20
© MINOTAIR Ventilation Inc. - www.minotair.com
(PENTACARE-V12-OWNER'S MANUAL-2019-Rev-014)
C
ALCULATING
V
ENTILATION
A
IRFLOW
•
The airflow rate of fresh air and stale air required throughout the house must be
calculated by adding together the airflow required for each room, as indicated in
the shaded columns below, unless calculated by a qualified professional. Airflows
are denoted in cubic feet per minute (cfm) or liters per second (l/s).
•
The smaller a room is in comparison to the other rooms, the closer the airflow rate
must be to the “Min” value.
Bigger rooms will require airflow rates closer to the
“Max”
value.
For each dwelling
Recommended airflow for
each room
Air ducts diameter
for each room
cfm
l/s
in
mm
SUP
PLY
Rooms requiring a fresh air supply*
Min Max Min Max Min Max Min Max
Each bedroom (one person)
10
20
5
10
5
5 125 125
Each bedroom (two persons)
20
30
10
15
5
6 125 150
Home office
10
20
5
10
5
5 125 125
Main lounging room (living room)
10
20
5
10
5
6 125 150
Each floor not already serviced by air supply
10
20
5
10
5
6 125 150
Basement if not already serviced by air supply
10
20
5
10
5
6 125 150
Optional rooms to be supplied with fresh air*
Dining room
10
20
5
10
5
6 125 150
Family room
10
20
5
10
5
6 125 150
Play room
10
20
5
10
5
6 125 150
Kitchen
(This will help the range hood work better).
10
20
5
10
5
6 125 150
Any other furnished room
10
20
5
10
5
5 125 125
EXT
RACTIO
N
Recommended rooms for stale air extraction*
Bathroom or shower
50
80
25
40
5
6 125 150
Restroom
10
20
5
10
5
5 125 125
Kitchen
(Not recommended. Use a range hood instead.)
(Minimum distance between the return grille and any cooking
surface must be 3 m (10 ft.)).
10
20
5
10
5
6 125 150
Laundry room
10
20
5
10
5
5 125 125
Basement
10
20
5
10
5
6 125 150
* Treat each room comprised in an open space as an individual room
Required fresh air supply
Write result
Main ducts
minimum diameter
cfm
l/s
cfm l/s
in mm
Total fresh air supply
1,2
Your
answer
Your
answer
≤
90
≤
40 6 150
1. Input this value into the microcontroller.
> 90 > 40 8 200
2. The total exhaust airflow must be identical
Table 1
–
Airflow planning.