Water Drainage
MLCAC-UTSM-2010-10
102
Installation
For Four-way cassette
4.4 Convergent drainage
1). The number of indoor units should be as small as possible to prevent the traverse main pipe overlong.
2). Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
3). Selecting the diameter
Number of connecting indoor units
→
Calculate drainage volume
→
Select the diameter
Calculate allowed volume =Total cooling capacity of indoor units (HP)×2 (l/ hr)
Allowed volume(lean 1/50) (l/ hr)
I.D. (mm)
Thick
Hard PVC
∽
≤
14
¢
25
3.0
Hard PVC
14
<
∽
≤
88
¢
30
3.5
Hard PVC
88
<
∽
≤
334
¢
40
4.0
Hard PVC
175
<
∽
≤
334
¢
50
4.5
Hard PVC
334
<
∽
¢
80
6.0
4.5 Drainage test
1). Drainage without drain pump
After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly.
2). Drainage with drain pump
Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water into the water receipt plate through the water inlet.
Turn on the power to Cooling operation. Check the pump’s operation and switch on the Water Level Switch. Check the pump’s sound
and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally.
Summary of Contents for MLCAC-UTSM-2010-10
Page 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2011 ...
Page 2: ......
Page 4: ......
Page 16: ...Service Space MLCAC UTSM 2010 10 12 Four way Cassette Type 3 Service Space ...
Page 22: ...Field Wiring MLCAC UTSM 2010 10 18 Four way Cassette Type 10 Field Wiring Wiring chart ...
Page 23: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 19 ...
Page 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Duct Type 9 The Specification of Power ...
Page 33: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 29 10 Field Wiring ...
Page 34: ...Field Wiring MLCAC UTSM 2010 10 30 Duct Type Air conditioner link circuit ...
Page 37: ......
Page 40: ...Service Space MLCAC UTSM 2010 10 58 Ceiling Floor Type 3 Service Space ...
Page 47: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 65 10 Field Wiring ...
Page 48: ...Field Wiring MLCAC UTSM 2010 10 66 Ceiling Floor Type ...
Page 51: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 69 2 Service Space ...
Page 54: ...Wiring Diagrams MLCAC UTSM 2010 10 72 Outdoor Units MOUB 48HDN1 R ...
Page 60: ...Troubleshooting MLCAC UTSM 2010 10 78 Outdoor Units For Duct type ...
Page 89: ...MLCAC UTSM 2010 10 Control Control 107 Part 5 Control 1 Controller 108 ...