Additional Refrigerant Charge
MLCAC-UTSM-2010-10
100
Installation
3. Additional Refrigerant Charge
Caution
a)
Refrigerant cannot be charged until field wiring has been completed.
b) Refrigerant may only be charged after performing the leak test and the vacuum pumping.
c) When charging a system, care shall be taken that its maximum permissible charge is never exceeded,
in view of the danger of liquid hammer.
d) Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the
appropriate refrigerant is charged.
e) Refrigerant containers shall be opened slowly.
f) Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the
diameter and the length of the liquid side pipe of the outdoor unit/indoor unit.
R(g) D(mm)
L(m)
φ
6.4
Φ
9.5
Φ
12.7
Less than 5m (One-way)
—
—
—
Added Refrigerant When
Over 5m(One-way)
11g/m×(L-5) 30g/m×(L-5)
60g/m×(L-5)
Remark:
R (g): Additional refrigerant to be charged
L (m): The length of the refrigerant pipe (one-way)
D (mm): Liquid side piping diameter
Summary of Contents for MLCAC-UTSM-2010-10
Page 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2011 ...
Page 2: ......
Page 4: ......
Page 16: ...Service Space MLCAC UTSM 2010 10 12 Four way Cassette Type 3 Service Space ...
Page 22: ...Field Wiring MLCAC UTSM 2010 10 18 Four way Cassette Type 10 Field Wiring Wiring chart ...
Page 23: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 19 ...
Page 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Duct Type 9 The Specification of Power ...
Page 33: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 29 10 Field Wiring ...
Page 34: ...Field Wiring MLCAC UTSM 2010 10 30 Duct Type Air conditioner link circuit ...
Page 37: ......
Page 40: ...Service Space MLCAC UTSM 2010 10 58 Ceiling Floor Type 3 Service Space ...
Page 47: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 65 10 Field Wiring ...
Page 48: ...Field Wiring MLCAC UTSM 2010 10 66 Ceiling Floor Type ...
Page 51: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 69 2 Service Space ...
Page 54: ...Wiring Diagrams MLCAC UTSM 2010 10 72 Outdoor Units MOUB 48HDN1 R ...
Page 60: ...Troubleshooting MLCAC UTSM 2010 10 78 Outdoor Units For Duct type ...
Page 89: ...MLCAC UTSM 2010 10 Control Control 107 Part 5 Control 1 Controller 108 ...