Mitsubishi Electric AT-50A Installation Manual Download Page 15

– 15 –

2-4. Test run

To run a test, follow the procedure below.
(1) Touch the Test Run button on the Service Menu screen to access the Test Run screen.
(2) Touch the OFF(ON) button (labeled 

1

 in the figure) to run a test on the group.

Test Run screen

Test Run Advanced setting screen

(3) During the test run, verify that air conditioned air is blowing out of the supply air outlet.
(4) After checking for normal operation of each unit, stop the units through AT-50A or the local remote controllers. 

* Refer to the indoor unit installation manual for the detailed information about test run.

2-5. Maintenance

Touch the Maintenance button [ 

 ] on the Service Menu screen to access the Maintenance screen.

(1) To view the System information 

Touch [System View] button on the Maintenance screen to view a list of equipments connected to the same refrigerant system. 
* Only the ones whose startup procedures have been successfully completed will appear in the list.

(2) To view the Malfunction Log 

Touch the Malfunction Log button on the Maintenance screen to view. The latest 50 malfunctions will appear three at a time.

Button

Function

1

OFF(ON)/Test Run

Touch the OFF(ON) button to start a test run. 
Touch the Test Run button to stop the test run. 
(These buttons are active only for the units that 
support the test run function.)

2

Operation mode

Touch this button to switch the operation mode.

3

Pipe temperature

The pipe temperature of the indoor unit with the 
lowest address in a given group will appear.

4

Advanced settings

Touch this button for advanced settings.

Display

Function

A

Indoor temperature

Indoor air temperature will appear.

B

Unit address up/
down arrows

Use the up/down arrows to select the indoor unit 
whose pipe temperature you want to check.

C

Pipe temperature

The pipe temperature of the indoor unit whose 
address is shown on the screen will appear.

D

Remaining time

The remaining time for the test run will appear.

Display content

1

Outdoor unit address

The addresses of the outdoor units that are 
connected to AT-50A will appear. (The number in 
the parentheses indicates the address of the Sub 
unit.)

2

Indoor unit address

The addresses of the indoor units that are 
connected to given outdoor units will appear.

Display content

1

Occurrence date

The date on which the error occurred.

2

Error source unit address

The address of the unit with the error.

3

Error detection unit address

The address of the unit that detected the 
error.

4

Error code

The error code that corresponds to the error.

5

Clear Log button

Use this button to clear all records on the 
Malfunction Log.

* Refer to the Instruction Book on how to make the settings not mentioned in this 

manual (e.g., schedule settings and button lock settings).

3

4

2

1

A

D

C

B

1

2

5

4

3

2

1

Summary of Contents for AT-50A

Page 1: ...ctric shock malfunctions smoke or fire do not operate the switches buttons or touch other electrical parts with wet hands To reduce the risk of injury or electric shock before spraying a chemical around the controller stop the operation and cover the controller To reduce the risk of injury or electric shock stop the operation and switch off the power supply before cleaning maintaining or inspectin...

Page 2: ...ical noise interference To reduce the risk of electric shock shorting or malfunctions keep wire pieces and sheath shavings out of the terminal block To reduce the risk of shorting current leakage electric shock or malfunctions keep the cables out of contact with controller edges To reduce the risk of electric shock malfunctions or fire seal the gap between the cables and cable access holes with pu...

Page 3: ...e controller 1 2 6 Installation Manual This manual 1 7 Instruction Book 1 8 CD ROM Instruction Book Installation Manual 1 2 Mounting bracket 1 AT 50A Power LED Touch panel For connection to the M NET A B Terminal for connection to the M NET cable non polarized External output adapter cable access hole External input adapter cable access hole Controller cover mounting screw SD memory slot for progr...

Page 4: ...or units apply An M NET interface sold separately is required 1 50 M NET remote controller Assign an address that equals the address of the main indoor unit with the lowest address in the group plus 100 Add 150 instead of 100 to set a sub remote controller 101 200 Sub system controller Assign an address that equals the lowest number of the group to be controlled plus 200 201 250 DIDO PAC YG66DCA A...

Page 5: ...nsure the M NET transmission cables and external input output cables are long enough to reach the controller Have extra cables to extend these cables as necessary To install the controller according to the instructions provided in sections a and b 1 above Include an extra 30 cm 12 in of cable to provide adequate slack in the cable Remove the sheath on the M NET transmission cable up to 20 cm 8 in ...

Page 6: ...the terminal block M NET transmission cable is non polarized Insert the cables in the groove on the controller so they will not be pinched when the cover is installed To route the cable along the wall surface Secure the cables in place with a cable cover and seal the gap between the cable cover and the controller with putty 5 Replace the cover Snap the cover into place and attach it to the control...

Page 7: ...ue between 0 2 and 1 seconds 4 Sample circuit recommended Mode External input signal setting Notes 1 Do not use external input Factory setting 2 Emergency stop Normal operation signal level signal When the units are not operating after receiving an emergency stop signal the ON OFF operation from the local remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the AT 5...

Page 8: ...during operation The maximum length of extension cable is 10 m 32 ft Use a cable of 0 3 mm 22AWG or thicker Insulate the area with vinyl tape where the controller cable and the extension cable are connected Relays lamps diode extension cables are field supplied Note The AT 50A has a slot for an SD memory card at the bottom that can be used to update software Refer to the Installation Manual for th...

Page 9: ... ON OFF Mode Set Temp and Filter Reset 12 External input mode Selects the external input mode 12 Filter sign Displays or suppresses the Filter sign on the HOME screen 12 Dry mode Includes or excludes Dry mode as an option for the operation mode 12 Set temperature range Schedule Selects the settable temperature range Standard 19 C 67 F to 28 C 83 F Low 8 C 46 F to 30 C 87 F Manual Settable to any a...

Page 10: ...enu Touch or HOME screen GRID zoom out view GRID zoom in view LIST view GROUP view Main Menu screen Login Page screen 1 Password Change screen Service Menu Service Menu screen Initial settings 1 Basic system Initial settings 2 Groups Groups Interlocked LOSSNAY Delete All System view Malfunction log Gas Amount Check Maintenance Test run Software update Button name Main Menu Service Menu Password Ch...

Page 11: ...begin the communication g The message shown above will appear on the screen displaying the initialization progress When initialization is complete the screen will automatically return to the HOME screen Initialization will take up to five minutes To change settings later perform a test run or verify the maintenance information 1 Touch MAIN MENU button on the HOME screen 2 Touch SERVICE MENU button...

Page 12: ...o ON OFF Mode Set Temp and Filter Reset External Input Mode 1 Press the External Input setting button labeled 1 in the figure to select between Not used Emergency Stop Level signal ON OFF Level signal and ON OFF Prohibit Permit Pulse signal Refer to the Installation Manual for detailed information on how to connect the AT 50A to external devices Filter Sign Display 1 Press the Filter Sign Display ...

Page 13: ...up Indoor units LOSSNAY units and general equipment cannot be combined in one group General equipment groups cannot include remote controller or system controllers Touch Page turn button to turn the pages and follow the directions below to make the settings for each group Group Name 1 Touch the Group Name Input button labeled 1 in the figure and enter the group name in the screen up to 16 characte...

Page 14: ...he Initial Settings 2 Groups button on the Service Menu and then touch the Interlocked LOSSNAY button on the Initial Settings 2 Groups screen to access the Interlocked LOSSNAY screen 1 Touch the LOSSNAY button labeled 1 in the figure On the popup window that appears check the address of the ventilation units to be interlocked with the operation of the indoor units 2 Touch the Interlocked indoor un...

Page 15: ...at support the test run function 2 Operation mode Touch this button to switch the operation mode 3 Pipe temperature The pipe temperature of the indoor unit with the lowest address in a given group will appear 4 Advanced settings Touch this button for advanced settings Display Function A Indoor temperature Indoor air temperature will appear B Unit address up down arrows Use the up down arrows to se...

Page 16: ... OK button If the message The DIP switch 4 is set to OFF appears check to make sure that the DIP switch 4 is turned to ON The DIP switch is located at the left bottom of the controller under the cover 4 Touch the OK button on the confirmation screen 5 Touch the OK button on the popup message to begin the update process 6 The lit LEDs on the three buttons F1 F2 and Collective ON OFF will indicate a...

Reviews: