QMP-5100B and QMP-5101B Installation and Operation Instructions

5

QMP-5100B/QMP-5101B Paging Wiring

The wiring connection between the QMP-5100B/QMP-5101B Master Paging Module  in Lobby Panel and the QIF-5000B 
Interface Module in the Audio Cabinet, is shown below.

QMP-5100B/QMP-5101B to QIF-5000B Wiring 

The interface wiring between the QIF-5000B and the QMP-5100B/QMP-5101B are as follows.

The maximum wiring run from the QIF-5000B to the QMP-5100B/QMP-5101B is 1000 feet or 305 metres. All RS-485 must be 
point-to-point from the QIF-5000B, to the QMP-5100B or QMP-5101B.  

No star-wiring or T-tapping is allowed.

 The 120 ohm 

End-of-Line Resistor on the RS-485 Output terminals is removed on all except the last wired Module.

MIC+, MIC-, SHLD:

18-22 AWG Twisted Shielded Pair

RS485+, RS485-, SHLD:

18-22 AWG Twisted Shielded Pair

PTT+, PTT:

18-22 AWG Twisted Pair

24 VDC Power:

16 -18 AWG

FACTORY INSTALLED

3.9K EOL RESISTOR

QMP-5100B/QMP-5101B

QIF-5000B
      J1

 

+

+

-

-

S

S

1

-

NOT USED

+

2

3

4

5

6

7

8

S

NOT USED

MIC.

RS485

MIC.  IN

MIC.  OUT

TWISTED SHIELDED
PAIR CABLE

FACTORY INSTALLED

3.9K EOL RESISTOR

QMP-5100B/QMP-5101B

+

-

PTT  OUT

FACTORY INSTALLED
120R EOL RESISTOR

QMP-5100B/QMP-5101B

+

+

-

-

S

S

RS485  IN

RS485  OUT

QMP-5100B/QMP-5101B

QIF-5000
      J2

1

-

NOT USED

+

2

3

4

5

6

7

8

NOT USED

PTT

TWISTED SHIELDED
PAIR CABLE

S

+

-

MIC.

PTT IN

+

-

+

-

24VDC  OUT

24VDC IN

+

-

-

+

24VDC

NOT USED

NOT USED

NOT USED

NOT USED

J1

Identified by 

RED 

LABEL

J2

Identified by 

BLUE 

LABEL

Summary of Contents for QMP-5100B Series

Page 1: ...ior notice U S A 42 20 Steve Reynolds Blvd Unit 17 Norcross Atlanta GA 30093 Tel 1 888 660 4655 Fax 1 888 660 4113 www mircom com QMP 5100B and QZP 5100 Series Firefighters Master Paging Module and An...

Page 2: ......

Page 3: ...oduction 1 Mounting 1 Labels 1 Paging Modules 2 Single Stage Operation 4 Two Stage Operation 4 QMP 5100B QMP 5101B Paging Wiring 5 QMP 5100B and QMP 5101B Paging Configuration 6 Paging Operation 7 QMP...

Page 4: ...Contents ii...

Page 5: ...io Paging Zones for ease of ribbon cable connection Labels Slide in labels which are supplied with the QMP 5100B and QMP 5101B as NP 776 E1 E2 English or F1 F2 French are to be separated and inserted...

Page 6: ...ter Paging Module See also the section Paging Operation The QMP 5101B Master Paging Module has a ribbon cable connection to the first QZP 5101 Zone Module and wiring terminals for connection to the QI...

Page 7: ...MPLIFIER TROUBLE CIRCUIT TROUBLE RESET LAMP TEST DIGITIZED MESSAGES P3 P2 SW1 SW2 1 8 1 1 1 8 S S MIC IN MIC OUT PTT IN PTT IN 24VDC INPUT 24VDC OUTPUT RS 485 INTERFACE INPUT I S I OUTPUT I S I CONNEC...

Page 8: ...There are two buttons and three LEDs per Zone The middle amber LED beside the top button indicates Zone Trouble The upper green LED by the top button indicates whether that Zone is selected for Voice...

Page 9: ...llowed The 120 ohm End of Line Resistor on the RS 485 Output terminals is removed on all except the last wired Module MIC MIC SHLD 18 22 AWG Twisted Shielded Pair RS485 RS485 SHLD 18 22 AWG Twisted Sh...

Page 10: ...F OFF ERROR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 DIP Switch SW 1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF OFF ON ON ON ON OFF OFF...

Page 11: ...ve green LED illuminates steadily This LED will not function if the DIP Switch SW1 5 is set to ON Warden Page Indicates that the Warden Page function is active green LED illuminates steadily QMP 5100B...

Page 12: ...operative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a fire alarm system After a power i...

Page 13: ...s televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are...

Page 14: ...s caused by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper ma...

Page 15: ...information is accurate as of the date of publishing and is subject to change or revision without prior notice at the sole discretion of the Company WARNING Mircom Technologies Ltd recommends that the...

Page 16: ...5 660 4113 Mircom 2011 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 411...

Reviews: