30
2. Installer Troubleshooting Guide
refer to section:
'Important safety Information'
first and refer also to
'user Trouble
shooting Guide'
.
The following troubleshooting solutions may require the removal of the cover of the
shower. The cover should only be removed by a competent tradesperson and when
doing so they should be aware of the following:
Isolate the electrical and water supply before initially removing the
•
cover.
Make sure ribbon cable is disconnected when removing the front
•
cover and reconnect when maintenance is complete.
Mains connections are exposed when the cover is removed.
•
refer to wiring diagram before making any electrical connections.
•
Make sure all electrical connections are tight to prevent arcing/
•
overheating.
Make sure all plumbing connections are watertight.
•
When following these instructions, it is sometimes necessary to examine the
appliance with the electrical and water supplies turned
on
. It is therefore essential
that the appropriate safe working practices are followed in accordance with the
current health and Safety Legislation.
If conducting a continuity check using a multimeter, make sure the electrical supply
is
IsoLaTeD
.
Fault Code Indicator Display Possible Cause/Rectification
a
OR
problem with incoming water supply. Isolator
valves closed, filter blocked or incoming water
supply blocked.
1.
check all isolator valves are fully open.
2.
clean / replace filter, refer to section:
'
Maintenance'
.
3.
check plumbing system for blockages.
0
Unidentified Error.
1.
reset / recommission.
2.
replace control pcb.