QMP-5100B and QMP-5101B Installation and Operation Instructions
1
QMP-5100B, QMP-5101B, QZP-5101, QZP-5102 and QZP-5103
Firefighters’ Master Paging Module System Installation, Wiring,
And Operation Instruction
Introduction
MIRCOM’s FireFighters’ Master Paging Module System is used as a Multi-Zoned System (with the QZP-5101,
QZP-5102 and QZP-5103 Paging Selector Panels).
Mounting
The modules mount in any of the BB-1000 Series Remote Annunciator enclosures except for the QMP-5101B
which mounts into a BB-5008 or BB-5014 backbox. For the QMP-5100B Master Paging Module, the included
extended window module must be installed in place of the existing window. In any BB-1000 enclosure, the QMP-
5100B is mounted bottom-most, and one to five QZP Selector Panels above, for up to 120 Audio Paging Zones for
ease of ribbon cable connection.
Labels
Slide-in labels which are supplied with the QMP-5100B and QMP-5101B as NP-776 (E1 & E2 English or F1 & F2
French) are to be separated and inserted into the appropriate pockets. The QZP-5101 includes blank labels for
Audio Paging Zone information.
Chassis Ground
Connect at least one of the BB-1000 Series, BB-5008 or BB-5014 backboxes’ Earth-Ground points (Chassis
Ground) to Earth Ground (cold water pipe).
Power Supply
Only the master paging QMP-5100B or QMP-5101B module requires power, 24 VDC, 200 mA DC from QIF-5000B
J2, Terminals 7 & 8.
Connectors
On the QMP-5100B and QMP-5101B, P3 is the connection for the Master Paging Module to the QZP-5101. On the
QZP-5101, P1 connects to the Master Paging Module (QMP-5100B or QMP-5101B) or the previous QZP Selector
Panel, and P2 connects to the next QZP Selector Panel. The QZP-5102 has two special cables, refer to cable
diagram packed with the unit for proper installation instruction.