MLCAC-UTSM-2010-10
Troubleshooting
Outdoor Units 81
3. Alarm lamp quick-flash
4. Defrost lamp flashes
Alarm lamp flashes at 5Hz
Judge: Water level switch is abnormal.
Select the cooling mode to make water pump work for a few minutes, then check
whether the system can run normally
Replace indoor PCB
Trouble is solved
Yes
No
Check whether the water drain pipe is blocked
No
Solve to make the water can flow
fluently
Yes
Check whether the water pump can work normally
Replace water pump
No
Yes
Defrost lamp flashes
Judge: Mode conflicts malfunction
Turn the indoor unit to heating mode or turn off the unit
Summary of Contents for MLCAC-UTSM-2010-10
Page 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2011 ...
Page 2: ......
Page 4: ......
Page 16: ...Service Space MLCAC UTSM 2010 10 12 Four way Cassette Type 3 Service Space ...
Page 22: ...Field Wiring MLCAC UTSM 2010 10 18 Four way Cassette Type 10 Field Wiring Wiring chart ...
Page 23: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 19 ...
Page 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Duct Type 9 The Specification of Power ...
Page 33: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 29 10 Field Wiring ...
Page 34: ...Field Wiring MLCAC UTSM 2010 10 30 Duct Type Air conditioner link circuit ...
Page 37: ......
Page 40: ...Service Space MLCAC UTSM 2010 10 58 Ceiling Floor Type 3 Service Space ...
Page 47: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 65 10 Field Wiring ...
Page 48: ...Field Wiring MLCAC UTSM 2010 10 66 Ceiling Floor Type ...
Page 51: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 69 2 Service Space ...
Page 54: ...Wiring Diagrams MLCAC UTSM 2010 10 72 Outdoor Units MOUB 48HDN1 R ...
Page 60: ...Troubleshooting MLCAC UTSM 2010 10 78 Outdoor Units For Duct type ...
Page 89: ...MLCAC UTSM 2010 10 Control Control 107 Part 5 Control 1 Controller 108 ...