R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
80 Control system
2.3 MGBT-F120W/DN1
5.5 Electric control schematic diagram of the unit
5.5.1 Electric control diagram of the main unit and subordinate units (see Attached Drawing (I))
5.5.2 Schematic diagram of connection and communication of the main unit and subordinate units (see Attached Drawing (II))
5.5.3 Indicating diagram of electric control of main control board (see
Fig.5-4
)
11 10
9
8 7
6 5
4
3
2
1
19
20
21
22
23
24
25
26
12
14
15
16
27
28
29
6
17
18
13
No
Detail information
1 Detection of current of the compressor B (protection code P5)
2
Detection of current of the compressor A (protection code P4)
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the
compressor is detected to exceed protective value set (33A for constant speed compressor), it will be shut down and
re-started after 3 min.
3
T4: outdoor ambient temperature sensor (fault code E7)
T3B: pipe temperature sensor of the condenser B (fault code E6 and protection code P7)
T3A: pipe temperature sensor of the condenser A (fault code E5 and protection code P6)
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit.
Start outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the modular unit detects the temperature of the outdoor pipe T3A or T3B
of the system exceeds the protective temperature 65
。
C, the corresponding system will be shut down. And it will be
re-started up, after the temperature drops below the recovery temperature 60
。
C. Another system will be not affected.
3) T4, T3B and T3A: when the temperature sensor is detected to suffer open circuit or short circuit, fault alarm will
occur.
●
When the main unit suffer fault of temperature sensor: the main unit and subordinate units will be shut down.
●
When the subordinate unit suffer fault of temperature sensor: the unit will be shut down, but other subordinate units
will not be affected.
4 Reserved
5
Unit outlet water temperature sensor (fault code E4)
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water
temperature.
Adjustment range of constant speed capability: ON and OFF.
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...