Pellerin Milnor Corporation
Figure 1. Round duct elbow fabrication
Elbow radius
Segmented elbows
Legend
D...
Cross-section diameter
Rl. . .
Long radius (Rl = 1.5 x
D*
Rs. . .
Short radius (Rs = D)*
1...
6-segment to smooth elbow
- best
2...
3-segment elbow -
acceptable
3...
2-segment or right angle el-
bow - do not use
2.3.3.
Vents
BNDDUI01.C11 0000086881 A.10 A.11
Released
Wind loads can contribute significantly to variations in the external pressure drop felt by dryers.
Only the vent designs identified with a check mark in the figure below.adequately counteract the
effect of wind load.
Do not use a screen in the vent for the main air inlet.
Figure 2. Vent Designs
3.
Duct Layout and Pressure Drop Calculations
BNDDUI01.R01 0000086879 A.10
Released
3.1.
Units of Measure Used in the Calculations
BNDDUI01.R02 0000086878 A.10
Released
Table 1. Units of Measure
Type of
Measurement
English Unit
Metric Unit
Abbreviated
Term
Abbreviated
Term
Short length
in
inches
(mm)
millimeters
Long length
ft
feet
(M)
meters
Air flow
scfm
standard cubic feet
per minute
(nlpm)
normal liters
per minute
Air and Duct Requirements for Milnor
®
Pass-through Dryers
52
Summary of Contents for 6458
Page 2: ......
Page 8: ......
Page 9: ...Safety 1 5 ...
Page 32: ......
Page 33: ...Installation 2 29 ...
Page 75: ...Installation Drawings 3 71 ...
Page 76: ......
Page 77: ...73 ...
Page 78: ...74 ...
Page 79: ...75 ...
Page 80: ......
Page 81: ...77 ...
Page 82: ...78 ...
Page 83: ...79 ...
Page 84: ...80 ...
Page 85: ...81 ...
Page 86: ......
Page 87: ...83 ...
Page 88: ...84 ...
Page 89: ...85 ...
Page 90: ...86 ...
Page 91: ...87 ...
Page 92: ...88 ...
Page 93: ...89 ...