Flooded type water cooled screw chiller (PCB Control)
13
3.
Specifications
Single head
MWSC_A-FB3
340
440
540
690
805
890
Cooling capacity
kW
340
440
540
690
805
890
Power input
kW
60
77
94
120
140
155
EER
kW/kW
5.66
5.71
5.74
5.75
5.75
5.74
Semi-hermetic screw compressor
Circuit A
Quantity
1
1
1
1
1
1
Circuit B
Quantity
--
--
--
--
--
--
Oil recharge
Circuit A
L
18
20
23
28
40
40
Circuit B
L
--
--
--
--
--
--
Refrigerant
Type
R134a
Circuit A
kg
130
145
160
200
230
250
Circuit B
kg
--
--
--
--
--
--
Control Type
EXV+Orifice
Evaporator
Type
Shell and tube flooded
Water content
L
150
170
190
210
240
270
Water flow
m³/h
58
76
93
119
138
153
Pressure drop
kPa
55
49
53
46
39
39
Max. pressure
kPa
1000
1000
1000
1000
1000
1000
Connection type
Victaulic coupling
Water inlet/outlet pipe dim.
mm
150
150
150
200
200
200
Condenser
Type
Shell and tube
Water content
L
150
170
190
210
240
270
Water flow
m³/h
73
95
116
148
173
191
Pressure drop
kPa
75
70
77
66
56
56
Max. pressure
kPa
1000
1000
1000
1000
1000
1000
Connection type
Victaulic coupling
Water inlet/outlet pipe dim.
mm
150
150
150
200
200
200
Unit length
mm
3550
3550
3550
3600
3600
3600
Unit width
mm
1220
1220
1220
1420
1440
1440
Unit height
mm
1730
1800
1900
2000
2020
2020
Shipping weight
kg
2500
2580
2950
3550
4050
4150
Running weight
kg
2700
2820
3220
3870
4420
4550
Safety protection device
The following safety devices are equipped as standard.
High pressure protection(High pressure switch & high pressure sensor)
Low pressure protection(Low pressure switch & low pressure sensor)
Compressor thermal protection
High discharge temperature on the compressor
Phase monitor; Star/Delta transition failed
Low-pressure ratio; Low oil level protection
Interrupter protection; Overload compressor protection
Over-voltage & low- voltage protection
Sensor malfunction protection
Contactor malfunction protection
Freeze protection
Note:
Nominal cooling capacities are based on following conditions: Chilled water inlet/outlet temperature 12/7
℃
(53.6F/44.6F);
Cooling water inlet/outlet temperature 30/35
℃
(86F/96F).
The design fouling factor for both evaporator and condenser are 0.086m2
•℃
/kW (0.0005ft2 F.hr/Btu).