background image

Safety 

Precautions

 Page 9

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

brazing process.  

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

procedures shall be used. However, it is important that best practice is followed since flammability is a 

consideration. The following procedure shall be adhered to:

Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 

circuit by cutting or brazing.   

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed 

with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 

oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 

with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 

finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 

work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 

place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 

ventilation available.

 

 

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check shall also take into account the effects of aging or 

continual vibration from sources such as compressors or fans.

9.Cabling

12.Removal and evacuation

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure

that contamination of different refrigerants does not occur when using charging equipment. Hoses or 

lines shall be as short as possible to minimise the amount of refrigerant contained in them. 

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Under no circumstances shall potential sources of ignition be used in the searching for or detection 

of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

Summary of Contents for MDDF-16

Page 1: ...DEHUMIDIFIER Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new machine Make sure to save this manual for future reference...

Page 2: ...ance Table of Contents Control Panel Features 12 Other features 15 Clean the grille and case 18 Clean the bucket 18 Troubleshooting Tips 19 Clean the air filter 18 When not using the unit for long tim...

Page 3: ...the unit Do not use the machine near flammable gas or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during oper...

Page 4: ...been damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut o to avoid damage to the machine due to lightning Do not run cord under carpeting Do not c...

Page 5: ...of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehu...

Page 6: ...manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appl...

Page 7: ...able material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flamma...

Page 8: ...supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing t...

Page 9: ...ions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The fo...

Page 10: ...g order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered r...

Page 11: ...prior notice Preparation rear front rear front rear front control panel control panel shoes dryer cover shoes dryer pipe drain hose outlet drain hose outlet drain hose outlet power cord buckle power c...

Page 12: ...to help prevent moisture damage The dehumidifier must be operated in an enclosed area to be most effective Close all doors windows and other outside openings to the room A dehumidifier operating in a...

Page 13: ...s Then press pad to operate the desired settings For panel H Indicator Function Indicator Function Timer ON light Timer OFF light Bucket full light Air purifier light Low fan speed light Med fan speed...

Page 14: ...fan control to Normal Note The turbo button is disabled in Dryer mode the Self clean Air purifier or Anti mould functions Pressing the turbo button for more than 3 seconds enables the Self clean funct...

Page 15: ...midity sensor error Unplug the unit and plug it back in If error repeats call for service ES Temperature sensor error Unplug the unit and plug it back in If error repeats call for service P2 Bucket is...

Page 16: ...on will also be cancelled There are two ways to remove collected water 1 Use the bucket When the unit is off if the bucket is full the unit will beep 8 times on some models and the Full Water indicato...

Page 17: ...the drain hose Select the desired humidity setting and fan speed on the unit for continuous draining to start 2 Continuous draining Note When the continuous drain feature is not being used remove the...

Page 18: ...urely seated for the dehumidifier to operate The air filter behind the front grille should be checked and cleaned at least every two weeks or more often if necessary NOTE DO NOT RINSE OR PUT THE FILTE...

Page 19: ...upright as it should be The floor surface is not level Hose to connector or hose connection may be loose Intend to use the bucket to collect water but the back drain plug is removed This is normal The...

Page 20: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Reviews: