Flooded type water cooled screw chiller (PCB Control)
24
8.
Operating range
Content
Running range
Chilled Leaving Water Temperature
5
℃~
15
℃
Cooling Entering water Temperature
20
℃
~35
℃
Water flow volume
Rating flow volume±20%
Max inlet/outlet water Temp. difference
8
℃
Fouling factor (m
2.
℃
/kW)
0.086
Voltage tolerance
Rating Voltage±10%
Phase tolerance
±2
%
Power supply frequency
Rating frequency±2%
Evaporator max working pressure on water side
1.0MPa
Compressor max. start count
4 times/h
Environment quality
High corrosive environment and high
humidity should be avoided.
Drainage system
The height of water drainage should not be
higher than the base of the unit on the spot
Normal operation ambient temperature
-10
℃
~45
℃
Storage and transport temperature
-15
℃~
50
℃
Applicable altitude range
:
No more than 1000m
MWSC_A-FB3
evaporator
Minimum
Maximum
Entering temperature at start-up
9°C
22°C
Leaving temperature during operation
5°C
15°C
Entering/leaving temperature difference at full load
3.8°C
7.1°C
MWSC_A-FB3
condenser
Minimum
Maximum
Entering temperature at start-up
19°C
33°C
Leaving temperature during operation
23°C
40°C
Entering/leaving temperature difference at full load
3.8°C
7.1°C
Note:
(1) For low-temperature applications, where the leaving water temperature is below 4°C, freeze protection switch will work unit
stop.
(2) If the temperature leaving the condenser is below 19°C,the unit will stop and warning
(3) Ambient temperatures: During storage and transport of the
MWSC_A-FB3
units. Including by container) the minimum
and maximum permissible temperatures is -20°C ~ 46°C(R134a);
Changes water temperature curve in the operation