background image

11

The default digital input (DX) connections are as follows: 

•    D1—pump 1 (M150 runtime accumulator, M850 status and runtime accumulator)         
•    D2—pump 2 (M150 runtime accumulator, M850 status and runtime accumulator) 
•    D3—pump 3 runtime or simultaneous pump (1 and 2) runtime accumulator

*(M150) 

•    D4—high level float
•    D5—pump 1 fail
•    D6—pump 2 fail
•    D7—phase fail
•    D8—unassigned or multiple pump runtime accumulator

*(M850)

  

MyDro Digital Inputs feature software selectable input characteristics including:

•  Dry contacts with wire fault supervision (requires 1000 ohm EOL resistors)
•  Dry contacts no wire fault supervision (NF)
•  Strap on current sensing switches (Mission PN OP400) with wire fault supervision
•  Strap on current sensing switches (Mission PN OP400) without wire fault supervision

Note:

 The MyDro does not directly support the Wet Well Module. See the technical 

document, Wet Well Module with MyDro, if replacing M110 or M800 with Wet Well 

Module to MyDro.

Warning:

 Digital inputs require dry contacts. This means that wires running to 

these inputs must not supply any voltage. Use an interposing relay if there are no 

dry contacts available. 

The digital inputs are set as normally open (N/O) by default. You must use N/O contacts 

on pump runtime inputs. You may use either N/O or normally closed N/C contacts on 

digital inputs 4 through 8. Notify Mission Technical Support (or indicate on RTU setup 

form) to change the default settings (refer to Figure 2).Connect the shields of digital input 

wires to the grounding lug located inside the RTU. 

 

Pump Runtime Inputs: On M150 RTUs, only inputs D1–D3 can be configured for pump 

runtimes. However, they can also be set as alarm inputs. D4–D8 on an M150 can only 

be configured as alarm inputs. 

D3*

 can be used for simultaneous runtimes by configuring 

digital input on touch screen.

On M850 RTUs, D1–D8 (on the main board) can be configured as pump runtime, pump 

runtime with alarm, or alarm inputs. As an option, the system can report multiple pump 

runtimes on M850 RTUs on 

D8.*

Summary of Contents for MyDro M150

Page 1: ...150 850 Installation Manual PMS 660...

Page 2: ...ion about available support resources including weekly webinars training tutorials quarterly newsletters troubleshooting documentation and Twitter updates Mission Technical Support is available 24 7 3...

Page 3: ...nnectivity Test Chapter 3 Antenna Installation Chapter 4 RTU Installation and Wiring Chapter 5 RTU Startup Chapter 6 Test the Installation Chapter 7 Site Commissioning Appendix A Terminology Appendix...

Page 4: ...amp hour Flying Lead Transformer 120 VAC to 12 VAC 1 2 amp Universal Antenna Mount Kit 11 RG58 cable with SMA M connector pole or wall mount bracket dual band antenna whip mini whip antenna 2 pole cla...

Page 5: ...d bases if no dry contacts are available 5 16 nut driver Interposing relay if output relays will be used Phillips head screwdriver Sealant Ladder for antenna mounting Available Input Output Expansion...

Page 6: ...he RTU from the box and place it on or near the control panel it will be monitoring Remove the antenna cable and antenna whip from the package and hand tighten the SMA M connector to the radio SMA F c...

Page 7: ...7 Figure 1 Main Printed Circuit Board Wired for Site Survey...

Page 8: ...the nut from the molded antenna base Feed the molded antenna base through the square cut out on the bracket Place the molded antenna base in the circle cutout Warning Secure the molded antenna base to...

Page 9: ...enclosure Cut lengthen or shorten the coaxial cable Mission can supply antenna extension cables and connectors up to 50 feet For lengths above this limit another RTU mounting location should be consid...

Page 10: ...l float in an intrinsically safe manner install it now Refer to the MyDro Expansion Module Installation Manual for more information 5 Terminate digital inputs Refer to the wiring diagram on the M150 M...

Page 11: ...M110 or M800 with Wet Well Module to MyDro Warning Digital inputs require dry contacts This means that wires running to these inputs must not supply any voltage Use an interposing relay if there are n...

Page 12: ...ilable on the mainboard refer to Figure 3 These inputs can accept a 4 20 mA or 0 5 volt signal Position analog channel signal selector to the left for a 4 20 mA signal and to the right for a 0 5 volt...

Page 13: ...default or normally closed refer to Appendix B Warning Relay behavior on communication failure is configurable under the Config Menu Relay Comm Fail Setup as Deenergize or No Change Warning If power...

Page 14: ...nductors going to the AC in connection see Figure 4B Mount the transformer in the control panel not the Mission RTU It is very important to only provide 12 16 VAC to the Mission mainboard AC input Hoo...

Page 15: ...the network If the RTU does not connect after two attempts contact Technical Support Figure 6 Battery Wiring 2 Check the wiring connections before powering the pump station If the wiring is correct po...

Page 16: ...16 Figure 7 Test the Installation...

Page 17: ...battery Remove the AC fuse and confirm the RTU stays online Replace the AC fuse 3 Test the radio connection Check the radio status on the LCD screen It should read connected If not call Technical Sup...

Page 18: ...You should see a list of alarm events with event time and the result Call Mission Technical Support after testing the installation to enable the device for alarm call outs A technician will verify pro...

Page 19: ...he RTU should be distributed to your operators as a how to document to get operators started with the Mission system It covers the basics of the system capabilities monitoring and alarming and helpful...

Page 20: ...led to turn on pumps wells valves or security lights Multiple M850s can be linked so an event at one station causes a relay change at another Mission s Tank and Well Control option and Intertie rely o...

Page 21: ...outside the RTU to minimize the chances of induced voltages A five amp hour battery with a charging circuit powers the RTU for 18 50 hours M850 and M150 during a power failure AC power fail alarm wil...

Page 22: ...22 Appendix B Output Relay Diagram...

Page 23: ...23 Installation Notes...

Page 24: ...as well as the marketing website Newsletter The quarterly newsletter provides useful information for water and wastewater professionals Each issue includes tips and tricks new features interesting ind...

Reviews: