The MINOTAIR must be installed using one of the three following methods:
o
Connection to a forced air ventilation system
–
Simplified method.
o
Connection to a forced air ventilation system
–
Extraction at the source.
o
Connection to an independent system of ventilation ducts.
C
ONNECTION TO A
F
ORCED
A
IR
V
ENTILATION
S
YSTEM
–
S
IMPLIFIED
M
ETHOD
•
This is the easiest installation method, though not necessarily the preferred one. It
will provide fresh air to all rooms supplied by the ventilation system. Stale air and
humidity extraction is done through the return plenum which could make humidity
management more difficult than if the extraction were done at the source.
•
This method is only possible if the MINOTAIR can be installed in the same room
where the forced-air system ventilator is located.
•
It is required that the forced air ventilator runs continuously or ventilator
operations is
interlocked with the “G” terminal of the MINOTAIR.
•
A minimum distance of 6 ft. (2 m) between the return and supply connections is
required.
Figure 9
–
Connection to a forced air ventilation system
–
Simplified method.
(The two MINOTAIR center ports are swapped for more clarity in the drawing)
NOTE:
Refer to the section about
to assess the need to
add a register key at this location.