REPLACING THE BATTERY

WARNING!

This Battery Pack contains potentially hazardous voltages.  Do
not attempt to disassemble the Battery Pack beyond the bat-
tery replacement procedure.  These Battery Packs contain no
user serviceable parts.  Repairs and Battery replacement must
be performed by

 QUALIFIED SERVICE PERSONNEL ONLY.

Do not open or mutilate batteries.  Released electrolyte is harm-
ful to the skin and eyes and may be toxic.

CAUTIONS:

(QUALIFIED

 

SERVICE PERSONNEL ONLY)

Do not dispose of batteries in a fire.  The batteries may explode.
The batteries in this Battery Pack are recyclable.  Dispose of
the batteries properly.  The batteries contain lead and pose a
hazard to the environment and human health if not disposed of
properly.  Refer to local codes for proper disposal requirements
or return the battery to the supplier.

The battery system can still present a risk of electrical shock.  These batteries
produce sufficient current to burn wire or tools very rapidly, producing molten
metal.  Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the
    battery terminals.
6. Determine if the battery is inadvertently grounded.  If the battery is, remove
     the source of the grounding.  Contact with any part of a grounded battery
     can result in an electrical shock.  The likelihood of such shock will be re-
     duced, if such grounds are removed during installation and maintenance.

These Battery Packs have an easy to replace hot-swappable batteries.  Please
read all of the WARNINGS and CAUTIONS before attempting to service the
batteries.  Typical battery life is 3 to 5 years.  Environmental factors do affect
battery life.  High temperatures, poor utility power, and frequent, short duration
discharges have a negative impact on battery life.

  NOTE:  

If there is a power

interruption while replacing the hot-swappable batteries, with the UPS on, the
load will not be backed up.

BATTERY REPLACEMENT PROCEDURE

(QUALIFIED

 

SERVICE PERSONNEL ONLY)

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERY MODULES

Hot-swappable batteries mean that the batteries can be replaced without
powering down the whole UPS system.

NOTE:  

If there is a power interruption while replacing the hot-swappable batter-

ies, with the UPS on, the load will not be backed up.  To hot-swap the Battery
Pack's battery modules start with step number 6.
1.  Turn off the equipment that is plugged into the output receptacles of the
    UPS.
2.  Press and release the On/Off/Test button on the front panel to turn the UPS
     off.
3.  Unplug the UPS's AC power cord from the AC wall outlet.
4.  Unplug the equipment from the output receptacles of the UPS.
5.  Unplug the computer interface cable from the rear panel of the UPS.
6.  Turn off all of the DC circuit breakers on the rear panel of all of the Battery
     Packs.
7.  Unplug all of the Battery Pack's AC power cords from the AC wall outlet.
8.  Disconnect all of the external battery cables.
9.  Remove the front panel retaining screws.  (FIG. 2)
10.  Lay the front panel on top of the Battery Pack.
11.  Remove the retaining screws for the battery retaining brackets.  (FIG. 3)
12.  Remove the battery retaining brackets. (FIG. 3)
13.  Disconnect the battery connectors (red and black) from each of the battery
      modules. (FIG. 4)
14.  Grasp one of the battery pull tabs and gently pull the battery module out of
       the Battery Pack and set on the floor. (FIG. 4)
15.  Grasp the other battery pull tab and gently pull the battery module out of
       the Battery Pack and set on the floor. (FIG. 4)

NOTE:  

Use Caution, the battery modules are heavy.

Replace the batteries with the same number and type as originally
installed in the Battery Pack.  These batteries have pressure oper-
ated vents.  These Battery Packs contain sealed non-spillable
maintenance free lead acid batteries.

CAUTION:

BP36RTXL

Internal
Battery
Module
Part #

BM0033

Model #

BP72RTXL

BM0034

BP24RTXL

BP48RTXL

BM0038

BM0039

Summary of Contents for BP24RTXL

Page 1: ...Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000433 R4 User s Manual BPRTXL Series Battery Packs...

Page 2: ...ight 2013 1 Introduction 2 2 Controls and Indicators 6 3 Installation 7 4 Operation 14 5 Troubleshooting 15 6 Replacing the Battery 16 7 Obtaining Service 20 8 Specifications 21 9 Limited Product Warr...

Page 3: ...ies is not for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Processing Equipment ANSI NFPA 75 Select a location which will provide good air circulat...

Page 4: ...user s authority to operate the equipment Life Support Policy As a general policy we do not recommend the use of any of our products in life support applications where failure or malfunction of the pr...

Page 5: ...aminants DO NOT operate the Battery Pack in extremely dusty and or unclean areas loca tions near heating devices water or excessive humidity or where the Battery Pack is exposed to direct sunlight Sel...

Page 6: ...of the front panel push the LED face plate outwards the face plate will pop out Position the LED face plate so that it reads in the up right position Re install the front panel on the Battery Pack 5...

Page 7: ...outwards the face plate will pop out Position the LED face plate so that it reads in the up right position Re install the front panel on the Battery Pack 9 The Wallmount Configuration is complete See...

Page 8: ...eakers and UPS s power switch are in Off position CAUTION If the Battery Pack s DC circuit bre aker is in the On position the battery voltage will be present at the open end of the Battery Pack s exte...

Page 9: ...voltage for the Battery Pack s internal charger The dipswitch must be set with the DC circuit breaker in the Off position and with the input power cord disconnected from the AC wall outlet Set the dip...

Page 10: ...discharges have a negative impact on battery life NOTE If there is a power interruption while replacing the hot swappable batteries with the UPS on the load will not be backed up BATTERY REPLACEMENT...

Page 11: ...ttery cables 23 Plug in all of the Battery Pack s AC power cords into the AC wall outlet 24 Turn on all of the DC circuit breakers on the rear panel of all of the Battery Packs 25 Properly dispose of...

Page 12: ...reach your dealer or if they cannot resolve the issue call or fax the Technical Support department at the following numbers Voice phone 972 446 7363 FAX line 972 446 9011 or visit our Web site at www...

Page 13: ...or other written instructions Any technical advice furnished before or after delivery in regard to use or application of Para Systems equipment is furnished without charge and on the basis that it rep...

Reviews: