41 LSH Electric Logsplitter
15
Original Instructions Version August 19
10.6 Jammed log
Do not try to knock the jammed log off.
Knocking about will damage the machine
or may launch the logand cause accident.
1. Release both controls.
2. After the log pusher moves
back and completely
stops at its starting position,
insert a wedge wood
under the jammed log (see figure 15).
3. Start the log splitter to push the
wedge wood underthe jammed one.
4. Repeat above procedure with
sharper slopewedge woods until
the log is completely freed.
11. Electrical connection
The electrical motor installed is connected and ready for operation. The connection complies with the
applicable VDE and DIN provisions.
The customer‘s mains connection as well as the extension cable used must also comply with these
regulations.
Damaged electrical connection cable
The insulation on electrical connection cables is often damaged.
This may have the following causes:
• Passage points, where connection cables are passed through windows or doors.
• Kinks where the connection cable has been improperly fastened or routed.
• Places where the connection cables have been cut due to being driven over.
• Insulation damage due to being ripped out of the wall outlet.
• Cracks due to the insulation ageing.
Such damaged electrical connection cables must not be used and are life-threatening due to the
insulation
damage.
Check the electrical connection cables for damage regularly. Make sure that the connection cable does
not hang on the power network during the inspection. Electrical connection cables must comply with
the
applicable VDE and DIN provisions. Only use connection cables with the marking „H07RN“.
The printing of the type designation on the connection cable is mandatory.
For single-phase AC motors, we recommend a fuse rating of 16A (C) or 16A (K) for machines with a high
starting current (starting from 3000 watts)!