC motor
Motor output
kW
0.090
0.095
0.160
Driving mechanism
Direct-driven by motor
Airflow rate
m
3
/min
10-11-12-13
14-15-16-18
21-24-26-28
21-24-27-31
(Low-Mid2-Mid1-High)
L/s
167-183-200-217
233-250-267-300
350-400-433-467
350-400-450-517
cfm
353-388-424-459
494-530-565-636
742-847-918-989
742-847-953-1095
Noise level (Low-Mid2-Mid1-High)
dB <A>
29-32-34-36
31-33-35-37
36-38-41-43
36-39-42-44
(measured in anechoic room)
Insulation material
Polyeter sheet
Air filter
PP honeycomb
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter of
Liquid
mm(in.)
refrigerant pipe
ø6.35 (ø1/4) Flare
ø9.52 (ø3/8) Flare
ø9.52 (ø3/8) Flare
ø9.52 (ø3/8) Flare
Gas
mm(in.)
ø12.7 (ø1/2) Flare
ø15.88 (ø5/8) Flare
ø19.05 (ø3/4) Flare
ø19.05 (ø3/4) Flare
Field drain pipe size
mm(in.)
O.D. 26mm (1)
Standard
attachment
Document
Accessory
Installation Manual, Instruction Book
Optional parts
Remarks
Drain pump kit
PAC-SH83DM-E
PAC-SH84DM-E
High efficiency filter
PAC-SH88KF-E
PAC-SH89KF-E
PAC-SH90KF-E
Wireless remote controller kit
Installation
PAR-SL94B-E
4
SPECIFICATION
4-1. SPECIFICATIONS
OCH449A