MLCAC-UTSM-2010-10
Troubleshooting
Outdoor Units 89
9. P2 malfunction
P2 display
Low pressure protection
Judge 1: The wiring between the low pressure switch and main control
board is connected well or correctly
Judge 2: Whether the low pressure switch is broken
Connect it well
Method: Short connect the low pressure switch socket, check
whether the system can run normally
Check whether the refrigerant system is ok
Yes
No
Judge 3: Check whether the outdoor ambient temperature is too low
Yes
Stop the unit
No
Judge 4: The refrigerant of the system is leakage
Yes
Method: Connect the pressure gauge to the gauge joint of the system,
check whether the pressure is lower than 0.14MPa
Leak hunting: Charge nitrogen or refrigerant to
the system, if the leakage is serious, there will
be distinct gas leakage “cici” sound; if the
leakage is slight, use the suds (mixture of water
and abluent is also ok if it can make bubble) or
electronic leak detector.
Judge 5: The refrigerant pipe is blocked
Yes
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize and
charge the refrigerant again
No
Replace outdoor main board
No
No
Yes
Replace low pressure switch
Summary of Contents for MLCAC-UTSM-2010-10
Page 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2011 ...
Page 2: ......
Page 4: ......
Page 16: ...Service Space MLCAC UTSM 2010 10 12 Four way Cassette Type 3 Service Space ...
Page 22: ...Field Wiring MLCAC UTSM 2010 10 18 Four way Cassette Type 10 Field Wiring Wiring chart ...
Page 23: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 19 ...
Page 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Duct Type 9 The Specification of Power ...
Page 33: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 29 10 Field Wiring ...
Page 34: ...Field Wiring MLCAC UTSM 2010 10 30 Duct Type Air conditioner link circuit ...
Page 37: ......
Page 40: ...Service Space MLCAC UTSM 2010 10 58 Ceiling Floor Type 3 Service Space ...
Page 47: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 65 10 Field Wiring ...
Page 48: ...Field Wiring MLCAC UTSM 2010 10 66 Ceiling Floor Type ...
Page 51: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 69 2 Service Space ...
Page 54: ...Wiring Diagrams MLCAC UTSM 2010 10 72 Outdoor Units MOUB 48HDN1 R ...
Page 60: ...Troubleshooting MLCAC UTSM 2010 10 78 Outdoor Units For Duct type ...
Page 89: ...MLCAC UTSM 2010 10 Control Control 107 Part 5 Control 1 Controller 108 ...