R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
120 Troubleshooting
10) Total outlet water temperature sensor malfunction
11) The unit outlet water temperature sensor malfunction
Total outlet water temp. sensor
malfunction
The unit outlet water temp. sensor
malfunction
The circuit of total outlet water temp.
sensor is broken.
Inform the customer service center.
PCB mistakes to alarm.
The circuit of total outlet water
temp. sensor is shorten.
Replace PCB.
Fixed joint.
Replace temp. sensor.
Replace temp. sensor.
The joint of total outlet water temp.
sensor is loose.
Inform
the
customer service
center.
PCB mistakes to alarm.
The unit’s circuit of outlet water
temp. sensor is broken.
Replace PCB.
Replace temp. sensor.
The unit’s circuit of outlet water
temp. sensor is shorten.
Replace temp. sensor.
The unit’s joint of outlet water
temp. sensor is loose.
Fixed joint.
Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...