R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
94 Control system
e
、
Save
(
See the
②
key in the Fig.4-29
)――
Save the current settings or the modified settings.
f
、
Modify(See the
③
key in the Fig.4-29)
――
Press this key the parameter of selected period become
changeable, and then click
“
Save
”
. Press the key again, all parameters in this period become unchangeable.
See Fig. 4-33.
Fig.4-33
Select the setting Period, click “Modify”, all parameter will become changeable status, see Fig. 4-34.
Fig.4-34
g
、
Delete key (See the
④
key in the figure)
――
select a Period and click the key, the current selected
Weekly Timing setting period could be deleted. Click the key, window as Fig. 4-35 shows, click
“
OK
”
to
delete Period. Successful delete the Period, message box as Fig. 4-36 will show.
Fig.4-35 Fig.4-36
(
1
)
Detail procedures of add a new Weekly Timing Schedule:
a
、
Select a wired controller: By clicking the
“
System diagram for weekly timing AC
”
wired controller icon at
the left side in the wired controller, or by selecting the wired controller at the drop-down box of
“
KJR
Address
”
.
b
、
Detail parameter for setting weekly timing schedule:
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...