background image

– 4 –

*1 The power consumption coefficient of AT-50A is 4 and that of an indoor unit is "1"*, which means that each AT-50A unit consumes power equivalent to

four indoor units. (*Indoor units receive power through the M-NET transmission line to maintain communication during power failure.) Refer to the
CITY MULTI DATABOOK for details. The total power consumption of the connected devices should not exceed the capacity of the power supply units.
The Design Tool by MITSUBISHI ELECTRIC allows its user to design air conditioning systems easily. 
AT-50A is compatible with the Design Tool version 3.9 or later. 
AT-50A can be connected to either TB7 or TB3. 
When connected to TB3, no power supply units are required.

• Address settings (Address overlaps are not allowed.)

Note

2. M-NET wiring design

(1) M-NET transmission cable specifications and restrictions

Address setting

Address range

Indoor unit

Assign the lowest address to the main indoor unit in the group, and assign sequential addresses to 
the rest of the indoor units in the same group.
Note: The following models require two addresses: PEFY-AF1200CFM and PEFY-AF1200CFM-R

1~50

Outdoor unit

Assign an address that equals the lowest indoor unit address in the same refrigerant system plus 
50.

51~100

Auxiliary outdoor unit 
(BC controller)

Assign an address that equals the address of the outdoor unit in the same refrigerant system 
plus 1.

52~100

LOSSNAY unit

Assign an arbitrary but unused address to each LOSSNAY unit after assigning an address to all 
indoor units.

1~50

Mr. Slim

®

 unit

Same rules as for the indoor units apply. An M-NET adapter (sold separately) is required.

1~50

MXZ unit

Same rules as for the indoor units apply. An M-NET interface (sold separately) is required.

1~50

M-NET remote controller

Assign an address that equals the address of the main indoor unit with the lowest address in the 
group plus 100. Add 150 instead of 100 to set a sub-remote controller.

101~200

Sub system controller

Assign an address that equals the lowest number of the group to be controlled plus 200.

201~250

DIDO 
(PAC-YG66DCA)

Assign an arbitrary but unused address to the controller after completing the address setting for 
the units with an address between 1 and 50. The number of controllable units depends on the 
number of channels used. (1 channel = 1 unit)

1~50

MA remote controller

Address setting is not required. The connection of two remote controllers requires the main/sub
setting for each controller to be made.

Cable
Specifications

Facility type

All facility types

Type

Shielded cable

CVVS · CPEVS · MVVS

No. of cores

2-core

Size

CVVS, MVVS: 1.25 mm² (AWG16) or larger

CPEVS: ø1.2 mm (AWG16 or its equivalent) or larger

Maximum indoor-outdoor transmission cable length

200 m [656 ft]

Maximum length of transmission line for centralized control and
indoor-outdoor transmission cables 
(Maximum cable distance via outdoor unit)

500 m [1640 ft]

*The maximum cable distance from the power supply unit to each outdoor 

unit or to the system controller is 200 m [656 ft].

• The system cannot be configured as shown in the examples below.

Groups that are not controlled by a main controller cannot be 
controlled from a sub controller.

Sub controllers cannot be controlled by two or more main controllers.

Each group cannot be controlled by two or more main 
controllers.

Group

Group

Group

Group

Group

Group

Group

Group

Group

Group

Main system controller 2

Main system controller 1

Main system controller

Sub system controller

Sub system controller

Main system controller 1

Main system controller 2

Summary of Contents for AT-50A

Page 1: ...ctric shock malfunctions smoke or fire do not operate the switches buttons or touch other electrical parts with wet hands To reduce the risk of injury or electric shock before spraying a chemical around the controller stop the operation and cover the controller To reduce the risk of injury or electric shock stop the operation and switch off the power supply before cleaning maintaining or inspectin...

Page 2: ...ical noise interference To reduce the risk of electric shock shorting or malfunctions keep wire pieces and sheath shavings out of the terminal block To reduce the risk of shorting current leakage electric shock or malfunctions keep the cables out of contact with controller edges To reduce the risk of electric shock malfunctions or fire seal the gap between the cables and cable access holes with pu...

Page 3: ...e controller 1 2 6 Installation Manual This manual 1 7 Instruction Book 1 8 CD ROM Instruction Book Installation Manual 1 2 Mounting bracket 1 AT 50A Power LED Touch panel For connection to the M NET A B Terminal for connection to the M NET cable non polarized External output adapter cable access hole External input adapter cable access hole Controller cover mounting screw SD memory slot for progr...

Page 4: ...or units apply An M NET interface sold separately is required 1 50 M NET remote controller Assign an address that equals the address of the main indoor unit with the lowest address in the group plus 100 Add 150 instead of 100 to set a sub remote controller 101 200 Sub system controller Assign an address that equals the lowest number of the group to be controlled plus 200 201 250 DIDO PAC YG66DCA A...

Page 5: ...nsure the M NET transmission cables and external input output cables are long enough to reach the controller Have extra cables to extend these cables as necessary To install the controller according to the instructions provided in sections a and b 1 above Include an extra 30 cm 12 in of cable to provide adequate slack in the cable Remove the sheath on the M NET transmission cable up to 20 cm 8 in ...

Page 6: ...the terminal block M NET transmission cable is non polarized Insert the cables in the groove on the controller so they will not be pinched when the cover is installed To route the cable along the wall surface Secure the cables in place with a cable cover and seal the gap between the cable cover and the controller with putty 5 Replace the cover Snap the cover into place and attach it to the control...

Page 7: ...ue between 0 2 and 1 seconds 4 Sample circuit recommended Mode External input signal setting Notes 1 Do not use external input Factory setting 2 Emergency stop Normal operation signal level signal When the units are not operating after receiving an emergency stop signal the ON OFF operation from the local remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the AT 5...

Page 8: ...during operation The maximum length of extension cable is 10 m 32 ft Use a cable of 0 3 mm 22AWG or thicker Insulate the area with vinyl tape where the controller cable and the extension cable are connected Relays lamps diode extension cables are field supplied Note The AT 50A has a slot for an SD memory card at the bottom that can be used to update software Refer to the Installation Manual for th...

Page 9: ... ON OFF Mode Set Temp and Filter Reset 12 External input mode Selects the external input mode 12 Filter sign Displays or suppresses the Filter sign on the HOME screen 12 Dry mode Includes or excludes Dry mode as an option for the operation mode 12 Set temperature range Schedule Selects the settable temperature range Standard 19 C 67 F to 28 C 83 F Low 8 C 46 F to 30 C 87 F Manual Settable to any a...

Page 10: ...enu Touch or HOME screen GRID zoom out view GRID zoom in view LIST view GROUP view Main Menu screen Login Page screen 1 Password Change screen Service Menu Service Menu screen Initial settings 1 Basic system Initial settings 2 Groups Groups Interlocked LOSSNAY Delete All System view Malfunction log Gas Amount Check Maintenance Test run Software update Button name Main Menu Service Menu Password Ch...

Page 11: ...begin the communication g The message shown above will appear on the screen displaying the initialization progress When initialization is complete the screen will automatically return to the HOME screen Initialization will take up to five minutes To change settings later perform a test run or verify the maintenance information 1 Touch MAIN MENU button on the HOME screen 2 Touch SERVICE MENU button...

Page 12: ...o ON OFF Mode Set Temp and Filter Reset External Input Mode 1 Press the External Input setting button labeled 1 in the figure to select between Not used Emergency Stop Level signal ON OFF Level signal and ON OFF Prohibit Permit Pulse signal Refer to the Installation Manual for detailed information on how to connect the AT 50A to external devices Filter Sign Display 1 Press the Filter Sign Display ...

Page 13: ...up Indoor units LOSSNAY units and general equipment cannot be combined in one group General equipment groups cannot include remote controller or system controllers Touch Page turn button to turn the pages and follow the directions below to make the settings for each group Group Name 1 Touch the Group Name Input button labeled 1 in the figure and enter the group name in the screen up to 16 characte...

Page 14: ...he Initial Settings 2 Groups button on the Service Menu and then touch the Interlocked LOSSNAY button on the Initial Settings 2 Groups screen to access the Interlocked LOSSNAY screen 1 Touch the LOSSNAY button labeled 1 in the figure On the popup window that appears check the address of the ventilation units to be interlocked with the operation of the indoor units 2 Touch the Interlocked indoor un...

Page 15: ...at support the test run function 2 Operation mode Touch this button to switch the operation mode 3 Pipe temperature The pipe temperature of the indoor unit with the lowest address in a given group will appear 4 Advanced settings Touch this button for advanced settings Display Function A Indoor temperature Indoor air temperature will appear B Unit address up down arrows Use the up down arrows to se...

Page 16: ... OK button If the message The DIP switch 4 is set to OFF appears check to make sure that the DIP switch 4 is turned to ON The DIP switch is located at the left bottom of the controller under the cover 4 Touch the OK button on the confirmation screen 5 Touch the OK button on the popup message to begin the update process 6 The lit LEDs on the three buttons F1 F2 and Collective ON OFF will indicate a...

Reviews: