MCAC-ATSM-2014-09                                                                                                  R410a tropical air-cooled scroll chiller unit 60Hz 

Content                                                                                                                                                                                                              1 

. PREFACE 

Along  higher  quality  building  environment  and  more  sophisticated  building  function,  there  is  now  a  greatly 
demand  for  system  expansion  for  a  flexible  air-condition  system  capable  of  finer  air-conditioning,  thus 
increasing importance of individual air-conditioning systems. On the other hand, due to social significance of 
environmental  and  energy  problems,  elements  such  as  energy-efficiency  and  low  maintenance  are  still 
strongly desired.   

As professional supplier of air condition appliance and service, Midea air condition permanently aims at 
"providing an solution to regulating the optimal environmental temperature "and brings customers with 
comfortable and agreeable environment whenever and wherever possible.

 

Midea, one of the holders of the Digital scroll technology manufacture, launched out the digital Scroll System 
in 2002, has now enhanced the R410A with the digital scroll system special for high ambient used that 
features capacity up to 1040kW. 

This publication contains a variety of information  related to the design and installation of this new unit. We 
hope this information will serve to deepen your understanding of the system, and will help you to efficiently 
develop its highly evolved characteristics. 

 
 

Technical Division 

Global Sales Company of Midea CAC Group 

Member of Midea Group 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for MGBT-D25W/DN1

Page 1: ...a air condition permanently aims at providing an solution to regulating the optimal environmental temperature and brings customers with comfortable and agreeable environment whenever and wherever poss...

Page 2: ...E 86 PART 3 107 1 MALFUNCTION PROTECTION CODES 108 2 TROUBLES AND SOLUTIONS 112 PART 4 123 1 TRANSPORTATION AND FOUNDATION INSTALLATION 124 2 WATER SYSTEM INSTALLATION 131 3 INSTALLATION OF WATER SYST...

Page 3: ...look drawing MGBT F180W DN1 24 2 PIPE CONNECTION DRAWING 26 2 1MGBT F25W DN1 MGBT D25W DN1 MGBT F30W DN1 MGBT D30W DN1 26 2 2 MGBT F60W DN1 27 2 3 MGBT F120W DN1 28 2 4 MGBT F180W DN1 29 3 REFRIGERATI...

Page 4: ...F30W DN1 4 MGBT D30W DN1 5 MGBT F60W DN1 Tube and shell 6 MGBT F120W DN1 7 MGBT F180W DN1 Design Serial Number Refrigerant type N1 R410A Omit for R22 Power Supply R 380 415V 3N 50Hz D 220V 3N 60Hz Ou...

Page 5: ...TSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 5 1 3 External Appearance 1 MGBT F120W DN1 MGBT F25W DN1 MGBT D25W DN1 MGBT F30W DN1 MGBT D30W DN1 MGBT F60W DN1 MGBT F18...

Page 6: ...unit can combine 16 separate module equal and less than 60kw or 8 module 120kw Cooling heating capacity can increase step by step by 5kW per each time within 25kW 960kW meanwhile each separate module...

Page 7: ...module only weighs 380kg 6 Back up function When unit is failed If the master unit fails all the units will stop If one slave unit fails this unit will stop but the others will keep running When the...

Page 8: ...rigerant Refrigeration system Electrical controller no Maximum combinations Digital Constant MGBT D25W DN1 Cooling Heating 1 1 R410A 2 1 16 MGBT F25W DN1 Cooling Heating 0 2 R410A 2 1 16 MGBT D30W DN1...

Page 9: ...urrent 2 A 25 3 Heating kW 9 2 Heating rated current A 24 7 Max Input consumption kW 14 7 13 7 Max Current A 43 7 39 9 Refrigerant Type R410A Refrigerant control EXV Weight kg 3 0 2 Condenser Air side...

Page 10: ...ection for compressor overload 8 Outlet and inlet water temperature difference protection 9 Compressor discharge temperature protection 10 Water flow cut off protection 11 Sensor malfunction protectio...

Page 11: ...33 96 Heating kW 9 8 Heating rated current A 27 7 Max Input consumption kW 14 7 13 7 Max Current A 43 7 39 9 Refrigerant Type R410A Refrigerant control EXV Weight kg 3 0 2 Condenser Air side Air side...

Page 12: ...n for compressor overload 8 Outlet and inlet water temperature difference protection 9 Compressor discharge temperature protection 10 Water flow cut off protection 11 Sensor malfunction protection Sou...

Page 13: ...2 54 5 Max Current A 87 2 164 7 Refrigerant Type R410A R410A Refrigerant control EXV capillary throttle Weight kg 6 5 2 6 5 4 Condenser Air side Air side heat exchanger type Fin coil Quantity of fan m...

Page 14: ...ction for compressor overload 8 Outlet and inlet water temperature difference protection 9 Compressor discharge temperature protection 10 Water flow cut off protection 11 Sensor malfunction protection...

Page 15: ...consumption kW 73 3 Max Current A 218 2 Refrigerant Type R410A Refrigerant control EXV capillary throttle Weight kg 6 2 6 Condenser Air side Air side heat exchanger type Fin coil Quantity of fan motor...

Page 16: ...on for compressor overload 8 Outlet and inlet water temperature difference protection 9 Compressor discharge temperature protection 10 Water flow cut off protection 11 Sensor malfunction protection So...

Page 17: ...3 8 2 0 875 4 1 MGBT F30W DN1 60 220 3 198 242 42 70 153 18 1 2 0 875 4 1 MGBT D30W DN1 60 220 3 198 242 42 70 153 110 18 1 13 8 2 0 875 4 1 MGBT F60W DN1 60 220 3 198 242 90 100 267 31 28 2 2 1 7 4 2...

Page 18: ...t 60Hz MCAC ATSM 2014 09 1 11 Outlook drawing MGBT F25W DN1 MGBT D25W DN1 MGBT D30W DN1 MGBT F30W DN1 Front view Top view Model Unit A B C D E F MGBT F D 25W DN1 MGBT F D 30W DN1 mm 1514 841 1865 115...

Page 19: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 19 No Name 1 Top cover 2 Air outlet 3 Air inlet 4 Water outlet 5 Water inlet 6 Electric control box...

Page 20: ...t 60Hz MCAC ATSM 2014 09 1 12 Outlook drawing MGBT F60W DN1 Front view Top view Model Unit A B C D E F G H I J K MGBT F60W DN1 mm 2000 900 1880 350 1420 225 1500 506 530 930 450 inch 78 74 35 4 74 13...

Page 21: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 21 No Name 1 Top cover 2 Air outlet 3 Air inlet 4 Water outlet 5 Compressor 6 Electric control box 7 Water inlet...

Page 22: ...unit 60Hz MCAC ATSM 2014 09 1 13 Outlook drawing MGBT F120W DN1 Front view Side view Top view Anchor hole Model Unit A B C D E F G H MGBT F120W DN1 mm 2000 1685 2080 350 1420 506 1550 1586 inch 78 74...

Page 23: ...2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 23 No Name 1 Top cover 2 Condenser 3 Compressor 4 Evaporator 5 Electric control box Air inlet 6 Water outlet 7 Water inlet 8...

Page 24: ...croll chiller unit 60Hz MCAC ATSM 2014 09 1 14 Outlook drawing MGBT F180W DN1 Front view Model unit A B C D E F G H MGBT F180W DN1 Mm 2850 2000 2110 3470 2156 506 1888 2388 inch 112 2 78 74 83 07 136...

Page 25: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 25 No Name 1 Top cover 2 Compressor 3 Evaporator 4 Water outlet 5 Electric control box 6 Water inlet 7 Condenser...

Page 26: ...MGBT F25W DN1 MGBT D25W DN1 MGBT F30W DN1 MGBT D30W DN1 The table below describes the symbols Symbol Symbol explanation Symbol Symbol explanation Stop valve Y shaped filter Pressure gauge Thermometer...

Page 27: ...ity tables 27 2 2 MGBT F60W DN1 The table below describes the symbols Symbol Symbol explanation Symbol Symbol explanation Stop valve Y shaped filter Pressure gauge Thermometer Water flow switch Circul...

Page 28: ...09 2 3 MGBT F120W DN1 The table below describes the symbols Symbol Symbol explanation Symbol Symbol explanation Stop valve Y shaped filter Pressure gauge Thermometer Water flow switch Circulating pum...

Page 29: ...ty tables 29 2 4 MGBT F180W DN1 The table below describes the symbols Symbol Symbol explanation Symbol Symbol explanation Stop valve Y shaped filter Pressure gauge Thermometer Water flow switch Circul...

Page 30: ...ressure cylinder A Low pressure cylinder B 4 way valve A 4 way valve B Condenser Evaporator Double pipe heat exchanger Fan Water outlet Water inlet EXV EXV Capillary Capillary 3 2 MGBT F60W DN1 Each m...

Page 31: ...w pressure cylinder B 4 Way valve A Fan A EXV Capillary EXV Capillary Fan B 4 Way valve B Compressor A low pressure cylinder A Unit 2 Unit 1 3 4 MGBT F180W DN1 Each module has six compressors with thr...

Page 32: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 Wiring Diagrams 4 1 MGBT F25W DN1 MGBT D25W DN1 MGBT F30W DN1 MGBT D30W DN1...

Page 33: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 33 4 2 MGBT F60W DN1...

Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...

Page 35: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 35 4 4 MGBT F180W DN1...

Page 36: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 Networking Communication wiring diagram 5 1 MGBT F25W DN1 MGBT D25W DN1 MGBT F30W DN1 MGBT D30W DN1...

Page 37: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 37 5 2 MGBT F60W DN1...

Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...

Page 39: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 39 5 4MGBT F180W DN1...

Page 40: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 6 Expolde view 6 1 MGBT F25W DN1...

Page 41: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 41 5 36 35 34 33 32 31 30 29 28 27 26 37 38 39 40 41 42 43 44 45 46 47 48...

Page 42: ...ces of electrical 1 9 Output pipe ass y of unit A 1 26 Drainage pan holder 2 10 Four way valve ass y of unit A 1 27 Electronic control box door 1 11 Input pipe ass y II of unit B 1 28 Welding parts wa...

Page 43: ...ed speed compressor 2 42 Middle partition plate 1 23 Base 1 43 Top cover 1 24 Base ass y 1 44 Sealed board 1 25 electronic control box assembly of Air cooled module 1 45 Rear Cover 1 25 1 Outdoor cont...

Page 44: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 37 36 35 34 33 32 31 30 29 28 27 26 5 38 39 40 41 42 43 44 45 46 47 48 49...

Page 45: ...left seal plate condenser 1 26 Fixed speed compressor 1 9 Output pipe ass y of unit A 1 27 Drainage pan holder 2 10 Four way valve ass y of unit A 1 28 Electronic control box door 1 11 Input pipe ass...

Page 46: ...Digital compressor 1 43 Middle partition plate 1 23 Base 1 44 Top cover 1 24 Chassis Parts 1 45 Sealed board 1 25 electronic control box assembly of Air cooled module 1 46 Rear Cover 1 25 1 Outdoor co...

Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...

Page 48: ...nents of the left seal plate condenser 1 25 12 Mounting plate with pieces of electrical 1 9 A machine component output tube casing 1 26 Drainage pan holder 2 10 A four way valve assembly machine 1 27...

Page 49: ...peed compressor 2 42 Middle partition plate 1 23 Base 1 43 Top cover 1 24 Base ass y 1 44 Sealed board 1 25 Air cooled electronic control box assembly module 1 45 Rear Cover 1 25 1 Outdoor control boa...

Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...

Page 51: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 51 25 1 25 2 25 3 25 5 25 6 25 7 25 8 25 9 25 10...

Page 52: ...ing parts water tray 1 11 Enter the pipe component II B 1 30 Electronic control box mounting plate 2 12 B unit 4 way valve ass y 1 31 A condenser components 1 13 Suction pipe ass y A 1 32 Cover 1 14 D...

Page 53: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 53 6 5 MGBT F60W DN1 46...

Page 54: ...p 2 26 Pole 4 9 Evaporator input pipe ass y 1 27 Electric box door 1 10 Evaporator input pipe ass y 1 28 Suction pipe ass y A 1 11 Cover 1 29 Suction pipe ass y B 1 12 Cover 1 30 4 way valve ass y A 1...

Page 55: ...ontrol box 1 40 Three phase asynchronous motor 2 21 2 Wire joint 3 41 Mid horizontal support 2 21 3 Transformer 1 42 Motor bracket ass y 4 21 4 Wire joint 1 43 Condenser seal connector 1 21 5 AC conta...

Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...

Page 57: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 57 Change to this one...

Page 58: ...r 1 12 8 Wire joint 4P 1 48 Evaporator connection pipe ass y of unit A1 of four way valve 1 12 9 Terminal block 6 48 1 Pressure controller 1 12 10 Terminal block 1 49 Four way valve ass y of unit B2 1...

Page 59: ...y 3 33 1 Electronic expansion valve 1 64 Pipe temp sensor ass y 4 34 Four way valve ass y of unit B1 1 65 Pipe temp sensor ass y 1 34 1 Four way valve set 1 66 Discharge temp controller 4 34 2 Pressu...

Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...

Page 61: ...ular reinforcement 12 13 I panel fasteners 10 53 Trunking II 1 14 Tube fixed plate III 12 54 II trunking cover 1 15 Block III electronic control box installed 2 55 Four way valve assembly 1 16 Rear Pa...

Page 62: ...nchronous motor 5 76 Compressor 6 30 Three phase asynchronous motor 1 77 Input pipe ass y of evaporator unit B 1 31 Motor bracket bonding parts 12 78 I fixed plate throttle parts 2 32 Strengthen the b...

Page 63: ...N1 MGBT D25W DN1 64 1 2 MGBT F30W DN1 MGBT D30W DN1 66 1 3 MGBT F60W DN1 68 1 4 MGBT F120W DN1 70 1 5 MGBT F180W DN1 72 2 CONTROL SYSTEM 74 2 1 MGBT F25W DN1 MGBT D25W DN1 MGBT D30W DN1 MGBT F30W DN1...

Page 64: ...4 8 49 31 52 8 75 29 68 9 02 28 00 9 30 26 29 9 77 24 24 10 25 21 87 10 77 8 00 34 57 8 74 32 46 9 01 30 54 9 29 28 78 9 58 27 06 10 06 24 97 10 56 22 55 11 09 9 00 35 55 8 83 33 35 9 10 31 34 9 38 29...

Page 65: ...2 8 23 30 85 8 66 34 42 9 18 39 45 9 91 43 00 16 79 6 12 21 07 6 95 24 88 7 72 27 73 8 39 30 24 8 84 33 69 9 37 38 54 10 12 44 00 16 47 6 24 20 69 7 09 24 45 7 88 27 29 8 57 29 80 9 02 33 13 9 56 37 8...

Page 66: ...31 80 9 70 30 00 10 00 28 17 10 50 25 97 11 03 23 43 11 58 8 00 37 04 9 40 34 78 9 69 32 72 9 99 30 84 10 30 28 99 10 82 26 76 11 36 24 16 11 92 9 00 38 09 9 49 35 73 9 79 33 58 10 09 31 62 10 40 29 7...

Page 67: ...76 33 46 9 22 37 34 9 78 42 79 10 56 43 00 18 22 6 52 22 86 7 40 26 98 8 23 30 08 8 94 32 80 9 41 36 54 9 98 41 81 10 77 44 00 17 86 6 65 22 44 7 55 26 53 8 39 29 61 9 12 32 32 9 60 35 94 10 18 41 04...

Page 68: ...9 40 60 00 20 00 56 34 21 00 51 95 22 05 46 85 23 15 8 00 74 09 18 80 69 57 19 38 65 44 19 98 61 68 20 60 57 98 21 63 53 51 22 71 48 32 23 85 9 00 76 18 18 98 71 46 19 57 67 16 20 18 63 24 20 80 59 51...

Page 69: ...18 82 75 85 19 95 86 93 21 55 43 00 37 00 13 30 46 42 15 11 54 81 16 79 61 10 18 25 66 63 19 21 74 23 20 36 84 92 21 99 44 00 36 28 13 57 45 58 15 42 53 88 17 13 60 14 18 62 65 65 19 60 73 00 20 78 83...

Page 70: ...68 40 95 103 89 43 00 93 71 45 15 8 00 148 17 36 66 139 13 37 80 130 88 38 96 123 36 40 17 115 96 42 18 107 03 44 29 96 65 46 50 9 00 152 35 37 02 142 92 38 16 134 32 39 34 126 48 40 56 119 02 42 59...

Page 71: ...39 91 173 85 43 10 43 00 74 00 26 59 92 85 30 22 109 62 33 58 122 21 36 50 133 27 38 42 148 46 40 72 169 84 43 98 44 00 72 57 27 13 91 17 30 83 107 76 34 26 120 27 37 24 131 30 39 20 146 01 41 55 166...

Page 72: ...02 61 43 155 84 64 50 140 56 67 72 8 00 222 26 54 99 208 70 56 69 196 33 58 45 185 04 60 26 173 94 63 27 160 54 66 43 144 97 69 75 9 00 228 53 55 53 214 38 57 24 201 48 59 01 189 72 60 84 178 53 63 8...

Page 73: ...260 78 64 65 43 00 111 00 39 89 139 27 45 33 164 43 50 36 183 31 54 74 199 90 57 62 222 69 61 08 254 76 65 97 44 00 108 85 40 70 136 75 46 25 161 64 51 39 180 41 55 86 196 95 58 80 219 01 62 33 250 1...

Page 74: ...perature sensor of the condenser A fault code E5 and protection code P6 1 T4 if there is one system that requires starting outdoor fans the fans are started through electric control of the unit Start...

Page 75: ...nits the subordinate unit module suffering communication fault will be shut down Less units will be detected by the wired controller which may display EA and in the meanwhile the indicator lamp of the...

Page 76: ...e switch will be opened and the auxiliary electric heater will stop working 19 PUMP Attention the control port value of the pump actually detected is ON OFF but not 220 240V control power supply so sp...

Page 77: ...A and B gears and control the unit through T4 2 T3B and T3A when the electric control of the modular unit detects the temperature of the outdoor pipe T3A or T3B of the system exceeds the protective te...

Page 78: ...t down Less units will be detected by the wired controller which may display EA and in the meanwhile the indicator lamp of the wired controller will flash Restart 3 minutes later after malfunction be...

Page 79: ...in start up state always in the process of operation 2 In case of refrigerating or heating shutdown the pump will be shut down 2 minutes after all modules stop operating 3 In case of shutdown under th...

Page 80: ...ection code P7 T3A pipe temperature sensor of the condenser A fault code E5 and protection code P6 1 T4 if there is one system that requires starting outdoor fans the fans are started through electric...

Page 81: ...ischarge temperature switch and high pressure switch of the system in series 13 Inlet water temperature sensor T62 TBH2 fault code EF 14 Shell and tube low temperature ant freeze sensor T61 TBH1 fault...

Page 82: ...way valve of the system A Phase B of power 24 Outdoor fan A controlled by T4 Phase B of power Outdoor fan B controlled by T4 Phase B of power 25 Reserved port 26 Reserved port 27 Input of transformer...

Page 83: ...electric control of the modular unit detects the temperature of the outdoor pipe T3A or T3B of the system exceeds the protective temperature 65 C the corresponding system will be shut down And it will...

Page 84: ...or T61 TBH1 fault code Eb 15 Water flow detection fault code of the main unit E0 is only valid for the main unit but invalid for subordinate units 1 Main unit if abnormal water flow occurs for the fir...

Page 85: ...24 Outdoor fan A controlled by T4 Neutral wire Outdoor fan B controlled by T4 Neutral wire 25 Reserved port 26 Reserved port 27 Input of transformer 220 230V AC current only valid for the main unit 28...

Page 86: ...er serial port The system default selection is COM1 the software will checkout the available serial ports in the computer automatically and will list them at the Optional Table 4 When login on you mus...

Page 87: ...Fig 4 3 will be display while PASSWORD error the window shows as Fig 4 4 Fig 4 3 Fig 4 4 7 In case the password error time exceed 6 times i e the 7th times password error the window show as Fig 4 5 an...

Page 88: ...wired controllers could be connected to the computer This kind of wired controller could be connected to the module group of 25KW 30KW 60KW 120KW 180KW etc Total 16 sub modules could be jointed to a...

Page 89: ...he operation of the selected refrigeration system 5 Query system parameter The in Fig 4 7 Press this key to query the selected refrigeration system the current operating parameter will be display 6 Qu...

Page 90: ...ig 4 12 Fig 4 13 If input an old password error window as Fig 4 14 will show if the new passwords be input do not match the message box as Fig 4 15 will display Fig 4 14 Fig 4 15 Click Re login window...

Page 91: ...Save to finish the wired controller modification see Fig 4 21 KJR Name could not empty or pure blank character string pure blank charter string is composed by space and tab Fig 4 21 c Delete wired con...

Page 92: ...sub module Select the sub module which wanted to delete select the wanted delete sub module at the drop down box of Sub module address and click Delete to finish this operation 3 Schedule management...

Page 93: ...od Time On Time Off Timing Status Control Mode Turn on quantity Mode set and Setting temp d Timing ON OFF key for controlling the weekly timing wired controller See the key in the figure when Weekly T...

Page 94: ...changeable status see Fig 4 34 Fig 4 34 g Delete key See the key in the figure select a Period and click the key the current selected Weekly Timing setting period could be deleted Click the key windo...

Page 95: ...or not Control Mode Automatically drive up mode Mode set Operation mode Cooling Heating Water Pump Setting temp Setting temp Note The ON OFF time of the weekly timing can not be at the same time point...

Page 96: ...riod at the drop down box of Period c Detail parameter for modifying weekly timing schedule Time On Turn on time when Time On selecting then means do not turn on the unit display as Fig 4 44 Fig 4 44...

Page 97: ...ring see Fig 4 48 Clear all record in the Menu See Fig 4 49 could be used to delete all error records Fig 4 47 Fig 4 48 Fig 4 49 4 Communication parameter includes Serial port set and History set See...

Page 98: ...User guidance and About See Fig 4 55 Fig 4 55 1 Owner s manual Software application manual i e this manual About some relevant software information Wired controller lock unlock Provided that the sele...

Page 99: ...hat the selected wired controller in lock status the key would display Unlock KJR see Fig 4 61 once successful unlock the wired controller the message box see Fig 4 62 would display then the key displ...

Page 100: ...red controller refrigeration system In the querying a message box see Fig 4 65 would pop up Fig 4 65 If successful query the system a message box see Fig 4 66 will pop up and note you query success an...

Page 101: ...orresponding error code will show in the System Query Provided that protection function perform the corresponding protection code will show in the System Query if move the mouse arrow to the these cod...

Page 102: ...vertime see Fig 4 75 would display Provided that sub module hasn t been selected namely the sub module address and the corresponding name are empty a message box see Fig 4 76 would pop up The query pe...

Page 103: ...parameter could be queried a message box See Fig 4 81 will display informing more parameters are empty Fig 4 79 Fig 4 80 Fig 4 81 System operate set 1 During setting message boxes as following might...

Page 104: ...ox as Fig 4 87 would show Fig 4 87 2 Set wired controller separately Do not tick the Uniformly Set Select the wanted set wired controller refrigeration system from the wired controller address column...

Page 105: ...message box as Fig 4 93 will display during the setting Once successful setting a message box as Fig 4 94 will display to inform you Successful System Set whereas Failed System set as Fig 4 95 will d...

Page 106: ...lect the Device Manager in the Hardware as Fig 4 98 3 The window Device Manager will be showed up after clicking the Device Manager as Fig 4 99 Fig 4 99 Fig 4 100 4 Click the icon in front of the Port...

Page 107: ...ooting 107 Part 3 TROUBLE SHOOTING PART 3 107 1 MALFUNCTION PROTECTION CODES 108 1 1 MGBT F25W DN1 MGBT D25W DN1 MGBT D30W DN1 MGBT F30W DN1 108 1 2 MGBT F60W DN1 109 1 3 MGBT F120W DN1 110 1 4 MGBT F...

Page 108: ...out any on line module unit 14 ED Wired controller and module unit communication error 15 Ed 1 hour consecutive 4 times PE protection 16 EE Wired controller and computer communication error 17 EF Inle...

Page 109: ...xchanger 13 EC Wired controller did not find out any on line module unit 14 Ed 1 hour consecutive 4 times PE protection happens 15 EF Inlet water temp sensor error 16 P0 High pressure or air discharge...

Page 110: ...t exchanger 13 EC Wired controller did not find out any on line module unit 14 Ed 1 hour consecutive 4 times PE protection 15 EF Inlet water temp sensor error 16 P0 High pressure or air discharge temp...

Page 111: ...e heat exchanger 13 EC Wired controller did not find out any on line module unit 14 Ed 1 hour consecutive 3 times PE protection 15 EF Inlet water temp sensor error 16 P0 High pressure or discharge tem...

Page 112: ...nd outlet and adjust the water flow volume Air or other non condensing gas still in the system Discharge gas from refrigerant charging inlet Re vacuum the system if necessary Scaling in water side of...

Page 113: ...tch error If the switch is defective please replace a new one Excessive low air suction pressure Add the refrigerant Clean the heat exchanger Check the EXV capillary filter Abnormal noise gives out fo...

Page 114: ...loose Fin heat exchanger in cooling mode is too dirty or aged or too heavy encrustation in shell tube for heating EXV capillary and filter are dirty blocking Discharge temp protection See the analysi...

Page 115: ...ase replace PCB EXV cannot be opened The EXV capillary and filter are dirty blocked and ice blocked PCB mistakes to alarm Inform the customer service center Refrigerant is few Inspect leakage in syste...

Page 116: ...maintenance PCB mistakes to alarm Yes Yes The fin of heat exchanger is dirty or aged in cooling mode Clean heat exchanger Replace PCB Replace temp sensor Check the fan motor capacitor 1 phase Replace...

Page 117: ...tion to analysis Yes Yes Yes No No No Water flow is lower The outlet water temp sensor or inlet water temp sensor brought drifting when collect temp PCB mistakes to alarm Replace temp sensor Replace P...

Page 118: ...otector is broken PCB mistakes to alarm No Yes Adjust connecting wire No No No Yes Check power supply Yes Yes Replace phase lack protector Replace PCB Inform the customer service center No power input...

Page 119: ...is less flow head Designed the water pipe inner dimension is too less Open the pump or change inspect the power supply or control circuit of pump Yes Yes Yes Yes Yes Yes Yes Yes Open the valve Replac...

Page 120: ...ervice center PCB mistakes to alarm The circuit of total outlet water temp sensor is shorten Replace PCB Fixed joint Replace temp sensor Replace temp sensor The joint of total outlet water temp sensor...

Page 121: ...lace PCB Replace temp sensor The unit s circuit of inlet water temp sensor is shorten Replace temp sensor The unit s joint of inlet water temp sensor is loose Fixed joint No Yes Yes Yes Yes Yes No No...

Page 122: ...nction Ambient temp sensor malfunction Inform the customer service center PCB mistakes to alarm The circuit of ambient temp sensor is broken Replace PCB Replace temp sensor The circuit of ambient temp...

Page 123: ...WATER PIPES 131 2 2 WATER QUALITY 132 2 3 INSTALLATION REGULATION GUIDE FOR TARGET FLOW CONTROLLER 133 3 INSTALLATION OF WATER SYSTEM PIPELINE 134 3 1 MGBT F25W DN1 MGBT D25W DN1 MGBT D30W DN1 MGBT F3...

Page 124: ...should be provided with an at least 50mm thick wood block cloth or hard paper Any person is not allowed to stand below the unit when lifting it t ation should not be more than 15 when carrying the uni...

Page 125: ...mm thick wood block cloth or hard paper to avoid damages to the unit Lifting angle The position should be provided with an at least 50mm thick wood block cloth or hard paper to avoid damages to the un...

Page 126: ...nit is installed where the flowing speed of air is high such as on the exposed roof the measures including sunk fence and Persian blinds can be taken to prevent the turbulent flow from disturbing the...

Page 127: ...Input of airflow A B D C Input of airflow Input of airflow E MGBT F25W DN1 MGBT D25W DN1 MGBT D30W DN1 MGBT F30W DN1 A B D C Input of airflow Input of airflow E Input of airflow Input of airflow MGBT...

Page 128: ...of airflow Input of airflow A B D C Input of airflow Input of airflow E MGBT F180W DN1 The recommend space parameter Module Installation space mm A B C D E MGBT F25W DN1 1500 2000 1500 2000 8000 MGBT...

Page 129: ...irection A and D should not be less than 11 8inch 300mm and the space between adjacent modular units in the direction B and C should not be less than 23 6inch 600mm If the spaces mentioned above canno...

Page 130: ...ion By means of the 0 59 inch 15mm diameter installation holes on the steel frame of the unit base the unit can be fastened on the foundation through the spring damper See upper pictures Schematic dia...

Page 131: ...ipes The pipelines should be free of any impurity and all chilled water pipes must conform to local rules and regulations of pipeline engineering 2 1 Basic requirements of connection of chilled water...

Page 132: ...servation including inlet pipes and flanges of the heat exchanger 13 The outdoor chilled water pipelines should be wrapped with an auxiliary heating belt for heat preservation and the material of the...

Page 133: ...the flow switch b To avoid electric shock and damages to the devices the power supply should be cut off when wires are connected or adjustment is done c When wiring connection is conducted adjustment...

Page 134: ...diameter mm inch Combined units Total water pipe inner diameter mm inch Combined units Total water pipe inner diameter mm inch 1 DN40 1 1 2 1 DN100 4 1 DN65 2 1 2 2 2 2 DN100 4 3 DN65 2 1 2 3 3 4 4 D...

Page 135: ...recommended installation mode No n module No n 1 address No 1 module No n 1 module No n 2 address No 0 address less than 16 modules Drill dead hole at the position and move the total effluent temperat...

Page 136: ...pipeline Total water outlet temperature sensor Water outlet Water inlet Electric control box Installation of multi module water system pipeline 1 Installation mode I recommended installation mode No n...

Page 137: ...No 1 module No n 1 module No n 2 address No 0 address Pump installation mode A less than 16 modules Water flow switch Drill dead hole at the position and move the total effluent temperature sensor at...

Page 138: ...ion and move the total effluent temperature sensor at No 0 address to the position Water flow switch Pump installation mode A less than 16 modules n the module quantity max 16 5 Installation mode V in...

Page 139: ...ontrol box Installation of multi module water system pipeline 1 Installation mode I recommended installation mode No 1 unit No 0 address main unit No n unit n 8 No n 1 unit No 2n 3 address No 2n 1 add...

Page 140: ...ss No 2n 1 address No 1 address No 2n 4 address No 2n 2 address Pump n the module quantity max8 Notices 1 For installation of multi module the most modules should be not more than 8 modular units 2 Fo...

Page 141: ...ch Drill dead hole at the position and move the total effluent temperature sensor at No 0 address to the position No 1 unit No 0 address main unit No n unit n 5 No n 1 unit No 3n 4 address No 3n 1 add...

Page 142: ...air please contact the maintenance center 4 2 Power supply specification Items Model Outdoor power supply Wiring Power supply Manual switch Fuse MGBT F25W DN1 MGBT F30W DN1 220V 3N 60Hz 70A 50A 25mm 2...

Page 143: ...provided should be obtained through power circuit breakers provided by the user to ensure that all voltages on the nodes of the provided power supply circuit are released when the circuit breakers ar...

Page 144: ...located out of easy reach of non professional maintenance personnel to avoid mal operation and improve safety 9 Connection of control wires of water flow switches the wire leads prepared by the user...

Page 145: ...epage Switch Water pump Contactor Over charge relay 220V 3N 60HZ Contactor winding Over charge relay 0 Main unit PCB A B C N 220V 3N 60HZ P1 P2 XT4 Two water pumps one is reserved Creepage Switch Wate...

Page 146: ...ply power to the heating belt and pre heat the compressor Inadequate pre heating may cause damages to the compressor Set up the wired controller See details of the manual concerning setting contents o...

Page 147: ...or requirements External physical is meeting for requirement Pipe diameter is meeting for requirement The length of system is meeting for requirement Water discharge is meeting for requirement Water q...

Page 148: ...diagram or the faults caused by water breaking while the unit is in operation should be the user s responsibility Do not re start the unit within 10 min after the unit is shut down during trial run W...

Page 149: ...ABOUT MAINTENANCE 150 1 1 MAINTENANCE FOR MAIN COMPONENTS 150 1 2 WATER QUALITY INSPECTION AND DIRT REMOVE 150 1 3 WINTER SHUTDOWN 150 1 4 REPLACING PARTS 150 1 5 REFRIGERATION SYSTEM 150 1 6 DISASSEM...

Page 150: ...ent water system from being eroded or re absorption of scale In case of using cleaning agent adjust the density of the agent cleaning time and temperature according to the scale settlement condition A...

Page 151: ...or needs to be disassembled 1 Cut off the power supply of unit 2 Remove power source connection wire of compressor 3 Remove suction and discharge pipes of compressor 4 Remove fastening screw of compre...

Page 152: ...t leaks please contact your supplier Water checks Inspection checks and actions Remark Check the water condition Drain the water from the air release plug If the water is dirty please replace all wate...

Page 153: ...9 R410a tropical air cooled scroll chiller unit 60Hz Wired Controller 153 Part 6 Wired controller PART 6 153 1 WIRED CONTROLLER KJRM 120D BMK E STANDARD 154 2 WIRED CONTROLLER KJR 120A MBTE OPTIONAL 1...

Page 154: ...isplay when the electric auxiliary heating water function is operated 4 Check Display when check function is operated 5 Anti freezing Display when the main unit ambient temperature is below 2 to remin...

Page 155: ...during spot check they are used to read over 0 15 units 15 Cancel key During setting parameters press this key to cancel setting After timing setting and then long press this key 3 seconds to cancel...

Page 156: ...ent setting is the minute of Timer 1 On press the or to adjust press key when finished the LCD will display as the following 1 TIMER OFF This time the hour of the clock will flash it means the current...

Page 157: ...imer 2 Whether press OK key Whether press key During any period of timing setting to press OK key then the timing period has been set will be effective only when the On and Off of one timing period ha...

Page 158: ...lock press the or to adjust press OK key when finished or wait for 7 seconds to be effective during the setting process press the Cancel key then it will exit without saving Note For getting the corre...

Page 159: ...erefore 16 wired controller could be parallel at most Operation method Press Constraint two button for 3 seconds to enter the wired remote address selection Press or key to select the desired value 7S...

Page 160: ...r or protection 1 outlet water temperature Tou current of the compressorIb 8 anti frozen temperature T6 outdoor pipe temperatureT3B 6 current of the compressor IA electronic expansion valv openingFA 1...

Page 161: ...nvironment temperature of wired controller 10 C 43 C 3 Operating RH of wired controller RH 40 RH90 1 8 Main functions of this wired controller as follows 1 Touch key operation 2 LCD displays operation...

Page 162: ...nd transmits the shutdown information Operation mode button In the power off status press this button to select the operation mode This function is invalid at power on status Modes shifted sequence as...

Page 163: ...e compressor IA Setting temperature Ts outdoor ambient temperatures T4 outdoor pipe temperature T3b outdoor pipe temperature T3A The wired controller only displays the last fault information and the p...

Page 164: ...erature setting mode Press this button for minus clock or time at wire clock or time setting mode 12 13 PAGEUP DOWN button to spot check the operation parameters of unit in the main menu 14 HYSTERESIS...

Page 165: ...ing indicator of wired controller is light unit is start to run and display running status at wired controller Press this button once again unit will stop running Operation procedure of system informa...

Page 166: ...d and some error must press the ALARM CLEAR button and then be cleared after the errors are cleared The details can refer to the error code table If this type of error comes out frequently then need t...

Page 167: ...N PROCEDURE Installation procedure Outdoor unit 00 Outdoor unit 01 Outdoor unit 02 Outdoor unit 15 Wired Controller 00 Use PQE to connect with the outdoor units NOTE Please connect the attached shorte...

Page 168: ...ease use 3 cord with shielding wire for connection The wire length depends on the specific situation in the installation wired controller 5 bit terminal base If it is under the host computer network c...

Page 169: ...RESS Set Period 2 start hour ADDRESS OK ADDRESS or Set Period 2 start minute ADDRESS OK ADDRESS or Y Y OK Y OK Y OK Y Y OK Set Period 2 end hour ADDRESS ADDRESS or Set Period 2 end minute ADDRESS ADDR...

Page 170: ...uently It should operate the wired controller to start up the unit after 3 minutes later or all units are shutdown 4 The wired controller and the outdoor unit must connect with the same power supply p...

Page 171: ...d on line Connect to LonWorks network by twisted pair wire and the communication mode is nonpolar Provide with a LonWorks control interface for BMS by network variables complying with LonMark standard...

Page 172: ...e Support Direct Memory reading and writing by the LNS network management tool 7 Communication port Communication port 8 Size 31 9cm X 25 1cm X 6 1cm 3 4 External dimension There are three installatio...

Page 173: ...NET WORK LSQ LONWORKS BMS SYSTEM RS485 P Q E Caution This system adopts the manner of shared network variable to manage A C system which cannot access the appointed A C within central A C system unti...

Page 174: ...46 9 245 10 244 11 243 12 242 13 241 14 240 15 Corresponding address of wired controller Caution First power on it needs to set the gateway property as the actual conditioner then connect the gateway...

Page 175: ...iSetMode nviSetTemp nviTempDiff nviClrErrorState nvoOutTemp nvoOnNum nvoRunNum nvoSystemMode nvoCool TempHi nvoCoolTempLo nvoHeatTempHi nvoHeatTempLo Air cooled Modular system Input network variable o...

Page 176: ...tting heat mode of Air cooled Modular system setting the min value of the total water outlet temperature This network variable only is effective when the nciType being set as 0 otherwise this network...

Page 177: ...the temperature paramete rs of unit which address is 1 Water outlet temperature of unit Water inlet temperature of unit This variable is only effective when the nciType being set as 0 Anti Freezing t...

Page 178: ...rrent 1 means the Compressor A current of unit which address is 1 Compressor B current of unit n means the address of the unit nvoCompBCurrent 1 means the Compressor B current of unit which address is...

Page 179: ...Accessories Item Name of accessory Type Qty Shape Usage 1 Installation and owner s manual 1 Installation and using instruction 2 The total outlet water temperature test kit LSQWRF65M A C ZL 10 1 Insp...

Page 180: ...318 83 1 041 12 66 943 20 12 635 52 3 191 84 1 007 11 63 252 21 12 05 53 3 069 85 0 974 10 59 784 22 11 496 54 2 952 86 0 942 9 56 524 23 10 971 55 2 841 87 0 912 8 53 458 24 10 473 56 2 734 88 0 883...