© MINOTAIR Ventilation Inc. - www.minotair.com
19
(PENTACARE-V12-OWNER'S MANUAL-2019-Rev-014)
C
ONNECTION TO AN
I
NDEPENDENT
S
YSTEM OF
V
ENTILATION
D
UCTS
•
This type of installation is required when the house is heated through electric
baseboards or a radiant system. Since these systems do not include forced air
ventilation ductwork, it is necessary to install a dedicated system of ventilation
ducts.
•
Like the previous method, stale air and moisture will be extracted directly at the
source through dedicated ducts to ensure better humidity management.
Therefore, one will be able to fully benefit from the HumiWatch365
©
system.
•
For this type of installation, it is
mandatory
to include a section of acoustic flexible duct
measuring 1 m (3 ft) at the end of each supply branch. This will soundproof the air supply.
The same must be done for the ducts serving the rooms where silence is sought.
IMPORTANT
: Only use acoustic flexible ducts capable of withstanding a negative static
pressure of 1.5 in H
2
O to prevent the extraction ducts liner from imploding. Moreover, if
the flexible duct must move moist air (humidifier, bathrooms), the insulation must be
protected by a vapor barrier located between the liner and the insulation. The Minotair
AcoustiCare©
series of flexible ducts and prefabricated mufflers are products that meet all
these requirements for peace of mind installations.
Figure 11
–
Connection to an independent system of ventilation ducts.
(The two MINOTAIR center ports are swapped for more clarity in the drawing)