Flooded type water cooled screw chiller (PCB Control)
59
IV. Electrical control
1.
Electrical data
LSBLGWXXX/MCF
365
465
560
750
825
925
1120
1230
1500
Standard voltage
V
380V~3Ph~50Hz+N+PE
Voltage range
V
342~418
Max. running current
A
162
200
236
311
354
380
472
518
622
Max. power consumption
kW
93.5
116.8
141.9
182.9
205.8
222
283.8
215.8 365.8
Rated current
A
106
133
162
208
253
266
324
359
417
Compressor A
Locked rotor Amps.
A
810
875
1340
1990
810
875
1340
1430
1990
Max. allowed current
A
219.6
274.3
333.2
429.5
241.6
260.7
333.2
369.6 429.5
Rated current
A
106
133
162
208
126.5
133
162
179.5 208.5
Rated power
kW
62
78
95
126
74
78
95
105
126
Compressor B
Locked rotor Amps.
A
--
--
--
--
810
875
1340
1430
1990
Max. allowed current
A
--
--
--
--
241.6
260.7
333.2
369.6 429.5
Rated current
A
--
--
--
--
126.5
133
162
179.5 208.5
Rated power
kW
--
--
--
--
74
78
95
105
126
Crankcase heater
Voltage
V
220
220
220
220
220
220
220
220
220
Total input
kW
0.3
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
Total Amps.
A
1.36
1.36
1.36
1.36
2.72
2.72
2.72
2.72
2.72
Note:
1. Customer to specify the exact nominal power supply available at site so that electrical components are selected
accurately.
2. Main power must be supplied from a single field supplied and mounted fused circuit breaker.
3. The compressor crankcase heaters must be energized for hours before the unit is initially started or after a prolonged
power disconnection.
4. All field wining must be in accordance with local standards.
5. Neutral line required on 380V-3Ph-50Hz(5 wires) power supply.
6. Rated load Amps values are on nominal conditions.
7. The ±10% voltage variation from the nominal is allowed for a short time not permanent.