The Charger Active (green) LED illuminates in a steady state when the Charger is
on. The Charger Active LED will extinguish when there is no acceptable AC present.
The DC Breaker On (green) LED illuminates in a steady state when the DC breaker
is in the On position. The DC Breaker On LED will extinguish when the DC breaker
is in the Off position.
INDICATOR PANEL
REAR PANEL
1. The DC Circuit Breaker connects and disconnects the DC bus voltage from the
Battery Pack to the UPS. The DC Circuit Breaker will trip in the event of a DC over-
current condition.
2. The External Battery connector is for Daisy Chaining additional Battery Packs.
3. The dipswitch is for setting the input voltage for the Battery Pack's internal charger.
4. The AC Outlet is for connecting the output cable to Daisy Chain additional Battery
Packs.
5. The AC Inlet is for connecting the input power cord to operate the Charger.
6. The Input Breaker will trip in the event that the Internal Charger draws excessive
current.
7. The External Ground Stud is for connecting an external ground wire.
8. The External Battery cable is for connecting the Battery Pack to the UPS or Daisy
Chaining additional Battery Packs.
INSTALLATION PLACEMENT
This Battery Pack series is
ONLY
intended to be installed in an indoor tem-
perature controlled environment that is free of conductive contaminants. DO
NOT operate the Battery Pack in: extremely dusty and/or unclean areas, loca-
tions near heating devices, water or excessive humidity, or where the Battery
Pack is exposed to direct sunlight. Select a location, which will provide good
air circulation for the Battery Pack at all times.
Route power cords so they
cannot be walked on or damaged. This Battery Pack series is not for use in a
computer room as defined in the Standard for the Protection of Electronic
Computer/Data Processing Equipment ANSI/NFPA 75. Typical battery life is 3
to 5 years. Environmental factors do affect battery life. High temperatures,
poor utility power, and frequent, short duration discharges have a negative
impact on battery life.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the Battery Pack. Place the Battery Pack in the final desired location and
complete the rest of the installation procedure.
WARNING!
These Battery Packs are extremely heavy. Any time
the Battery Pack has to be handled be sure to use, enough person-
nel, strong supports and equipment to safely handle the Battery Pack.
ENVIRONMENTAL
Operating Temperature (max)
Operating/Storage Humidity
Operating Elevation
0 to 40
°
C (+32 to +104
°
F)
95% Non-Condensing
0 to 3,000m (0 to +10,000 ft)
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
Storage Temperature
-15 to +45
°
C (+5 to +113
°
F)
Audible Noise at 1 m (3 ft.)
<45 dBA
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT
THE BATTERY PACK.
The mounting brackets are
ONLY
for se-
curing the Battery Pack to the rack.