REPLACING THE BATTERY
WARNING!
This Battery Pack contains potentially hazardous voltages. Do
not attempt to disassemble the Battery Pack beyond the bat-
tery replacement procedure. These Battery Packs contain no
user serviceable parts. Repairs and Battery replacement must
be performed by
QUALIFIED SERVICE PERSONNEL ONLY.
Do not open or mutilate batteries. Released electrolyte is harm-
ful to the skin and eyes and may be toxic.
CAUTIONS:
(QUALIFIED
SERVICE PERSONNEL ONLY)
Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this Battery Pack are recyclable. Dispose of
the batteries properly. The batteries contain lead and pose a
hazard to the environment and human health if not disposed of
properly. Refer to local codes for proper disposal requirements
or return the battery to the supplier.
The battery system can still present a risk of electrical shock. These batteries
produce sufficient current to burn wire or tools very rapidly, producing molten
metal. Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the
battery terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, remove
the source of the grounding. Contact with any part of a grounded battery
can result in an electrical shock. The likelihood of such shock will be re-
duced, if such grounds are removed during installation and maintenance.
These Battery Packs have an easy to replace hot-swappable batteries. Please
read all of the WARNINGS and CAUTIONS before attempting to service the
batteries. Typical battery life is 3 to 5 years. Environmental factors do affect
battery life. High temperatures, poor utility power, and frequent, short duration
discharges have a negative impact on battery life.
NOTE:
If there is a power
interruption while replacing the hot-swappable batteries, with the UPS on, the
load will not be backed up.
BATTERY REPLACEMENT PROCEDURE
(QUALIFIED
SERVICE PERSONNEL ONLY)
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERY MODULES
Hot-swappable batteries mean that the batteries can be replaced without
powering down the whole UPS system.
NOTE:
If there is a power interruption while replacing the hot-swappable batter-
ies, with the UPS on, the load will not be backed up. To hot-swap the Battery
Pack's battery modules start with step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS
off.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Turn off all of the DC circuit breakers on the rear panel of all of the Battery
Packs.
7. Unplug all of the Battery Pack's AC power cords from the AC wall outlet.
8. Disconnect all of the external battery cables.
9. Remove the front panel retaining screws. (FIG. 2)
10. Lay the front panel on top of the Battery Pack.
11. Remove the retaining screws for the battery retaining brackets. (FIG. 3)
12. Remove the battery retaining brackets. (FIG. 3)
13. Disconnect the battery connectors (red and black) from each of the battery
modules. (FIG. 4)
14. Grasp one of the battery pull tabs and gently pull the battery module out of
the Battery Pack and set on the floor. (FIG. 4)
15. Grasp the other battery pull tab and gently pull the battery module out of
the Battery Pack and set on the floor. (FIG. 4)
NOTE:
Use Caution, the battery modules are heavy.
Replace the batteries with the same number and type as originally
installed in the Battery Pack. These batteries have pressure oper-
ated vents. These Battery Packs contain sealed non-spillable
maintenance free lead acid batteries.
CAUTION:
BP36RTXL
Internal
Battery
Module
Part #
BM0033
Model #
BP72RTXL
BM0034
BP24RTXL
BP48RTXL
BM0038
BM0039