R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
114 Troubleshooting
3. Typical malfunction solutions
1) High pressure and discharged temperature protection
Yes
No
No
Yes
Yes
Yes
Yes
Yes
High pressure and
discharged protection.
No
No
Yes
Yes
Yes
Yes
No
No
No
No
High pressure protection.
Blower stops rotating or rotates in
reversed direction in cooling mode;
water pump is not open or the flow.
EXV cannot start running.
Pressure controller is broken
or the joint is loose.
Fin heat exchanger in cooling mode is
too dirty or aged; or too heavy
encrustation in shell-tube for heating.
EXV, capillary and filter are
dirty, blocking.
Discharge
temp.
protection.
See
the
analysis
of
discharge temp. protection
malfunction.
Inspect fan motor and
capacitor
(1phase)
or
start up the water pump.
Replace EXV or coil.
Replace press controller,
fixed joint.
Clean heat exchanger.
Replace EXV, capillary
and filter.
There is air and filled refrigerant
too much in system.(Generally
occur after maintenance.)
PCB make mistakes to alarm.
Empty, vacuuming and
append refrigerant if
necessary.
Check if it happened
frequently, if yes, please
replace PCB.
Inform
the
customer
service center.
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...