MCAC-ATSM-2014-09 R410a tropical air-cooled scroll chiller unit 60Hz
Control system 79
15
Water flow detection (fault code of the main unit E0) is only valid for the main unit but invalid for subordinate units.
1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. If
abnormal water flow occurs the third time, the main unit board will display fault code E0 (off-power recovery is needed),
and the wired controller will display fault code E0 (fault is displayed only after 3 detection).
2) Subordinate unit: (water flow detection will not be done).
16 (reserved port)
17 Electronic expansion valve of the system B
18
Electronic expansion valve of the system A
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
19
Auxiliary electric heater
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-230V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45
℃
, the switch
will be closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than
50
℃
, the switch will be opened, and the auxiliary electric heater will stop working.
20
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
21
Compressor of the system B;
Neutral wire;
Four-way valve of the system B;
Neutral wire.
22
Numerical code tube.
1) In case of stand-by, the address of the module is displayed;
2) In case of normal operation, 10. is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
23
Compressor of the system A;
Neutral wire;
Four-way valve of the system A;
Neutral wire.
24
Outdoor fan A, controlled by T4;
Neutral wire;
Outdoor fan B, controlled by T4;
Neutral wire;
25 Reserved port
26 Reserved port
27 Input of transformer, 220-230V AC current. (only valid for the main unit)
28
Input of three-phase four-wire power supply (fault code E1)
Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be 120º
among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be
displayed. When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase
dislocation of power supply are detected only in the early period after the power supply is connected, and they are not
detected while the unit is in operation.
29 Output of transformer
Faults
When the main unit suffers faults, the main unit stops operating, and all other units also stop running. When
the subordinate unit suffers faults, only the unit stops operating, and other units are not affected.
Protection
When the main unit is under protection, only the main unit stops operating, and other units keep running.
When the subordinate unit is under protection, only the unit stops operating, and other units are not affected.
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...